WDR-480 series 480W Single Output Industrial DIN RAIL Power Supply 1/2 Features : ESingle and two phase wide input range 180~550VAC Built-in active PFC circuit compliance to EN61000-3-2 E High efficiency 93% and low power dissipation E Protections: Short circuit / Overload / Over voltage / Over temperature E Cooling by free air convection E Can be installed on DIN rail TS-35/7.5 or 15 E UL 508(industrial control equipment)approved E EN61000-6-2(EN50082-2) industrial immunity level E Built-in DC OK relay contact E 100% full load burn-in test E 3 years warranty E SPECIFICATION MODEL OUTPUT WDR-480-24 WDR-480-48 DC VOLTAGE 24V 48V RATED CURRENT 20A 10A CURRENT RANGE 0 ~ 20A 0 ~ 10A RATED POWER 480W 480W RIPPLE & NOISE (max.) Note.2 100mVp-p 150mVp-p VOLTAGE ADJ. RANGE 48 ~ 55V O1.0% 24 ~ 28V VOLTAGE TOLERANCE Note.3 O1.0% LINE REGULATION O0.5% LOAD REGULATION O1.0% SETUP, RISE TIME 800ms, 150ms/400VAC POWER FACTOR (Typ.) EFFICIENCY (Typ.) 2000ms, 150ms/230VAC at full load 16ms / 230VAC at full load Note.6 180 ~ 550VAC FREQUENCY RANGE INPUT O1.0% 18ms / 400VAC HOLD UP TIME (Typ.) VOLTAGE RANGE O0.5% 254 ~ 780VDC 47 ~ 63Hz PFU0.84/400VAC PFU0.84/230VAC 92% 93% AC CURRENT (Typ.) INRUSH CURRENT (Typ.) 1.6A/400VAC 4A/230VAC COLD START 50A LEAKAGE CURRENT <3.5mA / 530VAC 105 ~ 130% rated output power Protection type : Constant current limiting, unit will shut down after 3 sec. ,auto-recovery after 1 minute if the fault condition is removed OVERLOAD PROTECTION OVER VOLTAGE OVER TEMPERATURE 56 ~ 65V 29 ~ 33V Protection type : Shut down o/p voltage, auto-recovery after 1 minute if the fault condition is removed 95J O5J (TSW) detect on heatsink of power switch Protection type : Shut down o/p voltage, recovers automatically after temperature goes down FUNCTION DC OK REALY CONTACT RATINGS (max.) 60Vdc/0.3A, 30Vdc/1A, 30Vac/0.5A resistive load WORKING TEMP. Note.5 -30 ~ +70J (Refer to "Derating Curve") WORKING HUMIDITY ENVIRONMENT STORAGE TEMP., HUMIDITY TEMP. COEFFICIENT VIBRATION SAFETY STANDARDS SAFETY & WITHSTAND VOLTAGE ISOLATION RESISTANCE EMC (Note 4) EMC EMISSION EMC IMMUNITY MTBF OTHERS DIMENSION PACKING NOTE 20 ~ 95% RH non-condensing -40 ~ +85J, 10 ~ 95% RH O0.03%/J (0 ~ 50J) Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 UL508 approved, IEC60950-1 CB approved by SIQ, design refer to GL I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC O/P-DC OK:0.5KVAC I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25J/ 70% RH Compliance to EN55022 (CISPR22), EN61204-3 Class B, EN61000-3-2,-3 Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A approved 112.8K hrs min. MIL-HDBK-217F (25J) 85.5*125.2*128.5mm (W*H*D) 1.7Kg; 8pcs/14.6Kg/0.9CUFT 1. All parameters NOT specially mentioned are measured at 400VAC input, rated load and 25J of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. 5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended. 6. Derating may be needed under low input voltage. Please check the derating curve for more details. File Name:WDR-480-SPEC 2012-07-30 WDR-480 series 480W Single Output Industrial DIN RAIL Power Supply Mechanical Specification Unit:mm 128.5 Case No.984B 125.2 TB2 + 1 2 DC OK 85.5 DC OK +V ADJ TB1 1 2 3 4 5 6 3 Terminal Pin No. Assignment (TB1) 35 Pin No. 1 2 3 Assignment FG AC/L2 AC/L1 Terminal Pin No. Assignment (TB2) Pin No. 1,2 3,4 5,6 ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15 Assignment DC OUTPUT +V DC OUTPUT -V Relay Contact Block Diagram DC OK I/P EMI FILTER & RECTIFIERS POWER SWITCHING PFC CIRCUIT RECTIFIERS & FILTER +V -V O.C.P. U.V.P. FG PFC CONTROL O.L.P. PWM & PFC CONTROL DETECTION CIRCUIT O.V.P. DC OK Relay Contact Contact Close PSU turns on / DC OK. Contact Open PSU turns off / DC Fail. Contact Ratings (max.) 30V/1A resistive load. File Name:WDR-480-SPEC 2012-07-30 WDR-480 series 480W Single Output Industrial DIN RAIL Power Supply Derating Curve Output derating VS input voltage 100 100 90 80 80 70 LOAD (%) LOAD (%) 60 40 20 -30 60 50 40 0 10 20 30 40 50 AMBIENT TEMPERATURE (J) 60 70 (VERTICAL) 180 190 200 250 290 310 360 400 450 490 500 520 550 INPUT VOLTAGE (VAC) 60Hz File Name:WDR-480-SPEC 2012-07-30