System Manual
Edition
SIRIUS Classic
Industrial Controls
siemens.com
05/2017
Safety guidelines
This manual contains notices which you should observe to ensure your own personal safety, as well as to pro-
tect the product and connected equipment. These notices are highlighted in the manual by a warning triangle
and are marked as follows according to the level of danger:
Safety note
Contains important information for the acceptance test and the safety-related use of the product.
Danger
Indicates that death, severe personal injury or substantial property damage will result if proper precautions
are not taken.
Warning
Indicates that death, severe personal injury or substantial property damage can result if proper precautions
are not taken.
Warning
Indicates that minor personal injury or property damage can result if proper precautions are not taken.
Caution
indicates that property damage can result if proper precautions are not taken.
Important
Draws your attention to particularly important information on the product, handling the product, or to a particu-
lar part of the documentation.
Qualified personnel
Only qualified personnel should be allowed to install and work on this equipment. Qualified persons are
defined as persons who are authorized to commission, to ground, and to tag circuits, equipment, and systems
in accordance with established safety practices and standards.
Correct usage
Note the following:
Warning
This device and its components may only be used for the applications described in the catalogue or the techni-
cal descriptions, and only in connection with devices or components from other manufacturers which have
been approved or recommended by SIEMENS.
This product can only function correctly and safely if it is transported, stored, set up, and installed correctly,
and operated and maintained as recommended.
Brands
SIMATIC®, SIMATIC HMI® and SIMATIC NET® are brands of SIEMENS AG.
Some other designations used in these documents are also brands; the owner's rights may be violated if they
are used by third parties for their own purposes.
Siemens AG
Division Digital Factory
PO Box 48 48
90026 NÜRNBERG
GERMANY
A5E40534713002A/RS-AA/001
05/2017 Subject to changes
Copyright © Siemens AG 2001
All rights reserved
Copyright SIEMENS AG 2001 All rights reserved
The reproduction, transmission or use of this document or its con-
tents is not permitted without express written authority. Offenders
will be liable for damages. All rights, including rights created by pat-
ent grant or registration of a utility model or design, are reserved.
Disclaimer of liability
We have checked this manual to ensure that its contents are correct
and applicable in relation to the hardware and software it describes.
Despite all our endeavors, however, discrepancies cannot be wholly
excluded and so we cannot guarantee complete correctness and
applicability. However, the data in this manual are reviewed regularly
and any necessary corrections included in subsequent editions. Sug-
gestions for improvement are welcomed.
SIEMENS AG
Technical Assistance
Breslauer Str. 5
D-90766 Fürth
Telephone: +49 (911) 895-5900 (8°° - 17°° CET)
Fax: +49 (911) 895-5907
E-mail: technical-assistance@siemens.com
Internet: www.siemens.com/sirius/technical-assistance
SIRIUS System Manual
A5E40534713002A/RS-AA/001 i
Contents
1 System overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
1.1 Specifications/regulations/approvals . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
1.2 Product range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
1.3 System features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-10
1.3.1 Environmental requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-11
1.3.2 Environmental protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-11
1.4 Components and combinations . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-12
1.5 Mounting methods and terminal systems . . . . . . . . . . . . . . . . . . . . . . . 1-16
1.5.1 Mounting the equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-16
1.5.2 Screw-type terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-18
1.5.3 Cage Clamp terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-19
1.5.4 Connection cross-sections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-21
1.6 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-22
1.6.1 Communication-capable low-voltage switching technology . . . . . . . . . . . . . . 1-22
1.6.2 Parameterization of PROFIBUS-DP and bus-capable low-voltage switching devices . . 1-23
1.6.3 Actuator-sensor interface (AS-Interface) . . . . . . . . . . . . . . . . . . . . . . . . 1-24
1.6.4 SIRIUS NET Communication-capable motor starter . . . . . . . . . . . . . . . . . . 1-29
2 3RV1 Circuit breaker/MSP 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
2.1 Specifications/regulations/approvals . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
2.2 Device description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
2.2.1 General description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
2.2.2 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
2.2.3 Information on configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
2.3 Application and areas of use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
2.3.1 Motor protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
2.3.2 Transformer protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
2.3.3 Starter protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
2.3.4 Motor protection with overload relay function . . . . . . . . . . . . . . . . . . . . . 2-14
2.3.5 Switching direct current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-15
2.3.6 Main and emergency stop switches . . . . . . . . . . . . . . . . . . . . . . . . . . 2-15
2.4 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
2.4.1 Attachable accessories: Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
2.4.2 Auxiliary contacts 3RV19 01-.., alarm switch 3RV19 21-111 and auxiliary
release 3RV19 .2-.... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-17
2.4.3 Motorized remote-control mechanism 3RV19 .6-.... . . . . . . . . . . . . . . . . . . 2-22
2.4.4 Disconnecting/isolator module 3RV19 .8-1A . . . . . . . . . . . . . . . . . . . . . . 2-25
2.4.5 Thru-the door rotary operators 3RV19 .6-.. . . . . . . . . . . . . . . . . . . . . . . . 2-27
2.4.6 Terminals for "Combination Motor Controller Type E" in acc. with UL 508 . . . . . . . 2-33
2.4.7 Enclosures and mounting accessories . . . . . . . . . . . . . . . . . . . . . . . . . 2-34
2.4.8 Busbar adapter 8US1 (Fastbus system) . . . . . . . . . . . . . . . . . . . . . . . . 2-39
2.4.9 Isolated 3-phase busbar system . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-43
2.4.10 Link module for connection to a contactor . . . . . . . . . . . . . . . . . . . . . . . 2-46
2.5 Mounting and connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-47
2.5.1 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-47
2.5.2 Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-48
2.5.3 Device circuit diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-50
2.6 Dimensional drawings (dimensions in mm) . . . . . . . . . . . . . . . . . . . . . . 2-52
SIRIUS System Manual
ii A5E40534713002A/RS-AA/001
2.7 Technical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-63
2.7.1 General specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-63
2.7.2 Permissible rating of approved devices for North America, u s . . . . . . . . . . . . . 2-66
2.7.3 Short-circuit breaking capacity Icn in acc. with IEC 60 947-2 . . . . . . . . . . . . . . 2-68
2.7.4 Limiter function with standard devices for 500 V AC and 690 V AC in acc.
with IEC 60 947-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-70
2.7.5 Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-70
2.7.6 Installation guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-71
2.8 Application notes for the use of 3RV1 downstream from frequency converters/
inverter with pulsing voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-72
2.8.1 Influences of high frequency currents upon the thermal overload release . . . . . . . 2-72
2.8.2 Other possible influences . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-73
3 3RT1 Contactors/ 3RH1 Control relays . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3.1 Specifications/regulations/approvals . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
3.1.1 Utilization categories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-3
3.1.2 Positively driven operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
3.1.3 Safe isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
3.1.4 Explanation of terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
3.2 Device description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
3.2.1 Coil systems S00 to S3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12
3.2.2 Short-circuit protection for SIRIUS contactors . . . . . . . . . . . . . . . . . . . . . 3-13
3.2.3 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-14
3.2.3.1 General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-14
3.2.3.2 Contact reliability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15
3.2.3.3 Electrical service life . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16
3.2.3.4 Ambient temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-20
3.3 Application and areas of use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-23
3.3.1 3RT10 contactors with 3 main contacts for switching motors . . . . . . . . . . . . . . 3-23
3.3.2 3RT14 contactors with 3 main contacts for switching resistive loads (AC-1) . . . . . . 3-24
3.3.3 3RT13 and 3RT15 contactors with 4 main contacts . . . . . . . . . . . . . . . . . . . 3-25
3.3.4 3RT16 capacitor contactors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-26
3.3.5 Contactors with an extended operating range . . . . . . . . . . . . . . . . . . . . . 3-28
3.3.5.1 Contactors with series resister (3RH11...-0LA0/3RT10...-0LA0) . . . . . . . . . . . . . . 3-28
3.3.5.2 Contactors with electronic control module frame sizes S0 to S3 (3RT10..-.X40-0LA2) . . . 3-30
3.3.5.3 Contactors with an extended operating range (3RH1122-2K.40, 3RT1017-2K.4.,
3RT102.-3K.40) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-31
3.3.6 3RH1 control relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-32
3.3.7 3RT10 contactor relays for switching motors (interface) and 3RH11 control relays
for switching auxiliary circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-33
3.3.8 3RA13 Contactor combinations for reversing . . . . . . . . . . . . . . . . . . . . . . 3-35
3.3.9 3RA14 Wye-delta combinations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-46
3.4 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-54
3.4.1 Attachable auxiliary switches for extending the auxiliary contacts . . . . . . . . . . . 3-57
3.4.1.1 Terminal markings of the contactors frame sizes S00 to S3 . . . . . . . . . . . . . . . . 3-62
3.4.1.2 Terminal markings of the contactors and control relays combined with auxiliary switch blocks 3-64
3.4.1.3 Auxiliary switches that can be attached to 3RH1 control relays . . . . . . . . . . . . . . 3-66
3.4.2 Time-delay auxiliary switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-69
3.4.2.1 Frame size S00 (3RT1916-2E, -2F, -2G) . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-69
3.4.2.2 Frame sizes S0 to S3 (3RT1926-2E, -2F, -2G) . . . . . . . . . . . . . . . . . . . . . . . . 3-71
3.4.3 Solid-state time relay blocks with semiconductor output . . . . . . . . . . . . . . . . 3-72
3.4.3.1 Frame size S00 (3RT1916-2C, -2D) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-73
3.4.3.2 Frame sizes S0 to S3 (3RT19 26-2C, -2D) . . . . . . . . . . . . . . . . . . . . . . . . . . 3-74
SIRIUS System Manual
A5E40534713002A/RS-AA/001 iii
3.4.4 Additional load module (3RT1916-1GA00) . . . . . . . . . . . . . . . . . . . . . . . 3-75
3.4.5 Coupling element for frame sizes S0 to S3 (3RH1924-1GP11) . . . . . . . . . . . . . 3-76
3.4.6 Surge suppression . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-78
3.4.7 Other accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-83
3.4.7.1 LED module for indicating contactor control (3RT19 26-1QT00) . . . . . . . . . . . . . . 3-83
3.4.7.2 Auxiliary connecting lead terminal, 3-pole for frame size S3 (3RT19 46-4F) . . . . . . . . . 3-83
3.4.7.3 EMC interference suppression module (3RT19 16-1P..) . . . . . . . . . . . . . . . . . . . 3-84
3.4.7.4 Soldering pin adapter for frame size S00 (3RT19 16-4KA.) . . . . . . . . . . . . . . . . . 3-85
3.4.7.5 Paralleling links (3RT19 .6-4B.31) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-87
3.4.7.6 Sealing cover (3RT19 .6-4MA10) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-88
3.4.7.7 Terminal covers for frame sizes S2 to S3 . . . . . . . . . . . . . . . . . . . . . . . . . . 3-89
3.5 Mounting and connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-91
3.5.1 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-91
3.5.2 Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-94
3.5.3 Changing the magnetic coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-98
3.5.4 Changing the contact pieces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-103
3.6 Dimensional drawings (dimensions in mm) . . . . . . . . . . . . . . . . . . . . . . 3-106
3.7 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-122
4 3RU11, 3RB10, 3RB12 Overload relays . . . . . . . . . . . . . . . . . . . . . . . . 4-1
4.1 Specifications/regulations/approvals . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
4.2 Device description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
4.2.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
4.2.2 Detailed device description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
4.3 Application and use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-10
4.3.1 Overload relay in the motor circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-10
4.3.2 3RU11 thermal overload relays and 3RB10 electronic overload relays . . . . . . . . . 4-15
4.3.3 3RB12 electronic overload relays . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-22
4.4 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-30
4.4.1 Electrical remote RESET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-30
4.4.2 Mechanical thru-the-door reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-31
4.4.3 Other accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-33
4.5 Mounting and connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-34
4.5.1 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-34
4.5.1.1 3RU11 thermal overload relays and 3RB10 electronic overload relays . . . . . . . . . . . . 4-34
4.5.1.2 3RB12 electronic overload relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-40
4.5.2 Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-41
4.5.3 Circuit diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-43
4.6 Dimensional drawings (dimensions in mm) . . . . . . . . . . . . . . . . . . . . . . 4-46
4.7 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-49
4.7.1 3RU11 thermal overload relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-49
4.7.2 3RB10 electronic overload relays . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-54
4.7.3 3RB12 electronic overload relays . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-61
4.7.4 Terminal bracket for stand-alone installation . . . . . . . . . . . . . . . . . . . . . . 4-66
SIRIUS System Manual
iv A5E40534713002A/RS-AA/001
5 3RA1 Fuseless load feeders/Combination starters . . . . . . . . . . . . . . . . . . 5-1
5.1 Specifications/regulations/approvals . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
5.2 Device descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
5.2.1 Mounting systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
5.2.2 Mounting kits for self-assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
5.2.3 Complete devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-5
5.3 Application and areas of use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7
5.4 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8
5.4.1 Accessories for the individual devices . . . . . . . . . . . . . . . . . . . . . . . . . 5-8
5.4.2 Accessories specifically for the SIRIUS 3RA fuseless load feeder . . . . . . . . . . . 5-8
5.4.3 Instructions for self-assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-9
5.5 Mounting and connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-18
5.5.1 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-18
5.5.2 Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-21
5.5.3 Circuit diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-23
5.6 Dimensional drawings (dimensions in mm) . . . . . . . . . . . . . . . . . . . . . . . 5-24
5.7 Technical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-28
6 3RH, 3TX, LZX Coupling links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
6.1 Specifications/regulations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
6.2 Device description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
6.2.1 Relay coupling modules versus semiconductor coupling modules . . . . . . . . . . . 6-4
6.2.2 Coupling links in two-tier and box terminal format . . . . . . . . . . . . . . . . . . . 6-5
6.2.3 Plug-in relay coupling links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6
6.2.4 Coupling links for direct attachment . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7
6.2.5 SIRIUS contactor relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7
6.2.6 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7
6.2.7 Notes on configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-8
6.2.8 Explanation of terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9
6.3 Application and areas of use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-10
6.3.1 General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-10
6.3.2 Criteria for selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-11
6.4 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-12
6.4.1 Accessories for two-tier coupling links . . . . . . . . . . . . . . . . . . . . . . . . . 6-12
6.4.2 Accessories for LZX plug-in relay coupling links . . . . . . . . . . . . . . . . . . . . . 6-13
6.5 Mounting and connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-14
6.5.1 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-14
6.5.2 Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-14
6.5.3 Device circuit diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-16
6.6 Dimensional drawings (dimensions in mm) . . . . . . . . . . . . . . . . . . . . . . . 6-20
6.7 Technical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-22
SIRIUS System Manual
A5E40534713002A/RS-AA/001 v
7 3RP20, 3RP15 Solid-state time relays . . . . . . . . . . . . . . . . . . . . . . . . 7-1
7.1 Specifications/regulations/approvals . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
7.2 Device description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3
7.2.1 Device types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3
7.2.2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-5
7.2.3 Special features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-5
7.2.4 Notes on configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-6
7.2.5 Explanation of terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-7
7.3 Application and areas of use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-8
7.3.1 Multifunction (3RP20 05 solid-state time relay) . . . . . . . . . . . . . . . . . . . . 7-8
7.3.2 Multifunctional (3RP15 05 solid-state time relay) . . . . . . . . . . . . . . . . . . . 7-12
7.3.3 On-delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-18
7.3.4 Off-delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-19
7.3.5 Clock pulse generator (3RP15 55 solid-state time relay) . . . . . . . . . . . . . . . . 7-20
7.3.6 Wye-delta function (3RP15 74/76 solid-state time relay) . . . . . . . . . . . . . . . . 7-21
7.3.7 Wye-delta function with overtravel (3RP15 60 solid-state time relay) . . . . . . . . . 7-21
7.4 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-22
7.4.1 Accessories for 3RP15 05, 3RP20 05 . . . . . . . . . . . . . . . . . . . . . . . . . 7-22
7.5 Mounting and connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-24
7.5.1 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-24
7.5.2 Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-25
7.5.3 Circuit diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-26
7.6 Dimensional drawings (dimensions in mm) . . . . . . . . . . . . . . . . . . . . . . 7-27
7.7 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-28
8 3RW3 Semiconductor motor control unit . . . . . . . . . . . . . . . . . . . . . . 8-1
8.1 Specifications/regulations/approvals . . . . . . . . . . . . . . . . . . . . . . . . . . 8-3
8.2 Device description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-5
8.2.1 Physical principles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-6
8.2.2 General device description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-10
8.2.3 Comparison of the 3RW3 semiconductor motor control unit (soft starter) with the
SIKOSTART 3RW22 and SIKOSTART 3RW34 motor control units . . . . . . . . . . . 8-14
8.2.4 Comparison of the 3RW3 semiconductor motor control unit (soft starter)
with the 3RA star-delta combination . . . . . . . . . . . . . . . . . . . . . . . . . . 8-16
8.2.5 Notes on configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-16
8.3 Application and use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-18
8.3.1 Areas of application and criteria for selection . . . . . . . . . . . . . . . . . . . . . 8-18
8.3.2 Installation guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-18
8.3.3 Overview tables: correction factors . . . . . . . . . . . . . . . . . . . . . . . . . . 8-21
8.3.3.1 3RW30/31 soft starters in a stand-alone installation . . . . . . . . . . . . . . . . . . . . . 8-21
8.3.3.2 3RW30/31 soft starters in combination with the 3RV1 circuit breaker . . . . . . . . . . . 8-22
8.3.3.3 Combining the 3RT contactor with the 3RU1 thermal overload relay and 3RW3 soft starter 8-24
8.3.3.4 Combining the 3RT contactor with the 3RB10 electronic overload relay and 3RW3 soft starter 8-26
8.3.4 Circuit example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-29
8.3.5 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-30
8.3.6 Event messages and diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-32
8.3.7 Timing diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-33
8.4 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-35
8.5 Mounting and connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-37
8.5.1 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-37
8.5.2 Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-37
8.5.3 Circuit diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-38
SIRIUS System Manual
vi A5E40534713002A/RS-AA/001
8.6 Dimensional drawings (dimensions in mm) . . . . . . . . . . . . . . . . . . . . . . . 8-41
8.7 Technical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-42
8.7.1 Control electronics/power electronics . . . . . . . . . . . . . . . . . . . . . . . . . . 8-42
8.7.2 Short-circuit protection and fuse coordination . . . . . . . . . . . . . . . . . . . . . 8-45
8.7.3 Site altitude . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-50
8.7.4 Specifications in acc. with IEC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-51
8.7.5 Specifications in acc. with NEMA . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-52
9 3RE Enclosed starter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-1
9.1 Specifications/regulations/approvals . . . . . . . . . . . . . . . . . . . . . . . . . . 9-2
9.2 Device description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-3
9.3 Application and areas of use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-5
9.3.1 The enclosed starter in motor branches . . . . . . . . . . . . . . . . . . . . . . . . . 9-5
9.3.2 Planning and operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-5
9.4 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-6
9.5 Mounting and connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-7
9.5.1 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-7
9.5.2 Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-7
9.5.3 Circuit diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-8
9.6 Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-9
9.7 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-10
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Index-1
SIRIUS System Manual
A5E40534713002A/RS-AA/001 1-1
1
System overview
Section Subject Page
1.1 Specifications/regulations/approvals 1-3
1.2 Product range 1-5
1.3 System features 1-10
1.3.1 Environmental requirements 1-11
1.3.2 Environmental protection 1-11
1.4 Components and combinations 1-12
1.5 Mounting methods and terminal systems 1-16
1.5.1 Mounting the equipment 1-16
1.5.2 Screw-type terminals 1-18
1.5.3 Cage Clamp terminals 1-19
1.5.4 Connection cross-sections 1-21
1.6 Communication 1-22
1. 6 . 1 Communication-capable low-voltage switching
technology 1-22
1. 6 . 2 Parameterization of PROFIBUS-DP and bus-capable
low-voltage switching devices 1-23
1.6.3 Actuator-sensor interface (AS-Interface) 1-24
1.6.4 SIRIUS NET Communication-capable motor starter 1-29
System overview
SIRIUS System Manual
1-2 A5E40534713002A/RS-AA/001
Introduction
SIEMENS is one of the leading manufacturers of control products. The
product range extends from devices that switch a few mA to circuit
breakers used in power distribution.
Throughout the continuing development of these products we have always
striven to ensure that requirements in terms of fundamental performance
features, electrical and mechanical service life, dimensions, and ease of
installation and maintenance are met or exceeded.
We have been able to meet the demands resulting from increased environ-
mental awareness, particularly in the last ten years or so, by developing and
using environment-friendly and recyclable materials. As a result, we have
developed modern industrial switching devices, particularly in the field of
low-voltage switchgear, that meet all the relevant demands in terms of
environment-friendliness.
Building on decades of experience, we have created a completely new
generation of circuit breakers, contactors, auxiliary contactors, overload
relays, contactor relays, time relays, and 3RW3 semiconductor motor con-
trol devices (referred to below as soft starters) under the name SIRIUS for
the large and continuously growing number of motor drives in the range up
to 250 kW (400 HP).
These new SIRIUS devices fulfill all the demands placed on them in practice
and can be used as stand-alone devices or modular components of com-
plete load feeders, or integrated in low-voltage distribution cabinets or low-
voltage switching stations.
System overview
SIRIUS System Manual
A5E40534713002A/RS-AA/001 1-3
1.1 Specifications/regulations/approvals
ALPHA/LOVAG The Low Voltage Controls and Distribution Division of Siemens AG is a
member of "Gesellschaft zur Prüfung und Zertifizierung von Niederspan-
nungsgeräten e.V. ALPHA" (Society for Testing and Certification of Low-
Voltage Equipment), Frankfurt am Main.
The responsibility of manufacturers and the high quality of products are pro-
moted by ALPHA by means of supportive procedural guidelines for testing
equipment in accordance with the currently valid standards. Providing spe-
cific conditions are fulfilled, ALPHA can also issue officially recognized
product certificates if required. As a member of LOVAG, ALPHA is also
working towards obtaining international recognition for declarations of con-
formity and certificates.
In LOVAG (Low Voltage Agreement Group), international specialists from
certification bodies and industry are working together to create a
standardized European certificate.
List of LOVAG members
ALPHA Germany
ASEFA France
ACAE Italy
CEBEC Belgium
CESI Italy
KEMA Netherlands
SEMKO Sweden
Explosion protection Motor protection devices that protect a motor installed in a potentially
explosive atmosphere against overloading must comply with certain special
requirements. These requirements are laid down in the following standards:
EN 60947-1
EN 60079-14
EN 60947-4-1
•EN 50014
EN 50019.
Certification
On July 1, 2003 a new era began in the area of explosion protection. Since
this date, within the European Union, only those devices and protection sys-
tems that have been certified for use in potentially explosive atmospheres in
accordance with directive 94/9/EU can be brought into circulation.
Only those motor protection devices that have been constructed in accor-
dance with the above-mentioned standards and which have a conformity
declaration from the manufacturer based on a prototype test certificate are
permitted to be brought into circulation within the member states of the EU.
The quality management system of the manufacturer is also subjected to
certain requirements and a "QM certificate" must be obtained for the manu-
facturer from a recognized authority.
System overview
SIRIUS System Manual
1-4 A5E40534713002A/RS-AA/001
Certification of the QM system
A certificate of approval for quality assurance production has been issued by
DMT 1) with the DMT 1) number 02 ATEX ZQS/EM, in accordance with
directive 94/9/EU.
This certificate is valid for equipment groups I and II and categories M2
and 2: Safety and control devices for electrical equipment.
Certificates
For the 3RV, 3RU, 3RB, 3UF5 and 3RN motor protection devices, the
corresponding conformity declarations and prototype test certificates for
Category 2G and partly 2D are available and can be supplied on request.
Identifying markings
All equipment must be marked in accordance with the ATEX guideline. The
ATEX identification code contains the equipment group, the approved envi-
ronment, the number of the certification authority and other technical data
that was determined from the type test.
UL/CSA Underwriters Laboratories (UL) and the Canadian Standards Association
(CSA) are authorized to grant approvals acording to US or Canadian regula-
tions and standards. These standards typically apply to the control product
as a componient and not the installation or the use of the product. It is the
responsibility of the end user of the control product to make sure each
installation complies with all of the applicable safety requirements, laws,
regulations, codes and standards (examples: N.E.C., the C.E.C. and OSHA
regulations.
1)DMT
The certification authority of the Deutschen Montan Technologie GmbH,
numbered as authority number 0158 in accordance with Article 9 of Direc-
tive 94/9/EU of the European Parliament dated March 23, 1994, certifies
that Siemens Amberg and Cham maintains a quality system for produc-
tion that satisfies Appendix IV of this directive.
System overview
SIRIUS System Manual
A5E40534713002A/RS-AA/001 1-5
1.2 Product range
SIRIUS system The SIRIUS product range consists of 3RV circuit breakers/Motor Starter
Protectors, 3RT contactors, 3RH/3RT control relays and auxiliary contacts,
3RU thermal overload relays, 3RB10/3RB12 electronic overload relays, 3RP
time relays, 3RW3 semiconductor motor control devices (referred to below
as soft starters), and combinations of these devices, which form the 3RA
load feeders (combination starters).
The individual devices are developed and built in such a way that it is very
easy to put them together to make load feeders. This is possible because
the devices are all built to work together on both an electrical and a
mechanical level.
Fig. 1-1: SIRIUS System
NSB00296
3
3
1
2
a
b
5
4
System overview
SIRIUS System Manual
1-6 A5E40534713002A/RS-AA/001
Circuit breaker (MSP) with a frame size of S00 and attachable accessories:
Fig. 1-2: Circuit breaker (MSP), accessories (frame size S00)
Circuit breakers (MSPs) with frame sizes of S0, S2, and S3 and attachable accessories:
Fig. 1-3: Circuit breakers (MSPs), accessories (frame sizes S0, S2, and S3)
Attachable accessories for frame sizes S00, S0, S2, and S3:
1.1) Transverse auxiliary switch with 1 changeover contact
1.2) Transverse auxiliary switch with 1 NO + 1 NC or 2 NO contacts
2) Lateral auxiliary switch with 2 contacts
3) Lateral auxiliary switch with 4 contacts
4) Shunt release
5) Undervoltage release
6.1) Undervoltage release with leading auxiliary contacts (S00)
6.2) Undervoltage release with leading auxiliary contacts (S0 to S3)
7) Alarm switch (S0 to S3)
8) Disconnecting module (S0 and S2)
NSB00005d
6.1
5
4
2
3
1. 2
1. 1
NSB00006d
8
3
2
7
5
4
6.2
1. 2
1. 1
System overview
SIRIUS System Manual
A5E40534713002A/RS-AA/001 1-7
Contactors with a frame size of S00 and accessories:
Fig. 1-4: Contactors, accessories (frame size S00)
1) Contactor
2) Control relay
3) Solid-state time relay block, on-delay
4) Solid-state time relay block, off-delay
5) Auxiliary switch block, time-delay
(on-delay or off-delay or wye-delta function)
6) 1-pole auxiliary switch block, infeed from above
7) 2-pole auxiliary switch block, infeed from above
8) 1-pole auxiliary switch block, infeed from below
9) 2-pole auxiliary switch block, infeed from below
10) 4-pole auxiliary switch block
(terminal markings in acc. with DIN EN 50 012 or DIN EN 50 005)
11) 2-pole auxiliary switch block, standard or electronic
type (terminal markings in acc. with DIN EN 50 005)
12) Soldering pin adapter for contactors with 4-pole auxiliary switch block
13) Soldering pin adapter for contactors and contactor relays
14) Additional load module to increase the permissible residual current
15) Surge suppressor with LED
16) Surge suppressor without LED
17) 3-phase feed-in terminal
18) Parallel link (neutral bridge), 3-pole, without terminal
19) Parallel link, 3-pole, with terminal
20) Parallel link, 4-pole, with terminal
NSB00448
15
3
4
5
6
7
8
9
10
11
14
20
19
16
12
13
1
17
18
2
System overview
SIRIUS System Manual
1-8 A5E40534713002A/RS-AA/001
Contactors with frame sizes of S0 to S3 with accessories:
Fig. 1-5: Contactors, accessories (frame sizes S0 toS3)
1) Contactor, frame size S0
2) Contactor, frame size S2
3) Contactor, frame size S3
For frame sizes S0 to S3:
4) Solid-state time relay block, on-delay
5) Solid-state time relay block, off-delay
6) Auxiliary switch block, time-delay (on- or off-delay or wye-delta function)
7) 2-pole auxiliary switch block, infeed from above
8) 2-pole auxiliary switch block, infeed from below
9) 4-pole auxiliary switch block
(terminal markings in acc. with DIN EN 50 012 or DIN EN 50 005)
10) Parallel link (neutral bridge), 3-pole, without terminal
11) Parallel link, 3-pole, with terminal
12) 2-pole auxiliary switch block, attachable on the right or left side
(terminal markings in acc. with DIN EN 50 012 or DIN EN 50 005)
13) 1-pole auxiliary switch block (a maximum of 4 can be snapped on)
14) Mechanical interlock, attachable at the side
NSB00449
4
10
5
18
17
16
11
1
12
9
6
15
14
1
8
7
13
16
19
21
20
2
21
22
23
20
3
System overview
SIRIUS System Manual
A5E40534713002A/RS-AA/001 1-9
15) Mechanical interlock, attachable at the front
16) Wiring blocks above and below (reversing mode)
17) Surge suppressor (varistor, RC element, diode combination),
attachable above or below (varies for S0 and S2/S3)
18) Coupling link for direct connection to the contactor coil
19) LED block to display contactor function
For frame sizes S2 and S3 only:
20) Terminal for contactor coil for setting up contactor combinations
21)Terminal cover for box terminals
For frame size S3 only:
22)Terminal cover for terminal end and bar connection
23)Auxiliary connecting lead terminal, 3-pole
System overview
SIRIUS System Manual
1-10 A5E40534713002A/RS-AA/001
1.3 System features
The entire SIRIUS range of devices is divided up into only four frame sizes
(S00 to 5.5 kW (7.5 HP), S0 to 11 kW (15 HP), S2 to 22 kW (40 HP), S3 to
45 kW (75 HP) at 400 V) with three different frame widths (45 mm for S00
and S0, 55 mm for S2 and 70 mm for S3) and has a uniform range of acces-
sories for all frame sizes.
Modular system The individual components of the SIRIUS range are building blocks in a
modular system that are harmonized in terms of both their frame size and
their technical specifications. This ensures that individual requirements can
be met quickly and cost-effectively.
Uniformity The devices are harmonized with regard to their ratings and their technical
specifications:
The same width ensures rapid installation.
The terminal systems are standardized, and devices with the same rated
current have the same terminals.
Performance capability All SIRIUS devices can be mounted side by side without derating in an
ambient air temperature of up to 60 °C.
Accessories All accessories, such as the auxiliary switches and surge suppressors, can
be mounted and removed without tools.
You can use link modules that connect devices both mechanically and elec-
trically to put together combinations of devices and build fuseless load
feeders.
Communication The interface of SIRIUS-control components with a high level control sys-
tem is in addition to the conventional wiring is possible over networking
systems:
AS-Interface
•PROFIBUS-DP
Using these networking systems SIRIUS-control components are incorpo-
rated in the SIEMENS automation concept Totally Integrated Automation.
Totally Integrated Automation offers the user threeway continuity in planing/
programing, data management and communication.
Safety technology SIRIUS-control components are often used in safety related installations.
With the Safety Integrated-concept, solutions ranging from safety relays up
to fail safe communication over AS-Interface or PROFIBUS-DP can be
achieved.
System overview
SIRIUS System Manual
A5E40534713002A/RS-AA/001 1-11
1.3.1 Environmental requirements
SIRIUS-control components are made for any climate and are suitable and
tested for global usage.
The related environmental requirements are described in DIN EN 60721-3-3
Important environmental requirements:
Ambient temperature: -25 to +60 °C
Relative humidity: 10 to 100 % (occasional condensation)
Additional information to the subject environmental requirements can be
found in the handbook "Switching, Protection, and Distribution in Low-Volt-
age Networks" (1994), P. 65.
1.3.2 Environmental protection
SIRIUS-control components do not contain Halogen, Asbestos, or Cadmium.
The manufacturing of SIRIUS devices complies with, as one of the very few
manufacturing locations, the stringent requirements of the EU-Öko-Audit-
Directive.
All SIRIUS devices work energy efficient and are close to being completely
recyclable.
System overview
SIRIUS System Manual
1-12 A5E40534713002A/RS-AA/001
1.4 Components and combinations
This section describes the components of the SIRIUS system and the
device combinations that are possible with these components.
Components of the SIRIUS system
The following table contains a list of the components of the SIRIUS system
together with the most important accessories:
Components Brief description/features Accessories
3RV1 circuit breakers (in
USA/Canada: Motor
Starter Protector)
- Switch and protect motors up to 100 A - Auxiliary switches (transverse,
lateral)
- Undervoltage releases
- Shunt releases
- Alarm switches
- Housing
- 3-phase busbar system
3RT10 motor contactors - Switch motors up to 45 kW (75 HP) and
currents up to 95 A
- Types: 3-pole for switching
- 4-pole, with 4NO or 2NO + 2NC contacts
- Soldering pin adapter
- Capacitor switching contactor
- -Reversing and wye-delta combinations
- Auxiliary switch blocks
- Surge suppressors
- Parallel links
- Time relay blocks
- Link modules
- Wiring blocks
3RH11 control relays - Same type of construction as the 3RT
- Basic version: 4-pole, expandable to 8 pins
by means of auxiliary switch blocks
- High contact stability (1 mA; 17 V)
3RT10/3RH11 contactor
relays
- Switch motors and auxiliary contactors with
an extended operating range (17 V to 30 V)
3RU11 overload relays -CLASS 10
- Phase loss sensitivity
- Series auxiliary contacts 1 NO + 1 NC con-
tact
- Frame size S00: repetition terminal for the
auxiliary contact and coil connection for
attachment to contactors
- Integrated, transparent and sealable cover
for the adjusting knob and test function
- Remote RESET, electrical
- Mechanical RESET
- Terminal bracket for stand-alone
installation
3RB10 overload relays - CLASS 10 and CLASS 20
- Rapid tripping operation in the event of
phase loss (< 3 s)
- Series auxiliary contacts 1 NO + 1 NC
- Low power loss, energy-saving
- Wide adjustment ranges for simple configu-
ration, selection, and less storage
- Extremely low energy requirements, approx.
50 mW
- Remote RESET, electrical
- Mechanical RESET
- Terminal bracket for stand-alone
installation
Table 1-1: Components and combinations with accessories
System overview
SIRIUS System Manual
A5E40534713002A/RS-AA/001 1-13
3RB12 overload relays - CLASS 5 to CLASS 30 can be set
- Phase loss sensitivity
- 2 outputs per 1 NO + 1 NC contact
- Integrated current transformers in all sizes
- Motor protection due to the connection of a
thermistor sensor circuit
- Internal ground fault monitoring
- Overload warning
- Remote and automatic reset possible
- High tripping accuracy
- Wide adjustment ranges
- Self-monitoring
- Summation current transformer for
external ground fault monitoring
- DC adapter
- Terminal cover
3RA1 load feeders
(combination starters)
- Load feeder (combination starter) consisting
of a circuit breaker (MSP) and contactor
- Simple assembly with link modules and
wiring blocks
- Reversing combination (link modules)
- Wye-delta combination
- Accessories for the basic devices
(contactors and circuit breakers)
- Special accessories:
Auxiliary switches connectable
from above or below
3RP20/15 solid-state
time relays
- 8 adjustable time ranges from 0.05 seconds
to 10 hours
- Constantly high repeatability
- Type with combination voltage (24 V DC and
110 to 240 V AC)
- 2 device types: on-delay and multifunctional
(7 functions)
- Long mechanical and electrical service life
- Coding plug sets
- Locking device
3RW30/31 soft starters - Reduction of the starting current for a
smooth start
- Soft coasting down function
- Only 3 motor supply leads are required
- System adaptation using setting options:
starting time, starting voltage, coasting
down time
-Fans
Load feeders
(combination starters)
with communication
capability
Complete pre-wired Load feeders (combina-
tion starters)/Motor starters
- for AS-Interface in degree of protection IP20:
AS-Interface Load feeders (combination
starters) 3RA5
- AS-Interface system accessories
- for AS-Interface in degree of protection IP65:
AS-Interface compact starter
- Supply modules/-wiring /
AS-Interface system accessories
- for PROFIBUS-DP in degree of protection
IP20: distributed I/O ET 200S
- System accessories ET 200S
- for PROFIBUS-DP in degree of protection
IP65: discredited I/O ET 200X
- Supply modules/-wiring / system
accessories ET 200X
- for AS-Interface and PROFIBUS-DP in degree
of protection IP65:
ECOFAST motor starter
- Supply modules/-wiring / system
accessories ECOFAST
Components Brief description/features Accessories
Table 1-1: (cont.) Components and combinations with accessories
System overview
SIRIUS System Manual
1-14 A5E40534713002A/RS-AA/001
Device combinations The following diagrams show you the possible device combinations, using
the S00 frame size as an example
Fig. 1-6: Device combinations
3RV10 Circuit
breaker (MSP)
3RA19 link
module
3RT10 Contactor
3RT10 Contactor
3RU11 Overload
relay
Fuseless
load feeder (combination starter)
Fused
load feeder
3RA13 reversing combination
3RA14 Wye-delta combination
System overview
SIRIUS System Manual
A5E40534713002A/RS-AA/001 1-15
Contactor combination for reversing the S00 frame size (with accessories)
Fig. 1-7: Contactor combination for reversing
Individual parts:
1/2) Contactors
4/5/6)Kit
The kit includes:
4) Mechanical interlock
5) 2 connection clips for 2 contactors
6) Wiring blocks above and below to connect the main conducting paths with electrical interlock
(NC contact interlock - can be removed if required)
Attachable accessories:
13) Soldering pin adapter
14) Auxiliary switch block, on the front (only an auxiliary switch block that complies with
DIN EN 50 005 can be used)
16) Surge suppressor
System overview
SIRIUS System Manual
1-16 A5E40534713002A/RS-AA/001
1.5 Mounting methods and terminal systems
1.5.1 Mounting the equipment
The method of mounting the equipment is uniform within each frame size.
Panel mounting The SIRIUS switching devices can be screwed on to a flat surface.
Please note the following points with some of the devices:
3RV1 circuit breaker (MSP), frame sizes S00/S0: Push-in lugs are required
for screw-type panel mounting
3RP15 time relay: Push-in lugs are required for screw-type panel
mounting
Coupling links: No screw-type panel mounting
Soft starters: No screw-type panel mounting
Snap-on mounting
(DIN rail mounting)
The SIRIUS switching devices are snapped onto 35 mm DIN rails in acc.
with DIN EN 50 022 without a tool.
The devices with a frame size of S3 require a rail with an installation height
of 15 mm. Alternatively, they can also be snapped onto 75 mm rails.
Frame size Mounting Removal
S00 to S3 Panel Mount Removed with a screwdriver
S00, S0 Snapped onto a
35 mm rail (in acc. with
DINEN50022)
Removed without a tool
S2 Snapped onto a
35 mm rail (in acc. with
DINEN50022)
The snap-on spring can be opened with a
screwdriver
S3 Snapped onto a
35 mm rail (in acc. with
DINEN50022)
Snapped onto a
75 mm rail
The snap-on spring can be opened with a
screwdriver
Table 1-2: Mounting methods
System overview
SIRIUS System Manual
A5E40534713002A/RS-AA/001 1-17
The following table shows you how to mount the device onto the DIN rail:
The following table shows you how to remove the device from the DIN rail:
You will find notes on mounting the different devices onto DIN rail in the
relevant parts of the fifth section of any chapter entitled “Mounting and
connection
.
Frame
size
Procedure Illustration
S00/S0 Place the device on
the upper edge of the
rail, and press it down-
wards until it snaps
onto the lower edge
of the rail.
S2/S3 Place the device on
the upper edge of the
rail, and tilt it towards
the rail until it snaps
onto the lower edge
of the rail.
Table 1-3: Mounting the device on the DIN rail
Frame
size
Procedure Illustration
S00/S0 Push the device
downwards to release
the tension of the
mounting spring, and
remove the device by
tilting it.
S2/S3 Using a screwdriver,
push the clip on the
lower rear side of the
device downwards to
release the tension of
the mounting spring
(1), and remove the
device by tilting it (2).
Table 1-4: Removing the device from the rail
2
1
1
1
2
System overview
SIRIUS System Manual
1-18 A5E40534713002A/RS-AA/001
1.5.2 Screw-type terminals
The terminals used do not vary within a frame size. The current switched by
the different devices of a single frame size does not vary either. This means
you can use the same tool, torque, and conductor cross-section for the cir-
cuit breakers, contactors, and overload relays of a single frame size. The
stripping lengths of the conductors are also the same. This is important in
the case of prefabricated wiring.
Screw-type terminals All the devices have screw-type terminals, either a terminal with a top
washer or a box terminal, depending on the frame size.
Devices with frame sizes S00 and S0 have terminals with captive screws
and terminal washers that enable you to connect 2 conductors, even if they
have different cross-sections.
The box terminals of frame sizes S2 to S3 can also take 2 conductors with
different cross-sections.
Connection tools Use the following tools to make the connection:
Frame sizes S00 to S2: Screws are available for rated currents of up to
50 A for Pozidriv2 screwdrivers.
Frame size S3: To obtain the required torques for the frame size for up to
95 A, Allen screws are used.
- Frame size S3: Allen screw SW4
The screwdriver guides around the terminal allow screw driving machines to
be used.
Lugs and connecting
bars
You can remove the box terminals from the devices with a frame size of S3
to connect conductors with lugs or connecting bars. A terminal cover is
available as shock protection and to ensure that you comply with the
required creepage and clearance distances when the box terminals are
removed. You can find a detailed description in the forth section of an indi-
vidual chapter entitled “Accessories”.
System overview
SIRIUS System Manual
A5E40534713002A/RS-AA/001 1-19
1.5.3 Cage Clamp1 terminals
The Cage Clamp terminal system is now available for circuit breakers
(MSPs), contactors, overload relays, and time relays.
Cage-type clamping units, known as Cage Clamp terminals in the case of
SIRIUS products, facilitate quick and maintenance-free wiring.
Design The Cage Clamp terminal consists of two parts:
A power rail for conducting current
A spring cage-type clamp for clamping strength
Fig. 1-8: Cage Clamp terminal
Conductors The Cage Clamp terminal on the switching devices clamps all copper wires
(single-core, stranded and finely stranded) from 0.25 mm2 to 2.5 mm2. The
conductors can be clamped directly or with some protection for splicing. To
this end, wire end ferrules or pin-end connectors can be placed on the con-
ductor ends. The best solution is an ultrasonically condensed conductor.
1. Cage Clamp is a registered trademark of the Wago Corporation
Clamp
Power rail
Single-core
Stranded
Finely stranded
Finely stranded with wire end ferrule
System overview
SIRIUS System Manual
1-20 A5E40534713002A/RS-AA/001
Safety The devices are equipped with a two-wire connection. In other words, there
are two independent connections for each conducting path.
Only one conductor is connected to each clamping unit.
The clamp presses the conductor against the power rail, which is curved at
this point. A highly specific compressive load per area is achieved making it
gas tight.
The clamp presses its flat surface against the conductor, thus avoiding dam-
age to it. The spring force of the clamp is designed so that it automatically
adjusts to the radius of the conductor. This allows any deformation of the
conductor to be dealt with. It is not possible for the clamping unit to loosen
by itself.
This connection is vibration- and shock-proof. These types of stress do not
damage the conductor or cause any loss in contact.
Machines and systems in which this type of stress occurs, such as vibra-
tors, rail vehicles and elevators, are particularly suitable applications for this
connection.
Transfer
accuracy
The contact pressure between the conductor and power rail is optimal,
making this clamp terminal suitable for high-voltage installations and also for
the transfer of voltages and currents in the mV and mA ranges in measuring
technology and electronics.
Tool Screwdrivers for opening the Cage Clamp terminals can be obtained from
the SIEMENS low voltage controls catalog.
Procedure The following table shows you how to use the Cage Clamp
Step Procedure
1Insert the screwdriver into
the rectangular opening
until it stops.
The screwdriver head auto-
matically keeps the clamp
open.
2Insert the conductor into
the oval terminal opening.
3Remove the screwdriver.
The terminal closes, and
the conductor is thus
securely clamped.
Table 1-5: How to use a Cage Clamp terminal
NSJ 00001
NSJ 00002
NSJ 00003
System overview
SIRIUS System Manual
A5E40534713002A/RS-AA/001 1-21
Small conductor
cross-section
With conductor cross-sections that are 1 mm2, you should use an insu-
lating stop to avoid contact between a terminal and the conductor insula-
tion.
The illustration below shows the procedure:
Fig. 1-9: Conductor cross-sections 1 mm²
1.5.4 Connection cross-sections
Because SIRIUS is a modular system, the connection cross-sections are the
same for all devices of a single frame size.
The following tables specify the permissible conductor cross-sections for
main and auxiliary conductor connections. The example shown is frame
size S0:
Frame size S0
1m
3RT1916-4JA02
Coil terminals: A1/A2
Auxiliary conductor: NO/NC Main conductor
Screw-type
terminals
Cage Clamp
terminals
L1 L2 L3
T1 T2 T3
5 ... 6 mm / PZ2
0.8 to 1.2 Nm
7 to 10.3 lb·in 2 to 2.5 Nm
18 to 22 lb·in
2 x (0.5 to 1.5 mm²)
2 x (0.75 to 2.5 mm²) 2 x (0.25 to 2.5 mm²) 2 x (1 to 2.5 mm²)
2 x (2.5 to 6 mm²)
2 x (0.5 to 1.5 mm²)
2 x (0.75 to 2.5 mm²) 2 x (0.25 to 1.5 mm²) 2 x (1 to 2.5 mm²)
2 x (2.5 to 6 mm²)
2 x (0.25 to 2.5 mm²)
AWG 2 x (18 to 14) 2 x (24 to 14) 2 x (14 to 10)
Table 1-6: Connection cross-section for frame size S0
10
10
10
System overview
SIRIUS System Manual
1-22 A5E40534713002A/RS-AA/001
1.6 Communication
Fig. 1-10: Communication
1.6.1 Communication-capable low-voltage switching technology
The communication-capable control components from SIEMENS ensures
the user a continuous Automation solution from network up to the control
panel. The concept is based on using AS-Interface and PROFIBUS-DP, the
two standardized and open networking systems, which can be connected to
by virtually all of the known control system manufacturers.
Actuator-sensor inter-
face (AS-Interface)
AS-Interface is a standardized, non-proprietary networking system
(IEC 62026-2) for simple and usually binary actuators and sensors. It is pos-
sible to connect it to SIMATIC programmable logic controllers via different
master modules. A DP/AS-Interface link also ensures direct integration in a
PROFIBUS-DP system or connection to other field buses via couplers. Up to
248 sensors and 186 actuators can be connected to an AS-Interface network
over a maximum of 300 m. Safety-related signals can now also be net-
worked with AS-Interface, thus dispensing with the wiring of emergency
stop signals that were previously needed.
PROFIBUS PROFIBUS is a standardized, non-proprietary networking system
(IEC 61158) to which most PLCs of leading manufacturers can be con-
nected. Up to 125 nodes can be incorporated in one bus segment. Dis-
tances of up to 9.6 km can be bridged with copper conductors and up to
100 km with fiber-optic conductors.
S7-300
M
3
M
3
M
3
NSA00001b
AS-Interface
M
3
LOGO!
PROFIBUS-DP
NT NT
Safety
monitor
CP 343-2
Proximity
switch
BERO
Command
devices
SIGNUM
AS-Interface
Motor starter
Signal column
DP/AS-Interface
Link
SIMOVERT
MASTER DRIVES
Distributed
I/O device
ET 200X
Motor starter 3RA5
Motor protection and
control device
SIMOCODE-DP
3UF50
Circuit breaker
SENTRON WL/VL
HMI/Visualization
COROS/WIN CC
SIMATIC S7/C7
Input/output modules
in IP20
analogdigital
Membrane keyboard
3SB4
Input/output modules
in IP67
secure digital input modules
Distributed I/O device
ET 200S
System overview
SIRIUS System Manual
A5E40534713002A/RS-AA/001 1-23
PROFIBUS-DP PROFIBUS-DP (DP being a German abbreviation for distributed I/O) is used
for switching devices with higher communication requirements (e.g. the
transmission of a large volume of data with extremely fast response times).
It is also used to link individual AS-Interface segments.
PROFIsafe PROFIBUS-DP can also transfer safe signals. The PROFIsafe-Protocol can be
used to communicate safe inputs and outputs with a fail safe controller.
1.6.2 Parameterization of PROFIBUS-DP and bus-capable low-voltage switching devices
Before commissioning, PROFIBUS-DP must be configured, and the indi-
vidual bus nodes must be parameterized. There are user-friendly tools
available to the user for configuration and parameter assignments.
Parameter assignment
tools
For SIMATIC S7 masters, all the functions are integrated in the STEP 7
programming language.
For SIMATIC S5 masters and various non-SIEMENS masters, the COM
PROFIBUS parameter assignment software is required.
Manufacturers of non-SIEMENS masters offer other configuration and
parameter assignment programs.
There are various product specific software packages available that allow
you to easily parameterize and diagnose your low voltage control devices
with a variety of functions.
COM SIMOCODE for the motor protection- and control device
SIMOCODE-DP.
SWITCH ES motor starter for ECOFAST Motor starter and
ET 200S High Feature motor starter.
These Software packages are either completely incorporated in STEP 7,
communicated via PROFIBUS-DP or directly via a serial interface with the
respective field device
Applications The above program packages make it easy to carry out the following for
PROFIBUS-DP and its nodes:
Configuration
Parameter assignment
Documentation
Commissioning
Testing
Diagnostics
For additional information on communication-capable low-voltage switching
devices, as well as system components and accessories, see the following
catalogs:
Industrial Controls Catalog (PC 6000)
IK PI "Industrial Communication and Field Devices"
CA01 "Automation- and Drives technology" (CD-ROM)
System overview
SIRIUS System Manual
1-24 A5E40534713002A/RS-AA/001
1.6.3 Actuator-sensor interface (AS-Interface)
Actuator-sensor interface (AS-Interface) is a modular networking system for
sensors and actuators in the lowest field range.
It makes no difference to the program in the programmable controller
whether parallel wiring with input/output modules or AS-Interface is used.
It is therefore possible for existing systems to change to AS-Interface
because you can continue to use the same programs. The entire system can
be operated without additional software. It is not necessary to be familiar
with the internal workings of AS-Interface.
Replacement for the
cable harness
Process signals that occur locally are normally transferred to the open loop
control using extensive parallel wiring and input/output modules. This
means that each sensor or actuator in the field is connected to the input/
output modules with its own cable. AS-Interface makes it possible to
replace this cable harness with a simple two-wire cable for all sensors and/
or actuators.
Data and power on a
two-wire cable
The master communicates with the nodes via the AS-Interface cable. As
well as data, this cable also transfers the supply voltage for node operation
and node inputs, i.e. sensors. The voltage is supplied to the AS-Interface
cable from a special AS-Interface power supply unit with a data link.
Setting up different
structures
The AS-Interface cable is installed in the same way as for an electrical instal-
lation. A new node can be inserted at any point. This makes it possible to
set up network structures (e.g. tree, star or line structures). No shielding or
terminating resistors are required. The wiring can be adapted individually to
the system or machine.
Maximum System
configuration
Detailed configuration and installation guidelines can be found in the instal-
lation guideline "Installation of the AS-Interface networking system" (on
mounting the AS-Interface networking system).
Up to 62 nodes can be connected to the AS-Interface cable. A node is, for
example, an AS-Interface module (digital or analog) or a BERO (proximity
switch) with an integrated AS-Interface chip. A maximum of 4 binary sen-
sors and/or 4 actuators can be connected to an AS-Interface module.
This produces a maximum configuration of 248 inputs and 186 outputs
(62 nodes x 4 inputs and 3 outputs).
Degree of protection AS-Interface is a networking system for direct use on the machine. The
AS-Interface compact module has an IP67 degree of protection. They can be
used without an enclosure.
There are also AS-Interface modules with IP20 protection for use in enclo-
sures or distribution panels.
System overview
SIRIUS System Manual
A5E40534713002A/RS-AA/001 1-25
Installation system All compact modules are placed on a mounting plate. The mounting plate
takes the AS-Interface cable and keeps it in place. Polarity reversal is
virtually impossible due to the profile of the cable. The compact modules
are simply hooked on at the top of the mounting plate and secured with just
one screw. When you secure the modules, contact is made with the AS-
Interface cable. You do not have to strip or screw on the cable.
Coding prevents errors All the modules are mechanically and electrically coded.
The coding system prevents errors occurring in the event of replacement. At
replacement, only one module of the same type can ever be mounted. This
stops digital or analog modules (or even inputs or outputs) getting mixed up.
Addressing To participate in data transfer with the master, each node must be assigned
an address before commissioning of the AS-Interface network. Addressing
devices are available for this.
Addressing an installed
module
There is an additional feature which makes new SIEMENS modules even
more user-friendly: the addressing socket.
Using this socket you can address a module after it has been installed. It is
not necessary to unscrew the module. Installation can be carried out in the
system by personnel who are not familiar with the AS-Interface. The com-
missioning engineer can address the modules easily when they are already
installed. For the first time, this type of addressing is also possible with IP67
protection.
Diagnostics at a glance The new generation of AS-Interface modules (compact modules, analog
modules, and SlimLine modules) has the new display system developed by
SIEMENS.
The status of a module is displayed by two LEDs lighting up continuously or
flashing.
This simple diagnostic feature directly on the module makes it possible for
the user to find the error quickly and efficiently. This in turn reduces down-
times.
Certificates of the
AS-Interface
association
All SIEMENS AS-Interface products are tested in accordance with the rele-
vant testing regulations in an accredited test laboratory and certified by the
AS-Interface association.
System overview
SIRIUS System Manual
1-26 A5E40534713002A/RS-AA/001
Digital compact
modules with IP67
protection
AS-Interface modules in the compact range are characterized by optimized
operating features and improved user-friendliness.
This can reduce mounting and commissioning times for AS-Interface by up
to 40 %. Additional LEDs provide information on the most important operat-
ing modes of the module, resulting in a considerable increase in system
availability.
The modules of the compact range consist of two components:
Mounting plate and compact module
The mounting plate mechanically fixes the AS-Interface profile cables, takes
the compact module, and serves as a template with drill holes.
The compact module contains the electronic components for communica-
tion and the M12 standard connections for inputs/outputs. Up to four sen-
sors and four actuators can be easily and reliably connected to the compact
module using the M12 standard connection.
The mounting plate and compact module are connected to each other by
means of a single screw. Contact is established with the AS-Interface cable
by means of the proven insulation displacement method.
AS-Interface modules in the compact range with an M12 connection can
have a protective conductor (PE) connected to them.
Using an addressing socket integrated in the compact module, you can also
allocate addresses when the module is in place.
Analog compact
modules with IP67
protection
The design of the analog modules has been adapted for the compact
modules. The analog input and output modules each have two channels. You
can connect measuring sensors and analog actuators using standard M12
connectors. The following groups of analog modules exist:
Input module for two current sensors
Input module for two voltage sensors
Input module for two thermal resistors
Output module for two current actuators
Output module for two voltage actuators
All the measured values – except for the thermal resistance value of Pt 100
(not linear) – are available in linear form. In other words, the non-linear trans-
mission curve of the thermal resistor sensor is automatically linearized in
the analog module, and measured values can be processed directly in the
programmable controller.
The input and output channels are isolated. Two-wire and four-wire sensors
can be connected. Differential inputs produce considerable suppression of
common-mode interference. The integrating sigma-delta converter ensures
high measurement accuracy.
System overview
SIRIUS System Manual
A5E40534713002A/RS-AA/001 1-27
Safety first –
emergency-Stop via
AS-Interface
AS-Interface is a system that can transmit both standard signals and safety-
related input signals (e.g. Emergency stop) via the same cable.
Only an additional safety monitor and safe modules are required to use
AS-Interface as a safety bus. This enables category 4 in acc. with EN 954-1
to be achieved. A failsafe programmable controller or special master is not
necessary.
The concept and implementation of AS-Interface Safety at Work (AS-Inter-
face SaW) have been tested and certified by TÜV (technical testing associa-
tion).
This means that the system can be converted to the considerably more
flexible AS-Interface network, which is already available, thus eliminating
the need for the complex, separately implemented emergency stop wiring
that has been necessary up to now.
The following components for direct connection to AS-Interface are
available:
Safety monitors
Safety modules
Emergency-Stop devices
Light curtains
Laser scanners
System overview
SIRIUS System Manual
1-28 A5E40534713002A/RS-AA/001
A/B-Technique The new AS-Interface-specification allows the doubling of the number of
nodes on the network from 31 to 62. The 31 addresses that are possible in
an AS-Interface network can be subdivided into two separately independent
subaddresses e.g. in 1A and 1B .
If one uses this feature for all 31 slaves, then it is possible to have a maxi-
mum of 62 nodes on one AS-Interface network. The so-called A/B-Slaves
can have a maximum of four inputs and three outputs.
Another function of the new AS-Interface specification V2.1 is the inte-
grated analog value transfer. Integrated means that a special function block
is not required in order to be able to access the analog values. Accessing
data of analog values is therefore just as easy as with digital values. The use
of integrated analog value transfer is possible with analog nodes, that sup-
port Profiles 7.3 and 7.4.
Fig. 1-11: A/B-Technique
NSA00004
Slave 1 Slave 2A Slave 2B Slave 31
Slave 1 Slave 31
Slave 1A Slave 1B Slave 31BSlave 31A
Mixed operation is also possible:
With A/B slaves max. 62 stations:
So far 31 devices:
System overview
SIRIUS System Manual
A5E40534713002A/RS-AA/001 1-29
1.6.4 SIRIUS NET Communication-capable motor starter
SIRIUS NET is the name of the family of communication-capable motor
starters from SIEMENS. SIRIUS NET motor starters are available with
AS-Interface and PROFIBUS-interface, in IP20 degree of protection for use
inside the control panel or distribution panel, and in IP65 degree of protec-
tion for use outside the panel and mounted directly on the machine.
SIRIUS NET motor starters consist of completely pre-wired SIRIUS load
feeders/combination starters. This reduces the installation time and wiring
time to a minimum. All of the necessary inputs and outputs are already on
board. Depending on the design there are many Diagnostic functions that
support the user and owner. This reduces downtime and improves effi-
ciency.
3RA5 AS-Interface load
feeder/combination
starter
The preferred use of AS-Interface 3RA5 load feeder/combination starter is in
central control panels (IP65 degree of protection). It’s busbar (Fastbus)
adapter for 40 mm and 60 mm systems allows for quick installation. With
the connection via busbars, a whole range of 3RA5 load feeders/combina-
tion starters can be supplied with power. AS-Interface and auxiliary power
are simply connected by using a plug with insulation piercing connection
technology. The conductor to the motor can be attached without a terminal
strip by using a 5-pole power connector that attaches directly to the starter.
Due to its consistent plug-in technology a 3RA5 load feeder/combination
starter can quickly be changed out. The 3RA5 load feeder/combination start-
ers are available as direct or reversing starters up to 7.5 kW. For larger loads,
devices can be easily assembled by the customer by using standard SIRIUS
and AS-Interface components.
Load Feeder
3RA5
SIMATIC
ET 200S
SIMATIC
ET 200X
AS-Interface
Compact Starter
ECOFAST
Motor Starter
System overview
SIRIUS System Manual
1-30 A5E40534713002A/RS-AA/001
AS-Interface compact
starter
The AS-Interface compact starter is a starter designed to mount directly on
the machine (IP65 degree of protection). The durable plastic housing also
makes it suitable for use in the roughest industrial environment. With only
two screws it can be mounted on to a mounting plate with very little effort
and at the same time it makes contact with the AS-Interface- and auxiliary
power flat cable through the proven AS-Interface penetration technique. The
main power circuit side is quickly connected to the power bus cable and the
motor circuit. Assemblies with a contactor and circuit breaker (MSP) are
available up to 5.5 kW and with electronic contact element and electronic
overload relay are available up to 2.2 kW either as a direct and as reversing
starter. Two inputs on the starter can accept process signals via M12-socket
and route them to the PLC. Starters with brake contacts for an electrically
operated motor brakes are also optional.
ET 200X The ET 200X distributed I/O system with the wide variety of expansion
modules offers the possibility to provide all of the machines functions
directly on the machine - in IP65/IP67 degree of protection. Whether motor
starter, frequency converter, pneumatic or input/output module, whether in
harsh environments, in extreme time critical applications or a large number
of sensors and loads in one place - the modular SIMATIC ET 200X distrib-
uted I/O system offers the corresponding decentralized solution for every
application in the field. ET 200X consistently provides optimal communica-
tion with the high level system via PROFIBUS-DP. A single basic module
allows the addition of up to 6/7 expansion modules. With the AS-Interface-
Master module in the ET 200X, a mixture of networks can be very easily
attained at a reasonable price. The distributed signals in the installation can
also be optimally incorporated with very little set-up effort. With the intelli-
gent basic module for data preprocessing and control, distribution of self-
supporting and time-critical functions can be realized independent from the
higher level PLC. Only the most important control signals and diagnosis data
is then sent over PROFIBUS. This relieves the network as well as the high
level control. The programing and planning of these types of stations is
done with SIMATIC standard tool STEP7.
ET 200X motor starter The ET 200X motor starter is available in the same designs as the AS-Inter-
face compact starter. That means, as an electro-mechanical starter up to
5.5 kW, electronic starter to 2.2 kW. For further details see above. There is a
hand-held controller available that can also be used with both motor starter
families for activation at prestart-up and for service use.
ET 200S The ET 200S distributed I/O system, using PROFIBUS-DP, offers a plurality
of 2- and 4-channel input/output modules, Technology modules, such as
Standard motor starter, High Feature motor starter and safety technology
that can be configured almost any way you want in a fine modular form. The
modules with IP20 degree of protection are used in central control panels as
well as decentralized panels. All of the voltage potential only needs to be
supplied once. Through simple side-by-side mounting of the terminal mod-
ules the auxiliary power as well as the main power voltage are automatically
transferred. The purely passive terminal modules are the basis for the elec-
tronic modules that mount on them. These electronic modules can also be
removed or added while in the system is running. This safeguards the
accessibility of the machines and installation.
System overview
SIRIUS System Manual
A5E40534713002A/RS-AA/001 1-31
ET 200S motor starter The ET 200S motor starters are completely pre-wired SIRIUS load feeders/
combination starters with short-circuit protection and overload protection.
The required inputs and outputs for control and monitoring are already inte-
grated in the motor starter. The correct function of the motor starter is
monitored without any additional programming and will initiate a clear error
signal via PROFIBUS-DP if needed.
ET 200S SIGUARD The motor starters can be expanded for technical safety applications
(EN 954-1) with the SIGUARD power modules. Emergency-stop buttons,
safety limit switches or other floating contacts from safety devices use a
two channel connection. The functions on the sensor side are in accordance
with the standard and are monitored for, among other things, cross-circuit or
short-circuit. The integrated safety relays also check the proper switching of
the motor starters listed below. Additionally ET 200S Standard motor starter
requires a so-called F-Kit - a front mounted auxiliary contact- (return circuit).
The High Feature motor starter comes with these contacts already factory
installed. A special Connection module needs to be installed at the end of a
safety segment with one or more motor starters. For applications that
require category 3 or 4 (EN 954-1) a redundant infeed contactor needs to be
connected to the connection module (control and monitoring). For applica-
tions that require category 2 the return circuit needs to be closed on the
Connection module by using a jumper.
ET 200S Standard
motor starter
ET 200S Standard motor starter consists of a circuit breaker (MSP) and con-
tactor combination from the SIRIUS S00-Frame size. At a maximum rating of
5.5 kW, the motor starter gets power from the terminal module on the self-
establishing power bus (40 A). All that remains per motor starter is simply
adding the three conductors of the motor load and optional neutral/ground
connection. Distribution wiring on pre-stored terminal blocks is no longer
necessary, since the terminal modules already provide this function.
ET 200S High Feature
motor starter
The ET 200S High Feature motor starter is a new class of load feeder/combi-
nation starter up to 7.5 kW. Motor circuit breaker (MSP) for short-circuit pro-
tection, electronic overload relay for the overload protection, and contactor
or soft start for switching the circuit offer a range of new features:
The devices in frame size S0 have achieved Type 2 coordination for the
current ratings up to 16 Amps (7.5 kW). That means, that even after a
short circuit in the range of 50 kA the motor starter will not be destroyed
and can still be used. Only light welding of the contacts, without any
deformity worth mentioning and which can be separated by the user, is
permitted.
The current monitoring in all three phases serves as both the overload
evaluation and as the processing in the high level control. As an alterna-
tive to cyclic current value transmission it is also possible to set of an
upper and a lower limit value for each. These can be used, for example,
for the load dependent, autonomous shutting off of the starter.
All of the settings, as well as the rated motor current are automatically
transferred to the new starter by the high level controller in the event a
starter needs to be exchanged.
System overview
SIRIUS System Manual
1-32 A5E40534713002A/RS-AA/001
In the case of an exchange you only need to choose between two starter
types. The electronic overload relay offers an extraordinary adjustment
range (0.3 to 3.0 A and 2.4 to 16 A).
In some critical applications the process can be more important than the
protection of the motor. That is why under the estimation and supervision
of the user there is the possibility with the High Feature motor starter to
suppress the overload tripping function and continue operation of the
motor starter with the emergency start function.
The quickest assembly through completely pre-wired and simple plug-in
technology were added so that a range of functions could lead to increased
system availability. This makes the starter especially suitable for applications
that contain both time-critical and valuable processes.
ET 200S Failsafe motor
starter
The ET 200S Failsafe motor starter takes the advantages of the High
Feature motor starter and supplements them with the requirements from
the Safety technology. An integrated monitoring function checks whether or
not the contactor opens properly when the motor starter is turned off. For
example, should the contactor be welded and therefore can’t open, the cir-
cuit will be automatically opened by the motor circuit breaker (MSP). It
therefore meets the required redundancy of EN 954-1 for category 4 with-
out any additional mounting or wiring time. You can assign up to 6 separate
safety circuits of different motor starters inside of a single station to each
upstream power module. The control takes place either over a Safety
related control system, for example SIMATIC S7-300F and PROFIBUS-DP
(PROFIsafe) or over a separate safety switching device, for example the
safety monitor from AS-Interface Safety at Work.
The advantage in using the Failsafe motor starter solution lies in the flexible
order of various safety circuits and the integrated switching redundancy in
every starter. The cost to achieve this type of installation with conventional
technology would be much higher. However, if a larger group of motor
starters in one safety segment is needed, then a solution with ET 200S
SIGUARD could be the more favorable one.
For its safety function, the Failsafe motor starter requires that the contactor
contacts are electrically isolated from each other. Therefore, a design with a
softstarter function is not available.
Switch ES motor
starter
The Switch ES motor starter, the easy to use configuration and diagnoses
tool, not only lets you comfortably configure and diagnose the High Feature
motor starter while in operation with an on the spot point-to-point connec-
tion, but also supplies a range of additional information, such as statistics
data. That way the operating hours or the motor current during the last over-
load trip can be called up. Important information on the condition of the
installation can then be derived. The control function also comfortably lets
you test the motor starter without high level control, such as at prestart-up.
SIRIUS System Manual
A5E40534713002A/RS-AA/001 2-1
2
3RV1 Circuit breaker/MSP 1)
Section Subject Page
2.1 Specifications/regulations/approvals 2-3
2.2 Device description 2-5
2.2.1 General description 2-6
2.2.2 Operation 2-7
2.2.3 Information on configuration 2-10
2.3 Application and areas of use 2-13
2.3.1 Motor protection 2-13
2.3.2 Transformer protection 2-13
2.3.3 Starter protection 2-13
2.3.4 Motor protection with overload relay function 2-14
2.3.5 Switching direct current 2-15
2.3.6 Main and emergency stop switches 2-15
2.4 Accessories 2-16
2.4.1 Attachable accessories: Overview 2-16
2.4.2 Auxiliary contacts 3RV19 01-.., alarm switch 3RV19 21-111
and auxiliary release 3RV19 .2-....
2-17
2.4.3 Motorized remote-control mechanism 3RV19 .6-.... 2-22
2.4.4 Disconnecting/isolator module 3RV19 .8-1A 2-25
2.4.5 Thru-the door rotary operators 3RV19 .6-.. 2-27
2.4.6 Terminals for "Combination Motor Controller Type E" in acc.
with UL 508
2-33
2.4.7 Enclosures and mounting accessories 2-34
2.4.8 Busbar adapter 8US1 (Fastbus system) 2-39
2.4.9 Isolated 3-phase busbar system 2-43
2.4.10 Link module for connection to a contactor 2-46
1) 3RV1 is known in the North America as a Motor Starter Protector (MSP) and is not UL Listed
as a circuit breaker
3RV1 Circuit breaker/MSP
SIRIUS System Manual
2-2 A5E40534713002A/RS-AA/001
2.5 Mounting and connection 2-47
2.5.1 Installation 2-47
2.5.2 Connection 2-48
2.5.3 Device circuit diagrams 2-50
2.6 Dimensional drawings (dimensions in mm) 2-52
2.7 Technical specifications 2-63
2.7.1 General specifications 2-63
2.7.2 Permissible rating of approved devices for North America, u s 2-66
2.7.3 Short-circuit breaking capacity Icn in acc. with IEC 60 947-2 2-68
2.7.4 Limiter function with standard devices for 500 V AC and
690 V AC in acc. with IEC 60 947-2
2-70
2.7.5 Characteristics 2-70
2.7.6 Installation guidelines 2-71
2.8 Application notes for the use of 3RV1 downstream from
frequency converters/inverter with pulsing voltage
2-72
2.8.1 Influences of high frequency currents upon the thermal
overload release
2-72
2.8.2 Other possible influences 2-73
Section Subject Page
3RV1 Circuit breaker/MSP
SIRIUS System Manual
A5E40534713002A/RS-AA/001 2-3
2.1 Specifications/regulations/approvals
Standards The 3RV1 circuit breaker/MSPs comply with the specifications for circuit
breaker/MSPs in acc. with IEC 60947-2/DIN VDE 0660, Part 101.
The circuit breaker/MSPs for motor protection comply with the specifica-
tions in acc. with IEC 60947-4-1/DIN VDE 0660, Part 102.
The auxiliary switches comply with IEC 60947-5-1/DIN VDE 0660
Part 200.
Approvals/
test reports
Confirmation of approvals, test certificates, and characteristics can be
obtained on the Internet/intranet. under
www.siemens.com/sirius/technical-assistance
Terminal markings The terminal markings comply with DIN EN 50 011.
Utilization categories Circuit breaker in acc. with IEC 60947-2: A
Motor starter in acc. with IEC 60947-4-1: AC-3 (main conducting paths)
DC - 11 / AC - 15 (control and auxiliary conducting paths)
Main and emergency
stop switches
The specifications for the main and emergency switches comply with
IEC 60204/DIN VDE 0113 Part 1.
Disconnector
specifications
Disconnector specifications comply with IEC 60947-3.
Shock protection 3RV1 circuit breaker/MSPs are shockproof in acc. with DIN VDE 0106
Part 100, even without accessories. You can find additional information on
the subject of shock protection in the "Switching, Protection and Distribution
in Low-Voltage Networks" manual, p. 37 ff.
Degree of protection The degree of protection of the 3RV1 circuit breaker/MSP is IP20.
In the terminal area of frame sizes S2 and S3, the degree of protection is
IP00, when the lug kits are removed.
Characteristics The time-current characteristics, the current limitation characteristics and
the I2t characteristics have been determined in acc. with IEC 60947 and
DIN VDE 0660.
3RV1 Circuit breaker/MSP
SIRIUS System Manual
2-4 A5E40534713002A/RS-AA/001
Conditions of
application
Explosion-proof motors
For motor protection circuit breaker/MSP 3RV10, CLASS 10 and for motor
protection circuit breaker/MSP with overload function 3RV11, CLASS 10:
DIN VDE 0165 and EN 50 019, DMT-Certificate according to directive
94/9 EG (ATEX-Approval).
Nuclear power plants
KTA certificate
Railway vehicles
DINEN50155
Ships and docks
Shipbuilding certificates of classes GL, LRS or DNV.
3RV1 Circuit breaker/MSP
SIRIUS System Manual
A5E40534713002A/RS-AA/001 2-5
2.2 Device description
3RV1 circuit breaker/MSPs are used to switch and protect three-phase
induction motors of up to 45 kW at 400 V AC (100 HP at 600 V AC) and for
loads with rated currents of up to 100 A.
The 3RV1 circuit breaker/MSPs have 3 poles. To achieve the highest degree
of flexibility, auxiliary switches, alarm switches, auxiliary releases, and other
accessories can be easily attached to the circuit breaker/MSPs without
tools.
3RV1 circuit breaker/MSPs and 3RT1 contactors work together both electri-
cally and mechanically. This enables them to be easily and quickly put
together to make load feeders.
Frame sizes 3RV1 circuit breaker/MSPs are available in 4 frame sizes (S00 to S3).
Fig. 2-1: 3RV1 circuit breaker/MSPs (frame sizes S00 to S3)
The following table shows you the frame sizes and the corresponding maxi-
mum rated operational current at a voltage of 400 V AC. The last column in
the table tells you which three-phase induction motor is suitable for which
particular size.
S00 S0 S2 S3
Frame
size Width Max. rated operational
current
Output power of the
three-phase induction
motor
S00 45 mm 12 A 5.5 kW
S0 45 mm 25 A 11 kW
S2 55 mm 50 A 22 kW
S3 70 mm 100 A 45 kW
Table 2-1: Circuit breaker/MSPs, frame sizes S00 to S3
3RV1 Circuit breaker/MSP
SIRIUS System Manual
2-6 A5E40534713002A/RS-AA/001
2.2.1 General description
Fields of application The 3RV1 circuit breaker/MSPs are suitable for:
Motor and plant protection
Starter protection (short-circuit protection)
Transformer protection
The 3RV16 11-0BD10 circuit breaker/MSP, frame size S00, is used for fuse
monitoring.
Releases 3RV1 circuit breaker/MSPs have:
Inverse-time delay, thermal overload releases
Instantaneous short-circuit releases
The overload releases can be set to the load current.
The short-circuit releases are set permanently to 13 times the rated current,
which allows motors to start up without problems. Circuit breaker/MSPs
used for transformer protection are set to 19 times the rated current to
avoid being tripped by the high inrush current.
When the circuit breaker/MSPs are tripped, in the case of frame size S00
the toggle switch goes into the tripped position, and in the case of frame
sizes S0 to S3 the rotary switch switches to the tripped position. Before it is
switched on again, the rotary switch must be put in the 0 position manually
(reset) to avoid switching to the fault inadvertently.
In the case of circuit breaker/MSPs with a rotary switch, the tripping opera-
tion can also be reported electrically by means of an alarm switch.
Tripping classes In acc. with IEC 947-4-1:
Frame sizes S00 to S3: class 10
Frame sizes S2/S3: class 20
Auxiliary release The circuit breaker/MSPs can also be equipped with one of the following
auxiliary releases:
Shunt release
Undervoltage release
Undervoltage release with leading auxiliary contacts
Auxiliary contacts The 3RV1 can use a transverse auxiliary contacts and/or a side mounted
auxiliary contacts (Section 2.4 Accessories).
Shock protection All frame sizes S00 to S3 are touch safe according to DIN VDE 0106
part 100. Additional protection covers are offered for frame sizes S2 and S3.
Frame size S2, S3: terminal covers for box terminals
Frame size S3: terminal covers for lug and bar connection
3RV1 Circuit breaker/MSP
SIRIUS System Manual
A5E40534713002A/RS-AA/001 2-7
Other accessories Other accessories for circuit breaker/MSPs:
•Alarm switch
Disconnecting module
Isolated 3-phase busbar system
Busbar adapter
Rotary switches
Terminals for "Combination Motor Controller Type E" in acc. with UL 508
Housing and front plates
2.2.2 Operation
Current setting Using a screwdriver, set the load rated current (current setting) Ie on the
scale of the 3RV1.
The proper dial setting will depend how the 3RV1 will be installed. There are
two determining factors:
1. Stand-alone installation: without a directly mounted contactor and clear-
ance left and right of a minimum 10 mm.
2. Side-by-side installation: with a directly mounted contactor and clear-
ance left and right of less than 10 mm. This is the typical installation
method.
Note the two possible dial markings on the dial:
Dash mark: Is the dial marking used when the 3RV1 is being applied in
stand-alone installation
Triangle mark: Is the dial marking used when the 3RV1 is being applied in
side-by-side installation
In both cases the ambient temperature may be +60 °C and the complete
current range can be used up to the highest setting. The relevant dial mark-
ing (Dash or Triangle) should be set according to the required current set-
ting. At temperatures over +60 °C current derating is necessary. The maxi-
mum allowable current setting for an ambient temperature of +70 °C can be
determined by a slightly longer setting line on the current scale.
Fig. 2-2: Current adjustment Ie adjustment (example: frame size S00)
360° o.k.
RV-00222
Ie
max. + 60 °C
max. + 70 °C
A
3RV1 Circuit breaker/MSP
SIRIUS System Manual
2-8 A5E40534713002A/RS-AA/001
Warning
The adjusting knob can be turned 360° clockwise. You can only turn it coun-
terclockwise within the adjustment range.
A setting over the marked current scale is not permitted
Sealing the
adjustment scale
You can prevent unauthorized adjustment of the current setting by placing a
transparent cover over it and sealing it.
Fig. 2-3: Sealing the adjustment scale (example: frame size S00)
Switches The state of the circuit breaker/MSP can be determined by the position of
the switch:
Fig. 2-4: Tripped position, 3RV (example: frame size S0)
3RV19 08-0P
Frame size Switch STOP ON Tripped
S00 Toggle switch OFF ON OFF
S0, S2, S3 Rotary switch OFF ON TRIPPED
Table 2-2: Contact position indicators of the circuit breaker/MSPs
RV-01050
3RV1 Circuit breaker/MSP
SIRIUS System Manual
A5E40534713002A/RS-AA/001 2-9
Locking the circuit
breaker/MSPs
You can prevent the circuit breaker/MSP from being switched on by unau-
thorized persons by securing the switching mechanism (toggle switch or
rotary switch) with a padlock (shackle diameter 3.5 to 4.5 mm)
The device can only be locked in the Off position.
Fig. 2-5: Locking the toggle and rotary switch (example: frame size S00 and S0)
Resetting after a tripping operation
When the circuit breaker/MSP trips, the switch goes into the tripped position.
You use the switch to close the circuit again.
In the case of frame sizes S0 to S3, the rotary switch must be manually
turned to the OFF position after the device trips. Then the circuit breaker/
MSP can be turned on again.
In the case of frame sizes S2 and S3, it is possible to switch on and off using
a motorized remote-control mechanism (see Section 2.4, Accessories).
Testing overload
tripping
The following table shows you how overload tripping of the circuit breaker/
MSP can be tested:
Ø 3.5... 4.5 mm
RV-00251
S00 S0
Drawing Step Procedure
1Switch the toggle switch/rotary
switch from 0 to 1.
2/3 Put a screwdriver in the test
opening and push it to the left.
Overload tripping is in working
order when the toggle switch
switches from 1 to 0 (frame
size S00) or goes into the
tripped position (frame sizes S0
to S3).
Table 2-3: Testing overload tripping (example: frame size S00)
1
2
RV -00223
3RV1 Circuit breaker/MSP
SIRIUS System Manual
2-10 A5E40534713002A/RS-AA/001
2.2.3 Information on configuration
Short-circuit protection The short-circuit releases of the 3RV1 circuit breaker/MSPs execute a three-
phase isolation of the faulty branch circuit from the network and prevent any
further damage.
With a short-circuit breaking capacity of 50 kA or 100 kA a voltage of
400 V AC, the switches are considered to be short circuit-proof, since
higher short-circuit currents are not to be expected where the switches are
installed.
Backup fuses are only required if the short-circuit current at the point of
installation exceeds the rated short-circuit breaking capacity of the circuit
breaker/MSPs.
You will find the short-circuit breaking capacity for other voltages and the
sizing of any required fuse listed in Section 2.7, Technical specifications.
Conditions of
application
3RV1 circuit breaker/MSPs are climate-proof. They are intended for use in
closed areas where there are no hazardous operating conditions such as
dust, corrosive fumes or destructive gases.
Appropriate housings are available as an accessory for use in dusty and
damp areas (see Section 2.4).
Selection Operational currents and starting currents can vary even in motors of the
same power. The motor powers listed in the tables are to serve only as
guide values. Most important when selecting the correct circuit breaker/
MSPs are the specific starting data and rating of the motor to be protected.
This also applies to circuit breaker/MSPs used for transformer protection.
Phase loss
sensitivity
The phase loss sensitivity of the circuit breaker/MSP ensures that it trips in
the event of the loss of a phase and the resulting overcurrents in the other
phases.
During normal operation, the device should have a three-pole load. To pro-
tect single-phase loads or direct current loads, all 3 main conducting paths
should be switched in series
Explosion protection Note
In the case of a three-pole load, at 3 to 8 times the set current, the release
time deviates by a maximum of ± 20 % and therefore complies with the
requirement of DIN VDE 0165 and EN 50019.
The 3RV10 circuit breakers (MSP) for motor protection, CLASS 10, and the
3RV11 circuit breakers for motor protection with overload relay function,
CLASS 10, have ATEX-Approval according to EU-requirement 94/9/EG
(DMT-Certificate).
3RV1 Circuit breaker/MSP
SIRIUS System Manual
A5E40534713002A/RS-AA/001 2-11
Characteristics The tripping characteristic of the inverse-time delayed overload release
(thermal overload release, a-release) is valid for direct current and
alternating current with frequencies of 0 to 400 Hz.
The characteristics are valid for tripping operations from a cold state. From a
warm state, the release times can be reduced up to 75 % depending on the
motor current and the ambient temperature.
The tripping characteristics of the instantaneous electromagnetic overcur-
rent releases (short-circuit release, n-release) is based on the rated current
In, which in the circuit breaker/MSPs with adjustable overload releases is
also the upper value of the adjustment range.
The following is a chart of the time-current characteristic:
Fig. 2-6: Time-current characteristic, chart
Time-current characteristics, current-limiting characteristics and I2t charac-
teristics can be requested directly from your sales representative, if neces-
sary.
10
5
2
1
10 000
5000
2000
1000
500
200
100
50
20
10
5
0,2
1
0,5
0,02
0,1
0,05
0,002
0,01
0,005
100
60
40
2
0,6 0,8 12346810
0,001 20 30 40 80 x n
NSB 00004a
min
s
60
Current
two-pole
load
Class 10
three-pole
load
Class 10
Opening time
three-pole
load
Class 20
3RV1 Circuit breaker/MSP
SIRIUS System Manual
2-12 A5E40534713002A/RS-AA/001
Frequency sensitivity of
the short-circuit
releases
The characteristics of the short-circuit releases apply to frequencies of
50/60 Hz. For lower frequencies, such as 16 2/3Hz, for higher frequencies
up to 400 Hz, and for direct current, appropriate correction factors have to
be taken into account.
The following characteristic curve illustrates the frequency sensitivity of the
short-circuit releases:
Fig. 2-7: Frequency sensitivity of the short-circuit releases
The increase in tripping current is approximately 40 % for DC voltage.
40
30
20
10
0
-10
-20
-30
050
100 200 250 300 350 400 Hz150
Tripping current
Change in %
3RV1 Circuit breaker/MSP
SIRIUS System Manual
A5E40534713002A/RS-AA/001 2-13
2.3 Application and areas of use
The tripping characteristics of the 3RV1 circuit breaker/MSPs are designed
primarily to protect three-phase induction motors. The circuit breaker/MSPs
are therefore also referred to as motor protecting switches. In Europe, the
3RV10 circuit breaker/MSPs for motor protection can also be used in the
protection of systems.
2.3.1 Motor protection
Current setting The current of the motor that is to be protected is set on the adjustment
scale. This sets the integrated overload protection of the motor current. The
short-circuit release is set at the factory to 13 times the value of the rated
current (the highest value on the current scale) of the circuit breaker/MSP.
This ensures problem-free startup and reliable protection of the motor.
Phase loss
sensitivity
The phase loss sensitivity of the circuit breaker/MSP ensures that it trips in
the event of the loss of a phase and the resulting overcurrents in the other
phases.
CLASS10/CLASS20 Circuit breaker/MSPs of frame sizes S00 to S3 (0-100 A) with thermal over-
load releases comply with tripping class 10 (CLASS 10). Circuit breaker/
MSPs with the CLASS 20 tripping characteristic are also available for frame
sizes S2 and S3 (11-100 A) for longer startup conditions.
2.3.2 Transformer protection
Inrush current In the case of primary protection of control transformers, the high inrush
currents that occur when the transformers are switched on often result in
the unwanted tripping of the protective devices.
Therefore, the 3RV14 circuit breaker/MSPs have overcurrent releases for the
protection of transformers that are set at the factory to approximately 19
times the rated current. This makes it possible to protect transformers in
which the inrush currents reach peak values of up to 30 times the rated cur-
rent with circuit breaker/MSPs in the primary circuit. The 3RV14 for trans-
former protection come in frame sizes S0 and S2 (0 to 40 A).
In the case of control transformers with low inrush current (SIEMENS 4AM
control transformers, for example), this is not required. 3RV10 circuit
breaker/MSPs can be used. In these lower inrush applications the 3RV14
devices are not UL listed for the protection of transformers.
2.3.3 Starter protection The 3RV13 starter protection switches are circuit breakers without overload
releases. They are used together with a contactor and overload relay if the
circuit breaker/MSP is not to be triggered in the case of overload tripping.
Like the 3RV10 the short-circuit release is set at 13 times the rated current.
The 3RV13 are available in frame sizes S0 to S3 (0 to 100 A).
3RV1 Circuit breaker/MSP
SIRIUS System Manual
2-14 A5E40534713002A/RS-AA/001
2.3.4 Motor protection with overload relay function
3RV11 circuit breakers/MSPs with the overload relay function are available
for frame sizes S0, S2, and S3.
Description The 3RV11 devices have the same overload and short-circuit trip characteris-
tics as the 3RV10. However the overload release doesn’t effect the switch-
ing mechanism of the circuit breaker/MSP. In the event of an overload, the
circuit breaker/MSP remains switched on.
The overload release uses two side mounted auxiliary contacts
(1NO + 1NC), that switch in the event of an overload. The auxiliary contacts
can be used for signalling or can be used to disconnect a downstream con-
tactor. After the circuit breaker/MSP has cooled down, the auxiliary contacts
are reset automatically.
Caution
In the overload range, the circuit breaker/MSP does not protect itself with
the overload relay function. You must therefore ensure that the power is
safely disconnected by means of a downstream switching device (e.g. a
contactor).
Fixed link: auxiliary
contacts with circuit
breaker/MSP
Note
The auxiliary contacts are factory mounted to the 3RV11 circuit breaker/MSP
on the right side and cannot be removed.
Diagrams
Fig. 2-8: Circuit breaker/MSP with overload relay function (frame sizes S0 to S3)
S0: 3RV11 21-.... S2: 3RV11 31-.... S3: 3RV11 42-....
TEST
RV-00588
TEST
RV-00589
TEST
3RV1 Circuit breaker/MSP
SIRIUS System Manual
A5E40534713002A/RS-AA/001 2-15
2.3.5 Switching direct current
The 3RV1 circuit breaker/MSPs for alternating current are suitable for
switching direct current. However, you must note the maximum permissible
DC voltage per conducting path. In the case of higher voltages, series con-
nection of 2 or 3 conducting paths is required.
Response thresholds The response thresholds of the overload releases remain unchanged. The
response thresholds of the short-circuit releases are increased with direct
current by approximately 40 %.
The following table lists suggestions for switching direct current:
Double ground fault Note
In the case of the circuit with 2-pole switching and an ungrounded system, it
is assumed that even in the event of a double ground fault that bridges two
contacts, safe disconnection still occurs.
2.3.6 Main and emergency stop switches
Since the circuit breaker/MSPs meet the requirements for disconnectors in
acc. with IEC 60947-3 and the additional test requirements for circuit
breaker/MSPs with disconnector features in acc. with IEC 60947-2, they can
be used with the appropriate accessories as main and emergency stop
switches. They must also comply with DIN VDE 0113.
Suggestion Circuit
breaker/
MSP
Frame
size
Max.
permissible
direct voltage EI
Meaning
3RV1. S00 to
S3
150 V DC 2-pole switching
Ungrounded system
If a ground fault can be excluded, or if every
ground fault is immediately corrected
(ground-fault monitoring), the maximum per-
missible DC voltage can be tripled.
3RV1. S00 to
S3
300 V DC 2-pole switching
Grounded system
The grounded pole must always be assigned
to the individual conducting path so that in
the event of a ground fault there are always
2 conducting paths in series.
3RV1. S00 to
S3
450 V DC 1-pole switching
Grounded system
3 conducting paths in series.
The grounded pole should be assigned to
the non switched conducting path.
Table 2-4: Suggestions for switching direct current
L-
M
L
+
L-
L
M
+
L-L
M
+
3RV1 Circuit breaker/MSP
SIRIUS System Manual
2-16 A5E40534713002A/RS-AA/001
2.4 Accessories
2.4.1 Attachable accessories: Overview
Auxiliary switches, alarm switches, auxiliary releases and other accessories
can be easily attached to the circuit breaker/MSPs without tools, as
required.
Accesso-
ries
Function/use Width Attach
to
Transverse
auxiliary
switch
The contacts of the auxiliary switches close and open together with the main
contacts of the circuit breaker/MSP. Variants:
1 changeover contact
1 NO + 1 NC contact
2 NO contacts
Width of
the circuit
breaker/
MSP
remains
the same
Front
Electroni-
cally opti-
mized
transverse
auxiliary
switch
One transverse auxiliary switch can be attached for each circuit breaker/MSP:
Variants:
1 changeover contact
Lateral
auxiliary
switch
One lateral auxiliary switch can be attached for each circuit breaker/MSP:
1 NO + 1 NC contact
2 NO contacts
2 NC contacts
2 NO + 2 NC contacts
9mm
9mm
9mm
18 mm
Left side
Alarm switch
for frame
sizes S0, S2
and S3
One alarm switch can be attached at the side of the circuit breaker/MSPs with
rotary switches.
The alarm switch has two contact systems:
One contact system (1 NO + 1 NC) reports a general
tripping operation, irrespective of whether it was caused by a short cir-
cuit, overload or auxiliary release.
The other contact system (1 NO + 1 NC) only switches in the event of a
short circuit tripping operation.
To reset the circuit breaker/MSP after a short circuit, the alarm switch must be
reset manually after the cause of the error has been eliminated.
18 mm
Shunt
release
Remote release of the circuit breaker/MSP:
Via PLC: The coil of the release should be connected to the voltage only
briefly.
Especially suitable for emergency stop disconnection by means of appro-
priate emergency stop switches in acc. with DIN VDE 0113.
18 mm Right
side
Accesso-
ries can-
not be
attached
on the
right of a
circuit
breaker/
MSP
with a
relay
function
(3RV11).
Under-
voltage
release
Trips the circuit breaker/MSP in the event of a voltage interruption (e.g. when
the power plug is removed) and prevents the motor starting up inadvertently
when the voltage returns.
Under-
voltage
release with
leading
auxiliary
contacts
2 NO
Function and use, see undervoltage release.
Additional function:
The auxiliary contacts isolate the undervoltage release from the power
system on both sides in the event of breaking or a tripping operation and
thus prevent voltage distortion to the control circuit when the switch is in
the off position.
It is possible to reset the circuit breaker/MSP because the contacts reset.
Table 2-5: Attachable accessories
3RV1 Circuit breaker/MSP
SIRIUS System Manual
A5E40534713002A/RS-AA/001 2-17
2.4.2 Auxiliary contacts 3RV19 01-.., alarm switch 3RV19 21-111 and auxiliary release 3RV19 .2-....
The maximum configuration for each 3RV1 circuit breaker/MSP is one trans-
verse auxiliary contact, one side mounted auxiliary contact with 2 contacts,
one alarm switch, and one auxiliary release. An alternative to the transverse
auxiliary contacts and one side mounted auxiliary contact with 2 contacts
would be to use a side mounted auxiliary contact with 2 NO + 2 NC. So
with any one circuit breaker/MSP a maximum of 4 auxiliary contacts with
auxiliary release can be used.
Possible combinations The following combinations of auxiliary switches and alarm switches or of
auxiliary switches are possible:
Auxiliary contacts with 2 contacts and alarm switches can be installed
individually or together. The side-mounted auxiliary contact is installed on
the left of the alarm switch.
Transverse and lateral auxiliary switches can be combined. Maximum of
4 auxiliary contacts is possible.
One auxiliary release can be attached on the right for each circuit breaker/
MSP
Accesso-
ries
Function/use Width Attach
to
Disconnect-
ing module
for frame
sizes S0 and
S2
The supply is fed to the circuit breaker/MSP via the disconnecting module.
A connector which can only be removed when the circuit breaker/MSP is
switched off isolates the circuit breaker/MSP from the power system on
3poles.
The shock-protected isolation position is easily visible and is secured by a pad-
lock to ensure that the connector cannot be used during maintenance work,
for example.
Width of
the circuit
breaker/
MSP
remains
the same
Upper
side/ line
side
Motorized
remote-con-
trol mecha-
nism
for frame
sizes S2 and
S3
The circuit breaker/MSPs can be opened and closed via the remote-controlled
mechanism by means of electrical commands. This enables a load or system
to be disconnected from and then reconnected to the power system from an
operator control panel.
The circuit breaker/MSP can be locally disconnected from and reconnected to
the remote-control mechanism.
148 mm
Rotary
switch
extension for
the door
The rotary switch extension for the door consists of a knob, a drive coupling
and an extension shaft. They comply with IP65. The door interlock prevents
the enclosure door being opened inadvertently when the switch is in the on
position. The off position can be secured with a maximum of 3 padlocks.
Depends
on the
application
Front
mount
Table 2-5: (cont.) Attachable accessories
3RV1 Circuit breaker/MSP
SIRIUS System Manual
2-18 A5E40534713002A/RS-AA/001
Mounting the
auxiliary contacts
The auxiliary switches, alarm switches, and auxiliary releases are mounted
in the same way for all frame sizes:
Transverse auxiliary contacts (3RV19 01-1D, -1E, -1F, -1G, -2E)
Fig. 2-9: Mounting the transverse auxiliary switch (frame size S00)
Side-mounted auxiliary contacts (3RV19 01-..)
Undervoltage release (3RV19 .2-....)
Fig. 2-10: Mounting/removing the side mount auxiliary contacts/undervoltage release
(example: frame size S00)
3RV1901-1D
3RV1901-.E
3RV1901-1F
3RV1901-1G
2
1
34
1
2
RV -01084
3RV1901-.A
3RV1901-.B
3RV1901-.C
3RV1901-.J
1
2
1
3RV19.2-1A..
2
3RV19.2-1C..
3RV19.2-1D..
2
3
3
3
1
1
3RV1 Circuit breaker/MSP
SIRIUS System Manual
A5E40534713002A/RS-AA/001 2-19
Voltage ranges of the
auxiliary releases
One undervoltage release or shunt release can be installed for each circuit
breaker/MSP. The following voltage ranges are possible:
Auxiliary release Frequency
Undervoltage release DC
24 V
AC 50 Hz AC 60 Hz
24 V
110 V
230 V
400 V
415 V
500 V
120 V
208 V
240 V
480 V
Undervoltage release
with leading
auxiliary contacts 2NO
230 V
400 V
415 V
240 V
480 V
Shunt release AC 50/60 Hz
100 % ED 1)
1)Transformer operational voltage of the lower mark of the voltage range at 0.85 (Tu = 60 °C)
is valid for 100 % (continuous) duty cycle only at AC 50/60 Hz
AC 50/60 Hz; DC
5 sec.. ED 2)
2)Transformer operational voltage of the lower mark of the voltage range at 0.9 (Tu = 60 °C) is
valid for 5 seconds duty cycle at AC 50/60 Hz and DC
20 – 24 V
90 – 110 V
200 – 240 V
350 – 415 V
500 V
20 – 70 V
70 – 190 V
190 330 V
330 – 500 V
500 V
Table 2-6: Voltage ranges of the auxiliary releases
3RV1 Circuit breaker/MSP
SIRIUS System Manual
2-20 A5E40534713002A/RS-AA/001
Mounting the alarm
switch
The following table explains how the 3RV19 21-1M alarm switch is mounted
onto the circuit breaker/MSP (frame sizes S0, S2 and S3):
Drawing Step Procedure
1Press and hold down the trans-
port safety button on the inside
of the alarm switch.
2Then press the blue RESET
button on the front of the alarm
switch.
3Hook the alarm switch onto the
circuit breaker/MSP.
4Move the alarm switch towards
the circuit breaker/MSP until
you hear it click into place.
Table 2-7: Testing overload tripping (example: frame size S0)
2
3
1 2
3RV 19 21-1M
3
4
3RV1 Circuit breaker/MSP
SIRIUS System Manual
A5E40534713002A/RS-AA/001 2-21
Alarm switch
(signalling switch)
signals
The alarm switch has two signals:
Tripped (short-circuit, overload or tripping through a shunt trip)
Short circuit signal (short circuit only)
The following table lists the signals, the status of the alarm switch, and the
procedure required:
Drawing Status Procedure
Tripped signal
Circuit breaker/MSP is
in the tripped position
Alarm switch:
LED is Red
RESET button (blue):
remains depressed
Switch off (Off position) and
then switch on again (On posi-
tion of the circuit breaker/
MSP)
Short circuit
Circuit breaker/MSP is
in the tripped position
Alarm switch:
LED is Red
RESET button (blue):
pushed out
Push in the RESET-button
(blue) on the Alarm switch
then switch the circuit
breaker/MSP off (Off posi-
tion) and
then switch it back on again
(On position of the circuit
breaker/MSP)
Table 2-8: Alarm switch with tripped signal and short circuit signal
21
3RV1 Circuit breaker/MSP
SIRIUS System Manual
2-22 A5E40534713002A/RS-AA/001
2.4.3 Motorized remote-control mechanism 3RV19 .6-....
The motorized remote-control mechanism is available for
230 V AC, 50/60 Hz and 24 V DC
Frame size S2: Inmax = 50 A
Frame size S3: Inmax = 100 A
Mounting and
connection
The following table shows you how to mount and connect the motorized
remote-control mechanism:
Drawing Step Procedure
1Remove the Allen key from the
cover of the motorized remote-
control mechanism.
2Use the Allen key to change the
selector switch to "Manual".
3/4 Undo the 2 screws and remove
the cover.
5/6 Undo the 4 screws on the remote-
controlled mechanism, and
remove it.
(Pozidriv 2).
Table 2-9: Mounting the remote-control mechanism (example: frame size S2)
1
3
3
4
2
MANUAL
AUTOMATIC
2
5(4 x)
6
3RV1 Circuit breaker/MSP
SIRIUS System Manual
A5E40534713002A/RS-AA/001 2-23
7Screw the frame onto the mount-
ing surface using 4 screws M4
(Frame size S2), M5 (Frame size
S3)
8/9 Attach the circuit breaker/MSP
using 2 screws.
Attention:
Use screws 14 mm in length.
10 Attach the ground wire.
11 Connect the main and control
wires to the circuit breaker/MSP.
12 If desired, set MANUAL RESET:
Remove the screw from the
RESET lever.
13-15 Put the remote-control mecha-
nism module into place,
making sure that the driver covers
the knob on the circuit breaker/
MSP, and screw it on.
Drawing Step Procedure
Table 2-9: (cont.) Mounting the remote-control mechanism (example: frame size S2)
7
9
9
7
8
S2: M4 / S3: M5
M5 (4 x)
3RV19 21-1M
15
12
Manual-
RESET
14
13
(4 x)
Automatic-
RESET
10
11
3RV1 Circuit breaker/MSP
SIRIUS System Manual
2-24 A5E40534713002A/RS-AA/001
Warning
Do not set the "Automatic" position or operate the remote-control mecha-
nism when open! There is a risk of injury!
Manual RESET Remove the screw from the RESET lever (step 12)
16-18 Screw the control wires for the
remote-control mechanism onto
the connector, and insert it.
19 Set the current.
20/21 Put the cover on, and screw it
tightly.
22 Use the Allen key to switch to
AUTOMATIC and replace the Allen
key in the cover.
Drawing Step Procedure
Table 2-9: (cont.) Mounting the remote-control mechanism (example: frame size S2)
16
17
21
21 22
(22)
20
18
19
UC
3RV1 Circuit breaker/MSP
SIRIUS System Manual
A5E40534713002A/RS-AA/001 2-25
2.4.4 Disconnecting/isolator module 3RV19 .8-1A
The disconnecting/isolator module is suitable for creating a visible isolating
distance. The isolating connector can only be removed in a deenergized
state. The isolating distance can be secured with padlocks when open.
Disconnecting modules are available for the circuit breakers/MSPs of frame
sizes S0 and S2.
Mounting sequence for
the disconnecting/
isolator module and
Transverse auxiliary
contacts
Attention
The disconnecting/isolator module covers the terminal screws of the trans-
verse auxiliary switch. We therefore recommend that you use the lateral
auxiliary switches or that you only install the disconnecting module once the
transverse auxiliary switch has been wired.
Mounting The modules are mounted in the same way for frame sizes S0 and S2.
The following diagrams show you how to mount the disconnecting module.
Example shown for frame size S0 (3RV1928-1A):
Fig. 2-11: Mounting the disconnecting module (example: frame size S0)
1
3
2
3RV19 28-1A
3RV1. 2
5
4
7
8
8
6
3RV1 Circuit breaker/MSP
SIRIUS System Manual
2-26 A5E40534713002A/RS-AA/001
Disconnecting and
locking
The disconnecting/isolator module can be locked and sealed or secured with
two padlocks if the connector is removed during maintenance work, for
example. The disconnecting/isolator module for frame size S0
(3RV19 28-1A) can use a padlock with a max. locking arm diameter of 6 mm,
for frame size S2 (3RV19 38-1A) a padlock with a max. locking arm diameter
of 9 mm can be used. The circuit breaker/MSP itself can also be secured
with a third padlock.
Fig. 2-12: Locking the disconnecting module (example: frame size S0)
Terminal cover
(frame size S2)
A terminal cover (3RT1936-4EA2) is available for the disconnecting module
in frame size S2 (3RV1938-1A) that protects the contacts from dirt and pro-
vides additional shock protection.
Fig. 2-13: Locking the disconnecting module and mounting the cover (frame size S2)
1
3
2
5
5
4
4
3RV19 38-1A
4
2
1
33RT19 36-4EA2
3RV1. 3
3RV1 Circuit breaker/MSP
SIRIUS System Manual
A5E40534713002A/RS-AA/001 2-27
2.4.5 Thru-the door rotary operators 3RV19 .6-..
Thru-the-door rotary operators are available for frame sizes S0, S2, and S3.
They consist of a lockable rotary handle with a detachable door coupling, an
extension shaft, and a connector for the switch drive.
There are two basic designs available. The thru-the-door rotary operator
3RV19 26-0. for standard applications and the thru-the-door rotary operator
3RV19 .6-2. for harsh conditions. Both designs have an IP65 rating and can
be locked in the OFF-position with up to three padlocks.
Both operators are available with either black/grey and/or red/yellow for
emergency-stop handle styles.
The thru-the-door rotary operator for harsh conditions also meet the discon-
nection requirements according to IEC 60 947-2.
3RV1 Circuit breaker/MSP
SIRIUS System Manual
2-28 A5E40534713002A/RS-AA/001
Thru-the door rotary operator 3RV19 26-0.
Mounting
Fig. 2-14: Mounting the thru-the-door rotary operator 3RV19 26-0. (example: frame size S2)
6
7
min. 16 mm
max. 20 mm
3
1
2
4
5
3RV19 26-0B, -0C: 130 mm
3RV19 26-0K, -0L: 330 mm
0.7 ... 0.9 Nm
3RV1 Circuit breaker/MSP
SIRIUS System Manual
A5E40534713002A/RS-AA/001 2-29
Opening the door The following table shows you how the cubicle door can be opened using
the thru-the-door rotary operator:
Opening the door with
great force
Note
If the circuit breaker/MSP is in the ON position and the door is opened with
a force >150 N to 200 N, the cap of the extension shaft is separated from
the rotary switch of the circuit breaker/MSP to prevent the circuit breaker/
MSP being destroyed.
The circuit breaker/MSP remains in the ON position.
Fig. 2-15: Operation note: Thru-the-door rotary operator 3RV19 26-0.
Drawing Procedure
To open the cubicle door, set the
circuit breaker/MSP to O (OFF).
This releases the extension shaft
from the rotary switch and allows
the door to be opened.
If you want to open the enclosure
door during operation, you can
override the procedure by press-
ing the button at the side of the
rotary knob (step 1).
To close it during operation, press
the button again so that the exten-
sion shaft snaps into place again.
Table 2-10: Opening a enclosure door using the thru-the-door rotary operator
2
1
1
2
ca.150 ... 200 N
3RV1 Circuit breaker/MSP
SIRIUS System Manual
2-30 A5E40534713002A/RS-AA/001
The extension shaft must then be remounted on the circuit breaker/MSP
and the rotary switch extension for the door as follows:
Locking When the rotary switch is in the OFF position, it can be secured with up to
3 padlocks (e.g. during maintenance work on the system).
Fig. 2-16: Locking the thru-the-door rotary operator
Drawing Step Procedure
1Switch the circuit
breaker off, and turn
the rotary switch on
the door to OFF.
2Put the cap of the
extension shaft on the
rotary switch of the cir-
cuit breaker/MSP, and
put the extension shaft
in the cap.
3Close the enclosure
door.
Table 2-11: Mounting the extension shaft
1
3
2
1
1
2
max.
ø 8 mm
3RV1 Circuit breaker/MSP
SIRIUS System Manual
A5E40534713002A/RS-AA/001 2-31
Thru-the door rotary operator for harsh conditions 3RV19 .6-2.
Mounting
Fig. 2-17: Mounting the thru-the-door rotary operator 3RV19 .6-2. (example: frame sizes S0 and S2)
8
7
RV-00593
6
5
RV-00592
3RV19 36: M4
3RV19 46: M5
1.2 ... 1.5 Nm
1.2 ... 1.5 Nm
1
2
RV-00590
RV-00591
3
4
RV-00594
A (mm) B (mm)
3RV19 26 50 111
3RV19 36 60 160
3RV19 46 60 185
C (mm) D (mm)
3RV19 26 163 463
3RV19 36 215 515
3RV19 46 240 540
46 ±4
4.5
RV
-0
0596
1.1 - 1.3 Nm
M4: 2.6 - 3 Nm
10
9
(4 x)
11
Mount the 3RV1 frame size S0
by simply snapping it on the
DIN rail
Frame size S0
Frame sizes S2/S3
Mount the 3RV1
frame size S2/S3 by panel mounting (2 x)
3RV1 Circuit breaker/MSP
SIRIUS System Manual
2-32 A5E40534713002A/RS-AA/001
Opening the door In order to open the enclosure door, turn the handle in the Off position. The
extension shaft disengages from the handle in this position and the door can
be opened.
Opening the door with
great force
Note
When the circuit breaker/MSP is in the On position (”I“-position) and the
door is opened with a force of 800 Nm, the operator can be destroyed. In
this case the circuit breaker/MSP remains turned on. Anything under a force
of 800 Nm, the operator will remain locked to the door.
Locking
Fig. 2-18: Locking the thru-the-door rotary operator (example: frame size S0)
The operator handle can be padlocked inside the enclosure. To do this the
circuit breaker/MSP must be in the Off position.
Fig. 2-19: Locking the thru-the-door rotary operator outside the enclosure
The operator can also be locked from outside the enclosure on the rotary
handle.
To do this the circuit breaker/MSP must first be in the Off position. Then pull
out the retractable locking device that is built in the handle. This locking
device can hold up to five padlocks with a maximum locking arm diameter of
6 mm or three padlocks with a maximum locking arm diameter of 8.5 mm.
3.5 ... 4.5 mm
RV-00595
1
2
12
3RV1 Circuit breaker/MSP
SIRIUS System Manual
A5E40534713002A/RS-AA/001 2-33
2.4.6 Terminals for "Combination Motor Controller Type E" in acc. with UL 508
Since July 16, 2001, 1 inch air clearance and 2 inch creepage distance is
required for "Combination Motor Controller Type E" on the input side in acc.
with UL 508. For the 3RV10 circuit breakers/MSPs frame size S0 use termi-
nal block 3RV1928-1H and for frame sizes S3 use terminal block
3RT1946-4GA07. The 3RV10 in frame size S2 complies with the required air
clearance and creepage distance without a terminal block.
These terminal blocks cannot be used in the S0 frame size at the same time
as the 3RV19.5 3-phase busbars or in the S3 frame size at the same time as
a transverse auxiliary switch.
Attention
Terminal blocks are not required for use in acc. with CSA.
Fig. 2-20: Terminals for "Combination Motor Controller Type E"
3RV19 28-1H
Self-Protected
Combination
Controller Type E
3RT19 46-4GA07
1
2
S3
S0
3RV1 Circuit breaker/MSP
SIRIUS System Manual
2-34 A5E40534713002A/RS-AA/001
2.4.7 Enclosures and mounting accessories
Molded-plastic enclosures (IP55) are available if you want to install circuit
breakers/MSPs as single units. All the enclosures are equipped with neutral
and ground terminals. Above and below are two openings that can be
knocked out for cable glands. On the back of the enclosure there are
2 precut openings. All the cable bushings have metric dimensions. The sur-
face casings can be sealed. There is space in the enclosure on the rail for
additional modular terminal blocks.
Widths The widths of the enclosures depend on whether auxiliary releases are used:
54 mm: circuit breaker/MSP + side-mount auxiliary contact
72 mm/82 mm: circuit breaker/MSP + side-mount auxiliary contact+
auxiliary release
Mounting the surface
mount enclosure
Fig. 2-21: Molded-plastic surface mount enclosure (example: frame size S00)
Model Molded-
plastic... Width Frame size
Enclosure with actuator membrane for toggle
switch
Surface mount 54 mm, 72 mm S00
Flush mount 72 mm S00
Lockable enclosure with rotary switch Surface mount 54 mm, 72 mm
82 mm
S0
S2
Flush mount 72 mm S0
Lockable enclosure with emergency stop rotary
switch (red/yellow)
Surface mount 54 mm, 72 mm
82 mm
S0
S2
Flush mount 72 mm S0
Table 2-12: Enclosures for 3RV1 circuit breakers/MSPs
3
4
1
2
Neutral/ground terminals
3RV1 Circuit breaker/MSP
SIRIUS System Manual
A5E40534713002A/RS-AA/001 2-35
Mounting the
flush mount enclosure
Fig. 2-22: Molded plastic flush mount enclosure (example: frame size S00)
Front plates Molded-plastic-front plates with IP55 degree of protection are suitable for
any housing:
4
4
5
1
223
3
1
Front plates and
accessories Model Frame
size
Front plates With actuator membrane and support for
switch S00
With lockable rotary switch S0, S2, S3
With lockable emergency-stop rotary
switch (red/yellow) S0, S2, S3
Accessories Support for front plate S0
Table 2-13: Front plates for any housings
3RV1 Circuit breaker/MSP
SIRIUS System Manual
2-36 A5E40534713002A/RS-AA/001
Mounting the front plates
Frame size S00
Fig. 2-23: Mounting the front plate (example: frame size S00)
Frame sizes S0, S2, S3
Fig. 2-24: Mounting the front plate (example: frame size S0)
3RV19 13-4C 3RV19 13-4B
e.g.
Enclosure door
65
43
5
2
M6
M3 1
VU-01015
65
43
5
2
M6
M3
e.g. Enclosure door
M3 4
1
2
3
3RV19 23-4G
3RV19 23-4.
M3
2
1
a
3RV1. 2 86.5
3RV1. 3 139.0
3RV1. 4 164.5
3RV19 23-4. + 3RV19 23-4G (only for frame size S0)
3RV1 Circuit breaker/MSP
SIRIUS System Manual
A5E40534713002A/RS-AA/001 2-37
Accessories for the housings and front plates
The following accessories are available for the housings and front plates of
the circuit breakers/MSPs:
Replacement actuator membrane 3RV19 13-7F (for frame size S00)
Locking device for 3 padlocks 3RV19 13-6B (for frame size S00)
Emergency-stop button (red/yellow) 3RV19 13-7D (for frame size S00)
Emergency-stop button (red/yellow) with safety lock 3RV19 13-7E (for
frame size S00)
Indicator lights 3RV19 03-5. (for frame sizes S00, S0, S2)
Fig. 2-25: Accessories for the enclosures and front plates (frame size S00)
Locking device 3RV19 13-6B (for frame size S00)
The locking device can be used on the inside of the housings or front plates.
To do this, remove the frame of the actuator membrane. The locking device
can be secured with up to 3 padlocks that can prevent the circuit breaker/
MSP from being switched on during maintenance work, for example.
Emergency-stop button 3RV19 13-7. (for frame size S00)
The emergency-stop button is attached to the actuator membrane. When
hit, the circuit breaker/MSP is switched off and the button locks into posi-
tion. You can release the button by turning it or using a key. The circuit
breaker/MSP can then be switched on again.
Indicator lights 3RV19 03-5B (for frame sizes S00, S0, S2)
Indicator lights are available for the housings and front plates of circuit
breakers/MSPs in frame sizes S00, S0, and S2. They contain a glow lamp
and red, green, yellow, orange, and transparent lenses. Indicator lights are
available for the following voltage ranges: 110-120 V, 220-240 V, 380-415 V
and 480-500 V.
3RV19 13-6B
3RV19 13-7D
3RV19 13-7E
1
2
3RV19 13-7F
3RV1 Circuit breaker/MSP
SIRIUS System Manual
2-38 A5E40534713002A/RS-AA/001
Installation of the
indicator lights
There is a precut opening on the front of the housing that can be knocked
out to install an indicator light
Fig. 2-26: Indicator light installation in a molded-plastic housing (example: frame size S00)
2
1
16 mm
3RV19 03-5.
3RV1 Circuit breaker/MSP
SIRIUS System Manual
A5E40534713002A/RS-AA/001 2-39
2.4.8 Busbar adapter 8US1 (Fastbus system)
To enable the circuit breakers/MSPs to be mounted without using up too
much space, and to ensure that the infeed is economical in terms of both
time and money, the switches can be mounted directly onto busbar systems
using busbar adapters.
The circuit breakers/MSPs are snapped onto the adapter and connected at
the input side. This prepared unit is mounted directly onto the busbar sys-
tems, thus both attaching it mechanically and establishing electrical contact.
Busbar systems The adapters are suitable for the following systems:
Accessories The following accessories are available for busbar adapters:
Modules that can be mounted on either side to widen the adapters
Busbar holder for 3 rails
Molded-plastic covers for 3 terminals (40 mm system)
Molded-plastic cover profiles for shock protection
Measurements The following table lists the dimensions of the busbar adapters and acces-
sories.
1) Up to 460 V AC with max. short-circuit breaking capacity of 25 kA
2) Not to be used for voltages < 480 V
short-circuit breaking capacity 480/500/525 V AC
- Up to In=25 A: max. 30 kA
- Up to In=90 A: max. 16 kA
short-circuit breaking capacity 690 V AC: max. 12 kA
Busbar systems with
center-to-center spacing
For copper busbars in acc. with DIN 46 433
Width Depth
40 mm systems 12 mm and 15 mm 5 mm and 10 mm
60 mm systems 12 mm to 30 mm 5 mm and 10 mm
Table 2-14: Busbar systems
System Busbar adapter and
accessories Length Width
For circuit
breakers/MSPs in
frame size
40 mm Circuit breaker/MSP
+ lateral auxiliary switch
121 mm
121 mm
45 mm
55 mm
S00, S0
S00, S0
Circuit breaker/MSP 139mm 55mm S2
Circuit breaker/MSP 182 mm
182 mm
70 mm
72 mm
S3 (to 400 V)1)
S3 (480 to 690 V)2)
Side module 139 mm
182 mm
13.5 mm
13.5 mm
S2
S3
60 mm Circuit breaker/MSP 182 mm 45 mm S00, S0
182mm 55mm S2
182 mm
182 mm
70 mm
72 mm
S3 (to 400 V)1)
S3 (480 to 690 V)2)
Side module 182 mm 13.5 mm S00 to S3
Table 2-15: Dimensions of the busbar adapters and accessories
3RV1 Circuit breaker/MSP
SIRIUS System Manual
2-40 A5E40534713002A/RS-AA/001
You can find additional information about load feeders on busbar systems in
Chapter 5.
Mounting circuit
breakers/MSPs on a
busbar system
Frame sizes S00/S0
The following illustrations show you how to mount circuit breakers/MSPs in
frame sizes S00 and S0 onto busbar adapters (8US1) and how to remove
them again, using frame size S00 as an example:
Fig. 2-27: Mounting circuit breakers/MSPs on busbar adapters (frame sizes S00 and S0)
10 mm
8US1. .1-5D
Link module
3RV1 Circuit breaker/MSP
SIRIUS System Manual
A5E40534713002A/RS-AA/001 2-41
Mounting circuit
breakers/MSPs on a
busbar system
Frame sizes S2/S3
The following illustrations show you how to mount circuit breakers/MSPs in
frame sizes S2 and S3 onto a busbar adapter:
Fig. 2-28: Mounting circuit breakers/MSPs on busbar adapters (frame sizes S2 and S3)
S2
8US1. 61-5FP08
1
8US11 11-4SM00
6-9 Nm
2
3
4
8
5
7
6
S3
(3x)
3RV1 Circuit breaker/MSP
SIRIUS System Manual
2-42 A5E40534713002A/RS-AA/001
Mounting
accessories
The following illustration shows you how to mount accessories for busbar
adapters for frame sizes S00 to S2:
Side module
Device holder
Extension piece
Outgoing terminal rail (for frame sizes S00 and S0 only)
Fig. 2-29: Accessories for busbar adapters (frame sizes S00 to S2)
Outgoing terminal rail
Extension piece
40 mm
1
2
1
2
Side module
Device holder
3RV1 Circuit breaker/MSP
SIRIUS System Manual
A5E40534713002A/RS-AA/001 2-43
2.4.9 Isolated 3-phase busbar system
For 3RV1 frame sizes S00, S0, and S2, 3-phase busbars can be used to
quickly and easily provide line side feeding when mounting circuit breakers/
MSPs on to DIN rail. There is only one power supply, via a feed-in terminal.
The 3-phase busbar systems are safe from fingers and are shock protected
DIN VDE 0106 Part 100. They are rated for the short-circuit stress that can
occur on the output side of the connected circuit breakers/MSPs.
Fig. 2-30: 3-phase busbar system (example: frame size S00)
Rated operational
voltage/current
Versions The 3-phase busbars take 2 to 5 circuit breakers/MSPs, depending on the
model. There are busbars with more generous spacing for circuit breakers/
MSPs with accessories attached on the side
3-phase busbar
3RV19 15-1CB
Protective cap
3RV19 15-6AB
Feeder lugs, connecton from
below 3RV19 15-5B
Feeder lugs, connecton from
above (3RV1915-5A))
Spacer
Rated operational voltage 690 V
Rated current Frame sizes S00, S0: 63 A
Frame size S2: 108 A
Table 2-16: Rated operational voltage/current
Frame size of
the circuit
breaker/MSP
Spacing Models
S00, S0 45 mm For 2, 3, 4, or 5 circuit breakers/MSPs
55 mm For 2, 3, 4, or 5 circuit breakers/MSP + acc.
63 mm For 2 or 4 circuit breakers/MSPs + accessories
S2 55 mm For 2, 3, or 4 circuit breakers/MSPs
75 mm For 2, 3, or 4 circuit breakers/MSPs + accessories
Table 2-17: Types of 3-phase busbars
3RV1 Circuit breaker/MSP
SIRIUS System Manual
2-44 A5E40534713002A/RS-AA/001
Combination of
frame sizes S00
and S0
Circuit breakers/MSPs in frame sizes S00 and S0 vary in height and depth.
They therefore cannot be combined on one busbar. You can combine two
busbars for circuit breakers/MSPs in frame sizes S0 and S00 using an exten-
sion piece.
Extending the bus It is possible to extend the busbars by clamping the connecting lugs of a
another bus (turned 180°) under the terminals of the last circuit breaker/MSP
(see the section on mounting).
Attention
Note the current-carrying capacity of the busbars when you extend them.
Accessories The following accessories are available for the isolated 3-phase busbar sys-
tem:
Feeder lugs from above (3RV1915-5A for S00, 3RV1925-5AB for S0,
3RV1935-5A for S2)
Feeder lugs from below (3RV1915-5B for S00, S0)
Connector
A connector links two 3-phase busbars over a space of 45 mm for circuit
breakers/MSPs in frame size S0 (left) and frame size S00 (right).
Protective cap for connecting lugs (3RV19 15-6AB)
Protective caps provide shock protection for spare slots. To extend the
bus, remove the protective caps.
Feeder lugs 3-phase feeder lugs make it possible to have greater conductor cross-sec-
tions than on the circuit breaker/MSP itself.
Tightening torque: 2 to 4 Nm (17.6 to 35.2 lb·in).
Feeder lugs – connec-
tion from below
Attention
The feeder lugs with connection from below is clamped on instead of a cir-
cuit breaker/MSP. Make sure you check how much space you require when
planning the 3-phase busbars.
Frame size of
the circuit
breaker/MSP
Connec-
tion Conductors Conductor
cross-section
S00, S0 From above Single- or multi-core
Finely stranded with wire end
ferrule
AWG
2.5 to 25 mm2
4 to 16 mm2
12 to 4
S00, S0 From below Single- or multi-core
Finely stranded with wire end
ferrule
AWG
6 to 25 mm2
4 to 16 mm2
10 to 4
S2 From above Single- or multi-core
Finely stranded with wire end
ferrule
AWG
2.5 to 50 mm2
1.5 to 35 mm2
14 to 0
Table 2-18: Conductor cross sections of the 3 phase feeder lugs
3RV1 Circuit breaker/MSP
SIRIUS System Manual
A5E40534713002A/RS-AA/001 2-45
Mounting the 3-phase
busbars
Fig. 2-31: Mounting the isolated 3-phase busbar system (frame sizes S00 to S0)
Frame size S0
Screw connection
Frame size S00
Cage-clamp
Frame size S00
Screw connection Turned
180°
3RV19 15-5B
3RV19 15-6AB
3RV19 15-1CB
3b
3a
3c
3
1
1
2
3RV19 25-5AB
3RV19 15-5B
3RV19 15-6AB
3RV19 15-1CB
8WA20 11-1DG30
Turned
180°
3RV19 15-5A
3RV19 15-1CA
3RV1 Circuit breaker/MSP
SIRIUS System Manual
2-46 A5E40534713002A/RS-AA/001
Fig. 2-32: Mounting the isolated 3-phase busbar system (frame size S2)
2.4.10 Link module for connection to a contactor
Link Module
Circuit breaker/
MSP-Contactor
When assembling a combination starter (load feeder) a link module between
the circuit breaker/MSP and the contactor is needed to provide both an elec-
trical and mechanical connection. The following types of link modules are
available:
Frame size S2
Screw connection
3RV19 35-5A
3RV19 35-6A
3RV19 35-1.
3RV19 35-1C
Operating voltage
Contactor
Frame size
Contactor
Frame size
Circuit breaker/MSP
AC and DC S00 S00
S00 S0
S0 S0
S2 S2
S3 S3
Table 2-19: Link module circuit breaker/MSP - contactor
3RV1 Circuit breaker/MSP
SIRIUS System Manual
A5E40534713002A/RS-AA/001 2-47
2.5 Mounting and connection
2.5.1 Installation
Mounting position You can install the 3RV1 circuit breakers/MSPs in almost any position.
Snap-on mounting The circuit breakers/MSPs are mounted by snapping them onto 35 mm rails
that comply with DIN EN 50 022. The circuit breakers/MSPs with a frame
size of S3 require a rail with an installation height of 15 mm. Alternatively,
they can also be snapped onto 75 mm rails.
Fig. 2-33: Mounting the circuit breakers/MSPs onto the rail
Panel mounting The circuit breakers/MSPs can be attached to a flat surface with 2 screws.
For circuit breakers/MSPs in frame sizes S00 and S0, two push-in lugs
(3RB1900-0B) (pack of 10) are also required.
Circuit breakers/MSPs in frame sizes S2 and S3 can be screwed directly
onto a base plate.
Fig. 2-34: Screw-on mounting of the 3RV1 (example: frame size S00)
S00
RV-00298
1
2
1
1
2
DIN EN 50022/23
S3
DIN EN 50022
RV-00226
3RB19 00-0B
Circuit breaker/MSP 3RV1
SIRIUS System Manual
2-48 A5E40534713002A/RS-AA/001
2.5.2 Connection
Tools The following items are required to connect the circuit breakers/MSPs:
Frame sizes S00 to S2: Pozidriv 2 screwdriver
Frame size S3: Allen key (4 mm)
Conductor
cross-sections
The typical SIRIUS conductor cross-sections apply (see Section 1.5.4
"Conductor cross-sections").
Screw-type terminals 3RV1 circuit breakers/MSPs with frame sizes S00 and S0 have terminals
with captive screws and terminal washers that enable you to connect
2 conductors, even if they have different cross-sections.
The box terminals of the circuit breakers/MSPs of frame sizes S2 and S3 can
also take 2 conductors with different cross-sections. With the exception of
circuit breakers/MSPs of frame size S3, which have terminal screws with a
4 mm Allen screw, all the terminal screws can be tightened using a standard
screwdriver or a Pozidriv screwdriver (size 2).
You can remove the box terminals from circuit breakers/MSPs with a frame
size of S3 to connect conductors with ring-tongue or connecting bars.
A terminal cover 3RT19 46-4EA1 is available as shock protection and to
ensure that you comply with the required creepages and clearances when
the box terminals are removed.
Soldering pin
connector
Circuit breakers/MSPs in frame size S00 can be soldered onto printed circuit
boards by means of a soldering pin connector. A soldering pin connector is
available for the main contacts only (3RV19 18-5A) or for the main contacts
and the transverse auxiliary contacts 1 NO +1 NC (3RV19 18-5B).
Circuit breaker/MSP 3RV1
SIRIUS System Manual
A5E40534713002A/RS-AA/001 2-49
Mounting the
soldering pin adapters
The soldering pin adapters are clamped above and below in the screw-type
terminals of the circuit breakers/MSPs. The power supply can also be taken
to the printed circuit boards via cables.
Fig. 2-35: Circuit breaker/MSP, soldering pin connector (frame size S00)
1
1
1
1
2
4
3
2
Circuit breaker/MSP 3RV1
SIRIUS System Manual
2-50 A5E40534713002A/RS-AA/001
2.5.3 Device circuit diagrams
Frame size S00
Fig. 2-36: Device circuit diagram (frame size S00, example: circuit breaker (MSP) for motor
protection 3RV10)
Frame sizes S0 to S3
Fig. 2-37: Device circuit diagram (frame sizes S0 to S3, example: circuit breaker (MSP) for motor
protection 3RV10)
max. 10 A
31L3L2L1
6
4
2T3
T2T1
5
11
14 12
3RV1901- 1D U
D2
D1
3RV1902-.A..
U
D1
D2 08
07
3RV1912-.C..
14
13 21
22
3RV1901-.E
C2
C1
3RV1902-.D..
I >> I >>
I >>
3RV1901- 1G
33 41
34 42
3RV1901-.A
4333
4434
3RV1901-.B
4232
41
31
3RV1901-.C
3RV1901-.J
13 21 31 43
14 22 32 44
2313
2414
3RV1901-1F
34
33 41
42
3RV1901-.A
4333
4434
3RV1901-.B
4232
4131
3RV1901-.C
max. 10 A
31L3L2
L1
64
2T3T2
T1
5
11
14 12
3RV1901-1D U
D2
D1
3RV1902-.A..
U
D1
D2 08
07
3RV1922-.C..
14
13 21
22
3RV1901-.E C2
C1
3RV1902-.D..
I >> I >>I >>
78
77 85
86
58
57 65
66
3RV1921-1M
3RV1901-1G
3RV1901-.J
13 21 31 43
14 22 32 44
3RV1901-1F
2313
2414
Circuit breaker/MSP 3RV1
SIRIUS System Manual
A5E40534713002A/RS-AA/001 2-51
Circuit breaker/MSP
with overload relay
function
Frame sizes S0 to S3
Fig. 2-38: Circuit breaker/MSP with overload relay function, device circuit diagrams (frame sizes S0
to S3)
max. 10 A
31L3L2L1
64
2T3
T2T1
5
I >> I >>I >>
98
97 95
96
34
33 41
42
3RV1901-.A
4333
4434
3RV1901-.B
4232
4131
3RV1901-.C
3RV1901-.J
13 21 31 43
14 22 32 44
11
14 12
3RV1901-1D
14
13 21
22
3RV1901-.E
3RV1901-1F
23
13
2414
3RV1901-1G
Circuit breaker/MSP 3RV1
SIRIUS System Manual
2-52 A5E40534713002A/RS-AA/001
2.6 Dimensional drawings (dimensions in mm)
Circuit breaker/MSP 3RV1
Fig. 2-41: 3RV10 31, 3RV13 31, 3RV14 31 (frame size S2)
Fig. 2-42: 3RV10 4, 3RV13 4 (frame size S3)
Fig. 2-39: 3RV10 11, 3RV16 (frame size S00) Fig. 2-40: 3RV10 21, 3RV13 21, 3RV14 21 (frame size S0)
1) Side-mount auxiliary contacts, 2-pole 7) Drilling pattern
2) Alarm switch (S0 to S3) or side-mount auxiliary contacts, 4-pole (S00 to S3) 8) 35 mm rail in acc. with EN 50022
3) Auxiliary release 9)
Mounting onto 35 mm rail, 15 mm high, in acc. EN 50 022
or
with EN 50 022
or 75 mm rail in acc. with EN 50023
4) Transverse auxiliary switch
5) Push-in lugs for screw mounting 10)4 mm Allen screw
6) Only with undervoltage release with leading auxiliary switch 11)Lockable in 0 position with shackle (3.5 to 4.5 mm in
diameter
1) 11) 3) 4)5)
8)
NSB 00026c
45
90
70
76
918
62
5
45 12
45
3,5
6)
2)
18
25
5
105
7)
11)
2) 5) 4)
8)
3)1)
NSB00027b
45
14
12
90
97
45 556
80
91
45
69
18 18
72
9
5
25
106
7)
20
5518 18
45
85
109
121
127
5
8
132
144
140
89
125
1) 2)
3) 4)
8)
NSB00028a
11)
9
5
30
130
7)
45
7018 18
116
165
150
5
7
8
132
153
157
146
10)11)
1) 2) 3)
4)
9)
NSB00029b
169
9
5
30
155
7)
Circuit breaker/MSP 3RV1
SIRIUS System Manual
A5E40534713002A/RS-AA/001 2-53
3RV11 circuit breaker/MSP with overload relay function
Fig. 2-45: 3RV11 42 (frame size S3)
1) Side-mount auxiliary contacts, 2-pole
2) Alarm switch or side-mount auxiliary contacts, 4-pole
3) Block for overload relay function
4) Transverse auxiliary switch
5) Push-in lugs for screw-type mounting
6) Drilling pattern
7) 35 mm rail in acc. with EN 50 022
8) Mounting onto 35 mm rails, 15 mm high, in acc. with EN 50 022 or 75 mm rails in acc. with EN 50 023
9) 4 mm Allen screw
10)Lockable in 0 position with shackle (3.5 to 4.5 mm in diameter)
Disconnecting/isolator module
Fig. 2-43: 3RV11 21, 3RV16 (frame size S0) Fig. 2-44: 3RV11 (frame size S2)
45
45
12
90
97
555
80
91
45
69
20
72 4)
7)
11) 5) 3)
2)1)
NSB00030b
18
9
5
25
106
6)
55
20
20
45
90
140
109
121
127
58
132
144
125
3)
4)
7)
11)
NSB00031c
2)1)
18
9
5
30
130
6)
70
90
20
45
116
150
57
8146
132
153
157
165
9) 3) 4)
8)
10)
NSB00032c
2)
1)
169
18
9
5
30
155
6)
Fig. 2-46: 3RV19 28-1A (for frame size S0) Fig. 2-47: 3RV19 38-1A (for frame size S2)
51
94
45
NSB00033a
96
144
55
NSB00034a
149
57
121
190
Circuit breaker/MSP 3RV1
SIRIUS System Manual
2-54 A5E40534713002A/RS-AA/001
Molded-plastic panel/surface mount enclosure
Fig. 2-48: 3RV19 13-1.... (for frame size S00)
a) 3RV19 13-1CA00: 85 mm
3RV19 13-1DA00: 105 mm
1) Knockout opening for M25
2) Knockout opening for rear M20 cable routing
b) with 3RV19 13-7D: 146.5 mm
with 3RV19 13-7E: 166.5 mm
The dimensions relate to the mounting surface
3) With safety lock
4) Max. shackle diameter for padlock is 8 mm
5) Indicator light 3RV19 03-5.
c) with 3RV19 13-7D: 64 mm
with 3RV19 13-7E: 84 mm
6) Locking device 3RV19 13-6B
7) Emergency-stop button 3RV19 13-7
d) The dimensions relate to the mounting surface
NSB 00035c
a)
77,5
45 19
145 - 148
4,5
88
7)
b) 99
b) 100,5 b) 143 d) 190
b)
c)
105
55
13
11 5)
1) 2)
4)
6)
3)
Fig. 2-49: 3RV19 23-1.... (for frame size S0) Fig. 2-50: 3RV19 33-1.... (for frame size S2)
a) 3RV19 23-1CA00: 85 mm
3RV19 23-1DA00: 105 mm
1) Knockout opening for M32 (left) and M40 (right)
2) Knockout opening for rear M32 cable entry
1) Knockout opening for M25 3) Opening for padlock with a max. shackle diameter of 8 mm
2) Knockout opening for rear M20 cable entry 4) Indicator light 3RV19 03-5.
3) Opening for padlock with a max. shackle diameter of 8 mm
4) Indicator light 3RV19 03-5.
150
18
181
235
250
7
25
2932
3)
NSB 00037c
1) 2)
4)
19
45
2)
145 - 148
4,5
155
a) 126 18
NSB 00036c
3)
1) 4)
Circuit breaker/MSP 3RV1
SIRIUS System Manual
A5E40534713002A/RS-AA/001 2-55
Cast-Aluminum panel/surface mount enclosure
Fig. 2-51: 3RV19 23-1.A01 for circuit breaker/MSP, frame size S0
Molded-plastic flush mount enclosure
Molded-plastic front plate
Fig. 2-54: 3RV19 13-4C (frame size S00)
160
170
135
52
116
105
1)
2)
2)
NSB 01088a
ON
I
O
OFF
O
M 25
M 25
2)
1) Leuchtmelder 3RV19 03-5.
2) Ausbrechöffnungen
für Verschraubung M25
1) Indicator light 3RV19 03-5.
2) Knockout opening for M25
Fig. 2-52: 3RV19 13-2DA00 (frame size S00) Fig. 2-53: 3RV19 23-2DA00/-2GA00 (frame size S0)
105
1)
max. 7
12 87
2)3)
95
1) Leuchtmelder 3RV19 03-5.
2) Ausbrechöffnungen für M25
3) Ausbrechöffnungen für M20
105 95
max. 6
12 87
1)2)3)
1) Leuchtmelder 3RV19 03-5.
2) Ausbrechöffnungen für M25
3) Ausbrechöffnungen für M20
1) Indicator light 3RV1903-5
2) Knockout opening for M25
3) Knockout opening for M20
1) Indicator light 3RV1903-5
2) Knockout opening for M25
3) Knockout opening for M20
40
NSB 00039a
85 56,5 10
12
62
70
4,5
ø 7
1)
1) Indicator light 3RV1903-5.
Circuit breaker/MSP 3RV1
SIRIUS System Manual
2-56 A5E40534713002A/RS-AA/001
Molded-plastic Front plate and Support
Fig. 2-55: 3RV19 23-4B, 3RV19 23-4E (frame sizes S0, S2, S3); 3RV19 23-4G (only for frame size S0)
Soldering pin adapters for main and auxiliary contacts
Fig. 2-56: 3RV19 18-5A/-5B (frame size S00)
40
NSB 00042a
85 56,5 10
1812
62
70
7,4ø 3,5
1)
1) Indicator light 3RV1903-5.
45
NSB00041
13,4
12
13,1
5
8,4
14,4 14,4
8,4
14,4
14,4
97,49
1039
59
49
5
2
Circuit breaker/MSP 3RV1
SIRIUS System Manual
A5E40534713002A/RS-AA/001 2-57
Thru-the-door rotary operators
Fig. 2-57: 3RV19 26-0. (short shaft for circuit breaker/MSP, frame sizes S0, S2, S3)
Fig. 2-58: 3RV19 26-0. (long shaft (with support) for circuit breaker/MSP, frame sizes S0, S2, S3)
NSB 01089b
min. 55
2)
1)
5
45
66
19 15
1 ... 4
17
33
max. 327
34,5
1) Abschließbar in Nullstellung mit Bügeldurchmesser max. 8 mm
2) Befestigung mit Überwurfmutter
NSB01107
3
22,5
24,3
4)
min. 45
max. 130
4) Lieferzustand mit Wellenlänge von 130 mm durch Kürzen der Welle anpassbar
1) Lockable in 0 position with shackle (max. 8 mm in diameter)
2) Affixed with screw caps
4) Supplied with a shaft length of 130 mm: adaptable by shortening of the shaft
NSB 01090b
16
5) min. 55
2)
1)
5
45
66
19 15
1 ... 4
17
33
max. 327
34,5
5) Erdungsklemme 35 mm2 und Haltewinkel für 330 mm Welle
1) Abschlibar in Nullstellung mit Bügeldurchmesser max. 8 mm
2) Befestigung mit Überwurfmutter
NSB01108
3)
min. 45
3
22,5
24,3
max. 330
3) Lieferzustand mit Wellenlänge von 330 mm durch Kürzen der Welle anpassbar
3) Supplied with a shaft length of 330 mm: adaptable by shortening of the shaft
1) Lockable in 0 position with shackle (max. 8 mm in diameter)
2) Affixed with screw caps
5) Ground terminal 35 mm2 and support bracket for 330 mm shaft
Circuit breaker/MSP 3RV1
SIRIUS System Manual
2-58 A5E40534713002A/RS-AA/001
Thru-the-door rotary operators for harsh conditions
Fig. 2-59: 3RV19 .6-2. (frame sizes S0, S2, S3)
min. 11 mm without shaft
NSB01091a
E F max. 341
min. 42 62 14
6
A
75
G
D
max. 330
min. 31
40
65
B
J
CH
6
Type Frame
Size
Measurements
Drilling pattern GroundDrilling pattern Door
A
125
170
194
B
111
144
180
C
50
60
60
D
77
87
100
E
112
162
187
F
50
50
48
G
27
27
25
H
9
10
10
J
42
47
53
S0
S2
S3
3RV1926-2
3RV1936-2
3RV1946-2
Circuit breaker/MSP 3RV1
SIRIUS System Manual
A5E40534713002A/RS-AA/001 2-59
Terminals for "Combination Motor Controller Type E" in acc. with UL 508
Motorized remote-control mechanism
Fig. 2-62: 3RV19 .6-3AP0 for circuit breaker/MSP
a) 3RV19 36-3AP0, frame size S2, 211 mm
b) 3RV19 46-3AP0, frame size S3, 236 mm
Fig. 2-60: 3RV19 28-1H (frame size S0) Fig. 2-61: 3RT19 46-4GA07 (frame size S3)
27
72
121
74
45
NSB 01228
10
NSB 01229
168
70
84
NSB00044
RESET I>
AUTOMATIC REVISION
MANUAL
I
SI EMENS
5
87
182
224
148
112
a)
Circuit breaker/MSP 3RV1
SIRIUS System Manual
2-60 A5E40534713002A/RS-AA/001
Busbar adapter shoes
Fig. 2-67: 8US11 11-4SM00 (for circuit breaker/MSP, frame size S3)
for 40- and 60-mm-systems
Fig. 2-63: 8US10 .1-5DJ07 (for circuit breaker/MSP,
frame sizes S00/S0)
Fig. 2-64: 8US10 61-5FK08 (for circuit breaker/MSP,
frame size S2)
Adapter width:
8US10 51-5DJ07: 45 mm
8US10 61-5DJ07: 55 mm
1) for 40-mm-busbar system
2) Side module 8US19 98-2KB00
1) for 40-mm-busbar system:
width: 12 to 15 mm
thickness: 5 and 10 mm
NSK-8186
55
139
68
1
2
13,5
142
40
40
NSK-8187
32
50
1)
Fig. 2-65: 8US12 51-5DM07 (for circuit breaker/MSP,
frame sizes S00/S0)
Fig. 2-66: 8US12 61-5FM08 (for circuit breaker/MSP,
frame size S2)
1) for 60-mm-busbar system 1) for 60-mm-busbar system
2) Side module 8US19 98-2BM00 2) Side module 8US19 98-2BM00
NSK-8188
55
13,5
182
68
1
2
185
NSK-8189
32
60
60
60
NSE00449
182
70
14
60
60
137
162
174
116
42
40 40
23 23
44
Circuit breaker/MSP 3RV1
SIRIUS System Manual
A5E40534713002A/RS-AA/001 2-61
3-phase busbar systems
Fig. 2-70: 3RV19 15-3..
Separation distance 63 mm:
3RV19 15-3AB for 2 circuit breakers/MSPs (length 101 mm)
3RV19 15-3CB for 4 circuit breakers/MSPs (length 227 mm)
Fig. 2-71: 3RV19 35-1. (for circuit breaker/MSP, frame size S2)
Separation distance 55 mm:
3RV19 35-1A for 2 circuit breakers/MSPs (length 111 mm)
3RV19 35-1B for 3 circuit breakers/MSPs (length 166 mm)
3RV19 35-1C for 4 circuit breakers/MSPs (length 221 mm)
Fig. 2-68: 3RV19 15-1... (frame size S00) Fig. 2-69: 3RV19 15-1... (frame size S0)
Separation distance 45 mm: Separation distance 55 mm:
3RV19 15-1AB for 2 circuit breakers/MSPs (length 83 mm) 3RV19 15-2AB for 2 circuit breakers/MSPs with accessories
(length 93 mm)
3RV19 15-1BB for 3 circuit breakers/MSPs (length 128 mm) 3RV19 15-2BB for 3 circuit breakers/MSPs with accessories
(length 148 mm)
3RV19 15-1CB for 4 circuit breakers/MSPs (length 173 mm) 3RV19 15-2CB for 4 circuit breakers/MSPs with accessories
(length 203 mm)
3RV19 15-1DB for 5 circuit breakers/MSPs (length 218 mm) 3RV19 15-2DB for 5 circuit breakers/MSPs with accessories
(length 258 mm)
21
13
64
108
83 128173
218
45
NSB 00055b
21
13
64
108
55
93
148
NSB 00056b
258
203
21
13
64
108
63 101
227
NSB 01092b
31
55
111
221
NSB00057b
165
15
96
166
Circuit breaker/MSP 3RV1
SIRIUS System Manual
2-62 A5E40534713002A/RS-AA/001
Fig. 2-72: 3RV19 35-3. (for circuit breaker/MSP, frame size S2)
Separation distance 75 mm:
3RV19 35-3A for 2 circuit breakers/MSPs with accessories (length 121 mm)
3RV19 35-3B for 3 circuit breakers/MSPs with accessories (length 196 mm)
3RV19 35-3C for 4 circuit breakers/MSPs with accessories (length 271 mm)
3-phase feeder lugs
Connector
31
75
271
121
NSB00058b
196
96
166
15
Fig. 2-73: 3RV19 15-5A Fig. 2-74: 3RV19 15-5B Fig. 2-75: 3RV19 25-5AB
Connection from above
(for frame size S00)
Connection from below
(frame sizes S00/S0)
Connection from above
(frame size S0)
Fig. 2-76: 3RV19 35-5A Fig. 2-77: 3RV19 15-5DB
Connection from above (for frame size S2) Frame size S0 (left) and frame size S00 (right)
NSB00060b
31
a
92
14 14
44
73
a) 19 mm for 3RV1.1
a) 23 mm for 3RV1.2
44
14 14
25
54
11471
NSB01093a
NSB00059a
24
44
25
34
NSB00061b
112
91
161
55
81
42,5
NSB 00062c
108
64
21
13
Circuit breaker/MSP 3RV1
SIRIUS System Manual
A5E40534713002A/RS-AA/001 2-63
2.7 Technical specifications
2.7.1 General specifications
Ty p e 3RV1. 1 3RV1. 2 3RV1. 3 3RV1. 4
Specifications
IEC 60 947-1, EN 60 947-1 (VDE 0660 Part 100) Yes
IEC 60 947-2, EN 60 947-2 (VDE 0660 Part 101) Yes
IEC 60 947-4-1, EN 60 947-4-1 (VDE 0660 Part 102) Yes
Frame size S00 S0 S2 S3
Pole number 3
Max. rated current Inmax (= max. rated operational current Ie)A12 25 50 100
Permissible ambient temperature
Storage/transportation °C -50 to +80
Operation °C -20 to +70 1)
Permissible rated current with the following internal cubicle temperature:
+60 °C %100
+70 °C %87
Circuit breaker in housing
Permissible rated current with the following ambient housing temperature:
+35 °C %100
+60 °C %87
Rated operational voltage UeV690
2)
Rated frequency Hz 50/60
Rated insulation voltage UiV690
Rated impulse strength Uimp kV 6
Utilization category
IEC 60 947-2 (circuit breaker) A
IEC 60 947-4-1 (motor starter) AC-3
CLASS In acc. with IEC 60 947-4-1 10 10 10/20 10/20
Direct current short-circuit breaking capacity (time constant τ = 5 ms)
(time constant t = 5 ms)
1 conducting path 150 V DC kA 10
2 conducting paths in series 300 V DC kA 10
3 conducting paths in series 450 V DC kA 10
Power loss (Pv) per circuit breaker In -> to 1.25 A W 5
Depends on rated current In In -> 1.6 A to 6.3 A W 6
(Upper setting range) In -> 8 A to 12 A W 7
In -> to 0.63 A W 5
Rper conducting path = P/I2×3 In -> 0.8 A to 6.3 A W 6
In -> 8 A to 16 A W 7
In -> 20 A to 25 A W 8
In -> to 25 A W 12
In -> 32 A W 15
In -> 40 A to 50 A W 20
In -> to 63 A W 20
In -> 75 A and 90 A W 30
In -> to 100 A W 38
Circuit breaker/MSP 3RV1
SIRIUS System Manual
2-64 A5E40534713002A/RS-AA/001
Ty p e 3RV1. 1 3RV1. 2 3RV1. 3 3RV1. 4
Shock resistance In acc. with IEC 68 Part 2-27 g/ms 25/11 (rectangular and sine pulse)
Degree of protection In acc. with IEC 60 529 IP20 IP20 3)
Shock protection In acc. with DIN VDE 0106 Part
100
protected against touching by fingers
Temperature compensation In acc. with IEC 60 947-4-1 °C -20 to +60
Phase loss sensitivity In acc. with IEC 60 947-4-1 Yes
Explosion protection In acc. with DIN VDE 0165 and EN 50 019 Yes for 3RV10 (Class 10), 3RV11(Class 10)
Isolating function In acc. with IEC 60 947-2 Yes
Main and emergency-stop switch features4) In acc. with IEC 60 204-1
(VDE 0113)
Ye s
Safe isolation between the main circuit and the
auxiliary circuit required for PELV applications
In acc. with DIN VDE 0106 Part 101
•to 400V + 10% Ye s
to 415 V+ 5 % (higher voltage on request) Yes
Mechanical life Operating
cycles
100,000 50,000
Electrical life 100,000 25,000
Max. switching frequency per hour (motor start-
ups)
1/h 15
1) Reduction in current above +60 °C 3) Connection room IP00
2) With molded-plastic housing 500 V 4) With corresponding accessories
Circuit breaker/MSP 3RV1
SIRIUS System Manual
A5E40534713002A/RS-AA/001 2-65
Conductor cross-sections - main circuit
1) After the box terminals have been removed, lug or busbar connections are also possible.
2) For notes on the Cage Clamp system, see page 1-19.
3) Use an insulation stop for a conductor cross-section 1 mm2.
4) Associated opening tool 8WA28 03/8WA28 04
Ty p e 3RV1. 3RV1. 2 3RV1. 3 3RV1. 4
Connection type Screw-type terminal Screw-type terminal with box termi-
nal
Terminal screw Pozidriv size 2 Pozidriv size 2 Allen screw 4 mm
Specified tightening torque Nm 0.8 to 1.2 Nm 2 to 2.5 3 to 4.5 4 to 6
Conductor cross-sections, 1 or 2 conductors
Single-core mm² 2 x (0.5 to 1.5) 2 x (1 to 2.5) 2 x (0.75 to 16) 2 x (2.5 to 16)
mm² 2 x (0.75 to 2.5)
(max. 4)
2 x (2.5 to 6) - -
Finely stranded with wire end ferrule: mm² 2 x (0.5 to 1.5) 2 x (1 to 2.5) 2 x (0.75 to 16) 2 x (2.5 to 35)
mm² 2 x (0.75 to 2.5) 2 x (2.5 to 6)
(max. 10)
1 x (0.75 to 25) 1 x (2.5 to 50)
Stranded mm² 2 x (0.5 to 1.5) 2 x (1 to 2.5) 2 x (0.75 to 25) 2 x (10 to 50)
mm² 2 x (0.75 to 2.5)
(max. 4)
2 x (2.5 to 6)
(max. 10)
1 x (0.75 to 35) 1 x (10 to 70)
AWG cables, single- or multi-core AWG 2 x (18 to 14) 2 x (14 to 10) 2 x (18 to 3) 2 x (10 to 1/0)
AWG - - 1 x (18 to 2) 1 x (10 to 2/0)
Ribbon cables (number x width x depth) mm - - 2 x (6 x 9 x 0.8) 2 x (6 x 9 x 0.8)
Removable box terminal 1)
With copper busbars mm - - - 18 x 10
With lug mm² - - - to 2 x 70
Cage Clamp connections2)3)4)
(1 or 2 conn. can be connected) Single-coil
Finely stranded with wire end ferrule
Finely stranded without wire end ferrule
AWG cables, single-core or stranded
mm²
mm²
mm²
AWG
2 x (0.25 to 2.5)
2 x (0.25 to 1.5)
2 x (0.25 to 2.5)
2 x (24 to 14)
-
-
-
-
Max. outer diameter of the conductor insulation: 3.6 mm
Permissible service position Any
In acc. with IEC 60 447 start
command "I" right or above
Auxiliary contacts
Front transverse auxiliary contacts with 1 changeover contact Switching capacity with different voltages
Rated operational voltage UeAC voltage V AC 24 230 400 690
Rated operational current Ie/AC-15 A 4 3 1.5 0.5
Rated operational current Ie/AC-12 Ith A10101010
Rated operational voltage UeDC voltage L/R 200 ms V DC 24 110 220
Rated operational current Ie/DC-13 A 1 0.22 0.1
Front transverse electronically optimized auxiliary contacts with 1 changeover contact
Rated operational voltage UeAC voltage V AC 3 to 60
Rated operational current Ie/AC-14 mA 1 to 300
Rated operational voltage UeDC voltage L/R 200 ms V DC 3 to 60
Rated operational current Ie/DC-13 mA 1 to 300
Front transverse auxiliary contacts with 1 NO + 1 NC, 2 NO contacts
Rated operational voltage UeAC voltage V AC 24 230
Rated operational current Ie/AC-15 A 2 0.5
Rated operational current Ie/AC-12 Ith A2.5 2.5
Rated operational voltage UeDC voltage L/R 200 ms V DC 24 48 60
Rated operational current Ie/DC-13 A 1 0.3 0.15
Side-mount auxiliary contacts with 1 NO + 1 NC, 2 NO, 2 NC, 2 NO + 2 NC and alarm switch
Rated operational voltage UeAC voltage V AC 24 230 400 690
Rated operational current Ie/AC-15 A6431
Rated operational current Ie/AC-12 Ith A10101010
Rated operational voltage UeDC voltage L/R 200 ms V DC 24 110 220 440
Rated operational current IeA 2 0.5 0.25 0.1
Circuit breaker/MSP 3RV1
SIRIUS System Manual
2-66 A5E40534713002A/RS-AA/001
2.7.2 Permissible rating of approved devices for North America, u s
In North America the 3RV1 is not approved as a “circuit breaker” and is commonly known as a Motor Starter Protector (MSP). The
SIRIUS 3RV1 series are approved for u/s and can also be used in acc. with UL 508 and C22.2 No.14 with a contactor as a Type F combi-
nation starter. You can use these MSPs as a "Manual Motor Starter" for "Group Fusing" or for "Group Installation" or as a "Combination Motor
Controller Ty p e E ".
3RV1 as a "Manual Motor Starter"
When the 3RV1 is used as a "Manual Motor Starter", it is always with a device for short-circuit protection (upstream short-circuit pro-
tection device). Any fusible link (“group fusing”) or UL 489 listed circuit breaker (“group installation”) can be used as a device for short-
circuit protection. The type and size are selected in acc. with the American NFPA 70 standard, Article 430-53 (c) for adequate protec-
tion of supply wiring.
Accreditation was issued under the following file numbers with the listed data:
u File No. E47705, Product Class NLRV
s Master Contract 165071, Product Class 3211 05
Motor Starter Protector Hp rating Rated current To 240 V AC To AC 480 Y/277 V To AC 600 Y/347 V
For FLA max. InIcu1)Icu1)Icu1)
Type V 1-phase 3-phase A kA kA kA
0.11 to 2 65 65 10
3RV10 11 2.5 65 65 10
3RV16 11-0BD10 115 ½- 3.2 65 65 10
200 3 4 65 65 10
Frame size S00 230 23 5 65 65 10
460 - 6.3 65 65 10
FLA max. 12 A, 600 V 575/600 -10 8 65 65 10
10 65 65 10
12 65 65 10
0.11 to 3.2 65 65 30
3RV10 21/3RV11 21 4656530
3RV13 21 5656530
115 2- 6.3 65 65 30
Frame size S0 200 3 8 65 65 30
230 5 10 65 65 30
FLA max. 25 A, 600 V 460 -15 12.5 65 65 30
575/600 -20 16 65 65 30
20 65 65 30
22 65 65 30
25 65 65 30
3RV10 31/3RV11 31 11 to 16 65 50 25
3RV13 31 20 65 65 25
115 3-25 65 65 25
Frame size S2 200 15 32 65 65 25
230 10 20 40 65 65 25
FLA max. 50 A, 600 V 460 -40 45 65 65 25
575/600 -50 50 65 50 25
11 to 16 65 65 30
3RV10 41/3RV10 42 20 65 65 30
3RV11 42 115 10 -25 65 65 30
3RV13 41/3RV13 42 200 20 30 32 65 65 30
230 20 40 40 65 65 30
Frame size S3 460 -75 50 65 65 30
575/600 -100 63 65 65 30
FLA max. 99 A, 600 V 75 65 65 30
90 65 65 30
100 (99) 65 65 30
Hp rating = output power in horse power (maximum motor power)
FLA = full load amps
1) Corresponds to "short circuit breaking capacity" in acc. with UL
Circuit breaker/MSP 3RV1
SIRIUS System Manual
A5E40534713002A/RS-AA/001 2-67
3RV10.A as "Combination Motor Controller Type E"
Since July 16th 2001, 1 inch air clearance and 2 inch creepage distance is required for a "Combination Motor Controller Type E" on the
input side with UL 508 The 3RV10 in frame sizes S0 and S3 are therefore approved with the terminal blocks listed below in acc. with
UL 508.
The 3RV10 in frame size S2 already complies with the required air clearance and creepage distance as a basic unit. These extended air
clearances and creepage distances are not required for CSA. The terminal blocks are therefore not required for use as a "Combination
Motor Controller Type E" in acc. with CSA. 3RV10’s are certified as "Combination Motor Controller Ty p e E " under the following file num-
bers with the listed data:
u File No. E156943, Product Class NKJH
s Master Contract 165071, Product Class 3211 08
Hp rating = output power in horse power (maximum motor power)
FLA = full load amps
1) Corresponds to "short circuit breaking capacity" in acc. with UL
2) Not required by CSA
Motor Starter Protector Hp rating Rated current To 240 V AC To AC 480 Y/277 V To AC 600 Y/347 V
For FLA max. InIcu1)Icu1)Icu1)
Type V 1-phase 3-phase A kA kA kA
0.11 to 1.6 50 50 30
3RV10 21 2505030
+ 3RV19 28-1H2) 115 2 2.5 50 50 30
200 3 3.2 50 50 30
Frame size S0 230 3 4 50 50 30
460 15 5 50 50 30
FLA max. 22 A, 480 V 575/600 10 6.3 50 50 30
12.5 A, 600 V 8505030
10 50 50 30
12.5 50 50 30
16 50 50
20 50 50
22 50 50
11 to 16 50 50 25
3RV10 31 20 50 50 25
115 3—25 50 50 25
Frame size S2 200 15 32 50 50 25
230 10 20 40 50 50 25
FLA max. 50 A, 600 V 460 40 45 50 50 25
575/600 50 50 50 50 25
3RV10 41 11 to 16 50 50 30
+ 3RV1946-4GA07 2) 20 50 50 30
115 10 —25 50 50 30
Frame size S3 200 20 30 32 50 50 30
230 20 40 40 50 50 30
FLA max. 100 A, 480V 460 75 50 50 50 30
75 A, 600 V 575/600 75 63 50 50 30
75 50 50 30
90 50 50
100 50 50
Rating of the control switches and alarm switches
Side-mount
auxiliary contact with
1 NO + 1 NC, 2 NO,
2NC, 2NO + 2NC
and alarm switch
Transverse
auxiliary contact with
1 changeover contact
Transverse
auxiliary contact with
1 NO + 1 NC, 2 NO
Max. rated voltage
In acc. with NEMA u V AC 600 600 240
In acc. with NEMA s V AC 600 600 240
Continuous current A 10 5 2.5
Switching capacity A600 B600 C300
Q300 R300 R300
Circuit breaker/MSP 3RV1
SIRIUS System Manual
2-68 A5E40534713002A/RS-AA/001
2.7.3 Short-circuit breaking capacity Icn in acc. with IEC 60 947-2
The table lists the rated limit short-circuit breaking capacity Icu and the rated service short-circuit breaking capacity Ics of 3RV1 circuit
breakers with different inception voltages and related to the rated current In of the circuit breakers.
The incoming supply of the circuit breakers is permissible at the upper or lower terminals irrespective of the rating.
If the short-circuit current at the installation location exceeds the rated short-circuit breaking capacity of the circuit breaker specified in
the table, a backup fuse is required. You can also use an upstream circuit breaker with a limiter function.
The maximum rated current of this backup fuse is specified in the tables. The rated short-circuit breaking capacity specified for the
fuse then applies.
Circuit breaker/contactor combinations for short-circuit currents of up to 50 kA can be used as fuseless load feeders in acc. with Part 5.
Circuit
breaker
Rated
current In
To 240 V AC 2)To 400 V AC
2)/415 V 3) To 440 V AC 2)/460 V3) To 500 V AC 2)/525 V3) To 690 V AC 2)
Icu Ics Max. Icu Ics Max. Icu Ics Max. Icu Ics Max. Icu Ics Max.
Fuse Fuse Fuse Fuse Fuse
(gL/gG) (gL/gG) (gL/gG) (gL/gG) (gL/gG)
Type A kAkAA kA kA A kAkA A kA kA A kAkAA
3RV10,
3RV16 11-
0BD10
frame size S00
0.16 to 0.8 100 100 100 100 100 100 100 100 100 100
1100 100 100 100 100 100 100 100 100 100
1. 2 5 100 100 100 100 100 100 100 100 •2220
1. 6 100 100 100 100 100 100 100 100 •2220
2100 100 100 100 100 100 •1010352235
2.5 100 100 100 100 100 100 •1010352235
3.2 100 100 100 100 50 10 40 1)3 340 2240
4100 100 100 100 50 10 40 1)3340 2240
5100 100 100 100 50 10 50 1)3350 2250
6.3 100 100 100 100 50 10 50 1)3 350 2250
8100 100 50 12.5 80 1)50 10 63 1)3363 2263
10 100 100 50 12.5 80 1)1010 63 3 363 2 263
12 100 100 50 12.5 80 1)1010 80 3 380 2 280
3RV1. 2
Frame size S0
0.16 to 1.25 100 100 100 100 100 100 100 100 100 100
1. 6 100 100 100 100 100 100 100 100 100 100
2100 100 100 100 100 100 100 100 •8825
2.5 100 100 100 100 100 100 100 100 •8825
3.2 100 100 100 100 100 100 100 100 •8832
4100 100 100 100 100 100 100 100 •6332
5100 100 100 100 100 100 100 100 •6332
6.3 100 100 100 100 100 100 100 100 •6350
8100 100 100 100 50 25 63 1)422163 6 350
10 100 100 100 100 50 25 80 1)422163 6 350
12.5 100 100 100 100 50 25 80 1)422180 6 363
16 100 100 50 25 100 1)50 10 80 1)10 5 80 4 263
20 100 100 50 25 125 1)50 10 80 1)10 5 80 4 263
22 100 100 50 25 125 1)50 10 100 1)10 5 80 4 263
25 100 100 50 25 125 1)50 10 100 1)10 5 80 4 263
3RV1. 3
Frame size S2
16 100 100 50 25 100 1)50 25 100 1)12 6 63 5 363
20 100 100 50 25 125 1)50 25 100 1)12 6 80 5 363
25 100 100 50 25 125 1)50 15 100 1)12 6 80 5 363
32 100 100 50 25 125 1)50 15 125 1)10 5100 4 263
40 100 100 50 25 160 1)50 15 125 1)10 5100 4 263
45 100 100 50 25 160 1)50 15 125 1)10 5100 4 263
50 100 100 50 25 160 1)50 15 125 1)10 5100 4 280
Circuit breaker/MSP 3RV1
SIRIUS System Manual
A5E40534713002A/RS-AA/001 2-69
No backup fuse required because it is short circuit-proof up to 100 kA.
Short circuit-proof up to min. 50 kA.
1 A backup fuse is only required if the short-circuit current at the installation location is > Icu.
2 10 % overvoltage
3 5 % overvoltage
Circuit
breaker
Rated
current In
To 240 V AC 2)To 400 V AC
2)/415 V 3) To 440 V AC 2)/460 V 3) To 500 V AC 2)/525 V 3) To 690 V AC 2)
Icu Ics Max. Icu Ics Max. Icu Ics Max. Icu Ics Max. Icu Ics Max.
Fuse Fuse Fuse Fuse Fuse
(gL/gG) (gL/gG) (gL/gG) (gL/gG) (gL/gG)
Type A kA kA A kA kA A kA kA A kA kA A kA kA A
3RV1. 41
Frame size S3
40 100 100 50 25 125 1)50 20 125 1)12 6100 6 363
50 100 100 50 25 125 1)50 20 125 1)12 6100 6 380
63 100 100 50 25 160 1)50 20 160 1)12 6100 6 380
75 100 100 50 25 160 1)50 20 160 1)8 4125 5 3100
90 100 100 50 25 160 1)50 20 160 1)8 4125 5 3125
100 100 100 50 25 160 1)50 20 160 1)8 4125 5 3125
3RV1.42
Frame size S3
With increased
switching
capacity
16 100 100 100 50 100 50 •30158012763
20 100 100 100 50 100 50 •30158012763
25 100 100 100 50 100 50 •30158012763
32 100 100 100 50 100 50 •221110012763
40 100 100 100 50 100 50 •18916012680
50 100 100 100 50 100 50 •157.5160105100
63 100 100 100 50 70 50 200 1)15 7.5160 7.54100
75 100 100 100 50 70 50 200 1)10 5160 6 3125
90 100 100 100 50 70 50 200 1)10 5160 6 3160
100 100 100 100 50 70 50 200 1)10 5160 6 3160
Circuit breaker/MSP 3RV1
SIRIUS System Manual
2-70 A5E40534713002A/RS-AA/001
2.7.4 Limiter function with standard devices for 500 V AC and 690 V AC in acc. with IEC 60 947-2
The table lists the rated limit short-circuit breaking capacity Icu and the rated service short-circuit breaking capacity Ics with an
upstream standard circuit breaker that fulfills the limiter function at 500 V AC and 690 V AC.
The short-circuit breaking capacity can be significantly increased using the upstream standard circuit breaker with a limiter function.
The circuit-breaker connected downstream, should be set to the rated current of the load. Be sure when you set up circuit breaker
combinations to note to the distances between the grounded parts and the distances between the circuit breakers.
Make sure that the cabling between the circuit breakers is short circuit-proof. You can mount the circuit breakers side by side.
No backup fuse required because it is short circuit-proof up to 100 kA.
Short circuit proof up to 100 kA.
1) 10 % overvoltage
2) 5 % overvoltage
2.7.5 Characteristics
You can obtain the characteristics for all the setting ranges from our Technical Assistance team by
e-mail: technical-assistance@siemens.com or over the Internet under:
www.siemens.com/sirius/technical-assistance
Standard circuit breaker
with limiter function
Standard circuit breaker To 500 V AC 1)/ 525 V 2)To 690 V AC 1)
Type Rated current InIcu Ics Icu Ics
Rated current InType A kAkAkAkA
3RV13 21-4DC10 3RV10 2 to 1 ••••
Frame size S0 Frame size S0 1.25 ••••
In = 25 A 1.6 ••••
2•5025
2.5 •5025
3.2 •5025
4•5025
5•5025
6.3 •5025
8100 50 20 10
10 100 50 20 10
12.5 100 50 20 10
16 100 50 20 10
20 100 50 20 10
22 100 50 20 10
25 100 50 20 10
3RV13 31-4HC10 3RV10 3 16 100 50 50 25
Frame size S2 Frame size S2 20 100 50 50 25
In = 50 A 25 100 50 50 25
32 100 50 50 25
40 100 50 50 25
50 100 50 50 25
3RV13 41-4HC10 3RV10 4 32 100 50 50 25
Frame size S3 Frame size S3 40 100 50 50 25
In = 50 A 50 100 50 50 25
3RV13 41-4MC10 3RV10 4 50 100 50 50 25
Frame size S3 Frame size S3 63 100 50 50 25
In = 100 A 75 100 50 50 25
90 100 50 50 25
100 100 50 50 25
Circuit breaker/MSP 3RV1
SIRIUS System Manual
A5E40534713002A/RS-AA/001 2-71
2.7.6 Installation guidelines
Rules for installing circuit breakers/MSPs
When mounting circuit breakers/MSPs, the following clearance must be maintained to grounded or
live parts.
Rules for installing circuit breakers/MSPs with limiter function
Circuit breaker/MSP Clearance to grounded or live parts
YX side Z
Type Frame size mm mm mm
3RV1. 1 S00 to 690 V 20 70 9
3RV1. 2 S0 to 500 V
to 690 V
30
50
90
90
9
30
3RV1. 3 S2 to 690 V 50 140 10
3RV1. 4 S3 to 240 V
to 440 V
to 500 V
to 690 V
50
70
110
150
167
167
167
167
10
10
10
30
Standard installation for frame sizes S0, S2 and S3 Installation of frame size S0 for the setting ranges 5.5 - 8 to 20 - 25 A at
690 V
Clearance to grounded or live parts for limiter function in mm Ue [V] S0S2S3
500 Z (side) 10 10 10
Y4050110
X90140167
690 Z (side) 30 10 30
Y5050150
X90140167
3RV1...
3RV1...
1L1 3L2 5L3 1L1 3L2 5L3
2T1 4T2 6T32T1 4T2 6T3
NSB 01304a
3RV1...
Z
Y
Z
Y
X
NSB01069
3RV1...
3RV1...
1L1 3L2 5L3 1L1 3L2 5L3
2T1 4T2 6T32T1 4T2 6T3
Load sideInfeed side
Wiring module
Frame size S0: 3RV1915-1A
Frame size S2: 3RV1935-1A
Frame size S3: 3RV1943-3D
(NOTICE! Due to the
wiring module always 10 mm
gap between the
circuit-breakers)
NSB01070
3RV1...
3RV1...
1L1 3L2 5L3 1L1 3L2 5L3
2T1 4T2 6T32T1 4T2 6T3
Load side
Infeed side
3RV1...
3RV1...
1L1 3L2 5L3 1L1 3L2 5L3
2T1 4T2 6T32T1 4T2 6T3
NSB01071
3RV1...
Z
Y
Z
Y
X
Circuit breaker/MSP 3RV1
SIRIUS System Manual
2-72 A5E40534713002A/RS-AA/001
2.8 Application notes for the use of 3RV1 downstream from frequency
converters/inverter with pulsing voltage
The use of thermal motor protection devices downstream from frequency
converters/inverters with pulsing voltage results in influences on the switch-
ing devices that could lead to the nuisance tripping of those devices. In the
following examples, practical guidelines are provided for such applications.
2.8.1 Influences of high frequency currents upon the thermal overload release
The thermal overload release on the circuit breakers/MSPs and overload
relays generally consists of a bimetal strip and a heating winding, that heat
up when motor current runs through them. The excessive bending of the
bimetal strip (such as with high motor current) results in the breaking of the
motor circuit.
This style of thermal overload release is set for 50 Hz AC current. So that the
trip point is also only for currents which have the same thermal effect (r.m.s.
value) or are similar to the set current in the required range of the standard.
This would be the case for AC current from 0 to 400 Hz and for DC current.
With high frequency currents, as occurs downstream of converters, the
bimetal strip becomes increasingly hot. This can be attributed to eddy
current loses induced by harmonics and to the Skin effect in the heater
windings. Both lead to the tripping of the overload release even with lower
currents (nuisance tripping!).
The influences are dependent on the frequency of the current. The higher
the frequency of the converter and the lower the adjustable range/rated
current, the higher the reduction of the trip current.
In order for the trip limits to once again fall into the standard range, the over-
load release setting needs to be corrected. The following table shows the
correction factors for the various setting ranges depending on the pulse
frequency of the converters.
Setting range /
Rated current
Pulse frequency [kHz]
0246810121416
3.2 - 50 A 1.00 1.07 1.12 1.16 1.18 1.19 1.21 1.22 1.23
0 .5 - 2 . 5 A 1. 0 0 1. 0 8 1. 13 1. 17 1. 2 1 1. 2 4 1. 2 6 1. 2 8 1.2 9
0 .3 2 - 0 . 4 A 1. 0 0 1. 0 9 1. 15 1. 2 1 1.2 5 1.2 9 1. 3 3 1.3 5 1. 3 7
0.16 - 0.25 A 1.00 1.10 1.17 1.24 1.28 1.33 1.38 1.42 1.46
Table 2-20: Correction factors for the various setting ranges
Circuit breaker/MSP 3RV1
SIRIUS System Manual
A5E40534713002A/RS-AA/001 2-73
Example Circuit breaker/MSP with the setting range of 1.1 - 1.6 A behind a frequency
converter with a pulse frequency of 8 kHz and a r.m.s. value of the motor
current at rated load: 1.2 A.
Set to: 1.2 A x 1.21 = 1.45 A
This compensates for the influences of the high frequency current. The trip
current lays within the standard range.
Attention
Harmonics can cause the r.m.s. value of the motor current to be higher than
the rated motor current. In this case nuisance tripping can still occur despite
the use of the correction factors.
In order to remedy this, the r.m.s. value of the motor current at rated load
needs to be ascertained and used as the basis current for the above
described correction procedure. Only measuring instruments suitable to
ascertain the values are those that can measure the true r.m.s. value up to
the frequencies that appear and can also reproduce them. Devices well suit-
able for this would be hot-wire instruments for example. Moving-iron mea-
suring elements are in fact r.m.s. measuring instruments, but can only be
used for frequencies up to 1 kHz and therefore can’t be used in most of the
above described cases. Common instruments such as a multimeter or a clip-
on ammeter are not suitable for measuring in the above described cases.
2.8.2 Other possible influences
a) Capacitive leakage currents
Despite adjusting the setting, nuisance tripping can still occur in individual
installations. Extensive investigations have shown that installations with
pulsing voltage can also lead to other effects that lower the trip current of
the overload release, such as an increase of current flowing through the trip
element.
A practical example:
Consider an installation that is fed from an inverter with 3 kHz pulse fre-
quency and has motors connected with a 80 m long cable. An analysis of the
actual flowing current shows a ripple amplitude of the motor current with
very high frequency currents (up to 150 kHz) and a peak value of 1.5 A. The
influence on the thermal overload release is still significantly higher than
described in example 1 at these frequencies. Moreover, capacitive leakage
currents appear in this installation due to the length of the cable and the
high frequency. These increase the current that flows through the trip ele-
ment and can lead to nuisance tripping.
In cases where high frequency currents of well over 16 kHz appear and the
procedure described in example 1 no longer leads to success, then you can
proceed as follows. In an overload free operation of the motor the overload
release needs to be set so high that the unit will not trip. After that the
motor needs to run for about 1.5 h at full load. Then the overload release
needs to be reduced to the trip limit and then set about 10 % higher than
Circuit breaker/MSP 3RV1
SIRIUS System Manual
2-74 A5E40534713002A/RS-AA/001
the trip limit. That will compensate for the influences of the installation. You
can then can use the achieved value as a correction factor for similar installa-
tions.
b) Rotational speed control of motors with a response characteristic
controlled Frequency converter
With the adjustment of the linear voltage-frequency-characteristic and a con-
tinual increase in current (see for example operating instructions Micromas-
ter parameter P077 and P078), decreased rotational speed (< 50 Hz) and
constant load torque can lead to the increase of the motor current. With this
adjustment the frequency converters output voltage is not reduced to the
same scale as the output frequency. If this results in nuisance tripping and
can’t be compensated for by a higher setting of the trip release (watch for
motor overload), then minimizing of the current increase or a readjustment
to a quadratic voltage-frequency-characteristic could provide a remedy.
SIRIUS System Manual
A5E40534713002A/RS-AA/001 3-1
3
3RT1 Contactors/
3RH1 Control relays
Section Subject Page
3.1 Specifications/regulations/approvals 3-3
3.1.1 Utilization categories 3-3
3.1.2 Positively driven operation 3-7
3.1.3 Safe isolation 3-7
3.1.4 Explanation of terms 3-9
3.2 Device description 3-10
3.2.1 Coil systems S00 to S3 3-12
3.2.2 Short-circuit protection for SIRIUS contactors 3-13
3.2.3 Operation 3-14
3.2.3.1 General information 3-14
3.2.3.2 Contact reliability 3-15
3.2.3.3 Electrical service life 3-16
3.2.3.4 Ambient temperature 3-20
3.3 Application and areas of use 3-23
3.3.1 3RT10 contactors with 3 main contacts for switching motors 3-23
3.3.2 3RT14 contactors with 3 main contacts for switching
resistive loads (AC-1)
3-24
3.3.3 3RT13 and 3RT15 contactors with 4 main contacts 3-25
3.3.4 3RT16 capacitor contactors 3-26
3.3.5 Contactors with an extended operating range 3-28
3.3.5.1 Contactors with series resister (3RH11...-0LA0/3RT10...-
0LA0)
3-28
3.3.5.2 Contactors with electronic control module frame sizes S0 to
S3 (3RT10..-.X40-0LA2)
3-30
3.3.5.3 Contactors with an extended operating range
(3RH1122-2K.40, 3RT1017-2K.4., 3RT102.-3K.40)
3-31
3.3.6 3RH1 control relays 3-32
3.3.7 3RT10 contactor relays for switching motors (interface) and
3RH11 control relays for switching auxiliary circuits
3-33
3RT1 Contactors/ 3RH1 Control relays
SIRIUS System Manual
3-2 A5E40534713002A/RS-AA/001
3.3.8 3RA13 Contactor combinations for reversing 3-35
3.3.9 3RA14 Wye-delta combinations 3-46
3.4 Accessories 3-54
3.4.1 Attachable auxiliary switches for extending the auxiliary
contacts
3-57
3.4.1.1 Terminal markings of the contactors frame sizes S00 to S3 3-62
3.4.1.2 Terminal markings of the contactors and control relays
combined with auxiliary switch blocks
3-64
3.4.1.3 Auxiliary switches that can be attached to 3RH1 control
relays
3-66
3.4.2 Time-delay auxiliary switches 3-69
3.4.2.1 Frame size S00 (3RT1916-2E, -2F, -2G) 3-69
3.4.2.2 Frame sizes S0 to S3 (3RT1926-2E, -2F, -2G) 3-71
3.4.3 Solid-state time relay blocks with semiconductor output 3-72
3.4.3.1 Frame size S00 (3RT1916-2C, -2D) 3-73
3.4.3.2 Frame sizes S0 to S3 (3RT19 26-2C, -2D) 3-74
3.4.4 Additional load module (3RT1916-1GA00) 3-75
3.4.5 Coupling element for frame sizes S0 to S3
(3RH1924-1GP11)
3-76
3.4.6 Surge suppression 3-78
3.4.7 Other accessories 3-83
3.4.7.1 LED module for indicating contactor control
(3RT1926-1QT00)
3-83
3.4.7.2 Auxiliary connecting lead terminal, 3-pole for frame size S3
(3RT19 46-4F)
3-83
3.4.7.3 EMC interference suppression module (3RT19 16-1P..) 3-84
3.4.7.4 Soldering pin adapter for frame size S00 (3RT19 16-4KA.) 3-85
3.4.7.5 Paralleling links (3RT19 .6-4B.31) 3-87
3.4.7.6 Sealing cover (3RT19 .6-4MA10) 3-88
3.4.7.7 Terminal covers for frame sizes S2 to S3 3-89
3.5 Mounting and connection 3-91
3.5.1 Mounting 3-91
3.5.2 Connection 3-94
3.5.3 Changing the magnetic coils 3-98
3.5.4 Changing the contact pieces 3-103
3.6 Dimensional drawings (dimensions in mm) 3-106
3.7 Technical data 3-122
Section Subject Page
3RT1 Contactors/ 3RH1 Control relays
SIRIUS System Manual
A5E40534713002A/RS-AA/001 3-3
3.1 Specifications/regulations/approvals
Regulations The following regulations apply to 3RT contactors:
IEC 60 947-1, EN 60 947-1 (VDE 0660 Part 100), which includes the
general specifications for low-voltage switching devices.
IEC 60 947-4-1, EN 60 947-4-1 (VDE 0660 Part 102), which contains, in
particular, the requirements for contactors and motor starters.
The following regulations apply to 3RH contactor relays:
IEC 60 947-1, EN 60 947-1 (VDE 0660 Part 100), which includes the gen-
eral specifications for low-voltage switching devices.
IEC 60 947-5-1, EN 60 947-5-1 (VDE 0660 Part 200) which includes, in par-
ticular, the requirements for control equipment and switching elements
for the control, signaling, locking, etc. of switchgear and controlgear.
Standards The following standards apply to the terminal markings of the contactors:
EN 50 012: terminal markings and identification numbers for auxiliary con-
tact elements of particular contactors (also applies to contactors with a
built-in auxiliary switch block)
EN 50 011: terminal markings, identification numbers, and identification
letters for particular auxiliary contactors (also applies to auxiliary contac-
tors with a built-in auxiliary switch block)
EN 50 005: terminal markings and identification numbers, general rules
Approvals/
test reports
Confirmation of approvals and test certificates and characteristics can be
obtained on the Internet/intranet:
https://support.industry.siemens.com/cs/ww/en/ps/16027/cert
Shock protection The shock protection provided is in acc. with DIN VDE 0106, Part 100.
3.1.1 Utilization categories
In acc. with EN 60 947-4-1, the purpose of the contactors and the stress
placed on them is indicated by the utilization category together with details
of the rated operational current or motor output and the rated voltage.
The following tables list the definitions of the utilization categories for low-
voltage switching devices and contactors from IEC 60 947 (VDE 0660).
The rated operational voltages for the various utilization categories are listed
in the low-voltage switching devices catalog.
3RT1 Contactors/ 3RH1 Control relays
SIRIUS System Manual
3-4 A5E40534713002A/RS-AA/001
Utilization category
for AC voltages
Definition of AC-1 to
AC-6b
The definitions of the utilization categories AC-1 to AC-6b for main circuits
can be found in the relevant regulations.
The main areas of application for contactors are:
AC-3 operation: switching of squirrel-cage motors
AC-1 operation: switching of resistive loads
AC-4 operation: plugging, reversing, inching
AC-6b operation: switching of capacitor banks
Test conditions Test conditions for the various utilization categories:
In AC-1 operation, the contactor must be able to switch 1.5 times the
rated operational current on and off.
In AC-3 operation, the starting currents of the motors must be controlled.
In other words, the contactor must be able to switch on 10 times the
rated operational current (Ie), and switch off 8 times the Ie.
In AC-4 operation, the contactor must be able to switch off or on 12 times
the rated operational current (Ie) and 10 times the Ie. This represents
extremely high stress for contactors because the high starting currents of
the motors have to be switched off.
In AC-6b operation, the rated values of capacitor loads may be derived
from capacitor switching tests or on the basis of existing experience and
research.
The breaking current is decisive in calculating the electrical service life:
In AC-1 and AC-3 operation, 1 x Ie must be assumed.
In AC-4 operation, 6 x Ie must be assumed because the contactor also has
to switch off the motor during startup.
AC Utilization category for
AC voltages
Switching capacity I/IeElectrical service life I/Ie
On Off On Off
AC-1 Non-inductive load or
a slightly inductive load
1. 5 1. 5 1 1
AC-2 Slip ring motors: switch on,
switch off
44 2.52.5
AC-3 Squirrel-cage motors:
switch on, switch off during
the run
10 8 6 1
AC-4 Squirrel-cage motors:
switch on, plugging or
reversing, inching
12 10 6 6
AC-6b Switching of capacitor
banks ——
Table 3-1: Utilization categories, test conditions for AC voltage
3RT1 Contactors/ 3RH1 Control relays
SIRIUS System Manual
A5E40534713002A/RS-AA/001 3-5
Utilization category
for DC voltages
Definition of
DC-1 to DC-5
The definitions of the utilization categories DC-1 to DC-6 apply to main
circuits for switching DC voltage.
The main areas of application for contactors are:
DC-3/DC-5 operation: switching of shunt or series motors
DC-1 operation: switching of resistive loads, resistance furnaces
Note
In the information on DC switching capacity in previous documents, the
utilization categories DC-2 and DC-4 correspond to the current utilization
categories DC-3 and DC-5.
Utilization category
for AC voltage
(auxiliary contact
elements)
Definition of
AC-12 to AC-15
IEC 60 947-5-1/EN 60 947-5-1 (VDE 0660 Part 200) contains the definitions
of the utilization categories AC-12 to AC-15 for switching elements for the
control, signaling, locking, etc. of switchgear and controlgear.
The main areas of application for auxiliary contactors are:
AC-14/AC-15 operation: switching of contactor coils, solenoid valves,
for example.
AC-14/AC-12 operation: switching of resistive loads, for example.
DC Utilization category for
DC voltages
Switching capacity I/Ie
Make/break Time constant L/R (ms)
DC-1 Non-inductive load or
a slightly inductive load,
resistance furnaces
1. 5 1
DC-3 Shunt motors:
switching on, plugging,
reversing, inching
42.5
DC-5 Series motors:
switching on, plugging,
reversing, inching
415
Table 3-2: Utilization categories, test conditions for DC voltages
Switching capacity
AC Utilization category for
AC voltage (auxiliary
contact elements)
Make Break
I/IeI/Iecosϕ
AC-12 Control of resistive load and semi-
conductor load in the input circuits
of optocouplers
110.9
AC-14 Control of a small electromagnetic
load (max. 72 VA)
610.3
AC-15 Control of an electromagnetic load
(greater than 72 VA)
10 1 0.3
Table 3-3: Utilization categories, test conditions for AC voltage (auxiliary contact elements)
3RT1 Contactors/ 3RH1 Control relays
SIRIUS System Manual
3-6 A5E40534713002A/RS-AA/001
Rated operational
currents
The rated operational currents for the various utilization categories are listed
in the low-voltage switching devices catalog. The test specifications given in
the table for each utilization category represent the scale for the making and
breaking capacity of the auxiliary contacts.
Example 3RT1016 contactor:
Ie/AC-15 of the auxiliary contact: 6 A/230 V
Making capacity: 10 x Ie/AC-15 = 60 A
This enables the contactor coil with the current consumption of 60 A to
be switched on.
Only the holding current is decisive for switching off the contactor coil.
According to regulations, the auxiliary contact must normally be able to
switch off the rated operational current.
Utilization category for
DC voltage (auxiliary
contact elements)
Definition of
DC-12 and DC-13
The DC voltage switching capacity of auxiliary contacts is defined in utiliza-
tion categories DC-12 and DC-13.
The main areas of application for contactors are:
DC-12: switching of resistive loads (typical application)
DC-13: switching of inductive loads, such as contactor coils and solenoid
valves
In DC operation, the difference in stress is also determined by the L/R time
constant. This must be specified by the user.
Switching capacity
DC Utilization category for DC voltage
(auxiliary contact elements)
Make Break
I/IeI/IeL/R (ms)
DC-12 Control of resistive load and semi-
conductor load in the input circuits
of optocouplers
111
DC-13 Control of solenoids 1 1 300
Table 3-4: Utilization categories, test conditions for DC voltage (auxiliary contact elements)
3RT1 Contactors/ 3RH1 Control relays
SIRIUS System Manual
A5E40534713002A/RS-AA/001 3-7
3.1.2 Positively driven operation
Regulations The regulations for positively driven operation are:
SIRIUS contactors comply with these regulations.
Definition: positively
driven contacts
Positively driven contacts are contacts that are mechanically connected with
one another in such a way that the NC contacts and NO contacts can never
be closed at the same time. This means ensuring that there is a distance
between the contacts of at least 0.5 mm throughout the entire service life
of the contactor, even when there is a defect, such as when the contact has
been wrongly welded (ZH 1/457).
Positively driven
operation in the case
of 3RT1/3RH11
Positively driven operation occurs in:
3RT101. contactors and 3 RH11 auxiliary contactors in frame size S00 in
both the basic unit and in the auxiliary switch block and also between the
basic unit and the built-on auxiliary switch block
3RT1 contactors in frame sizes S0 to S3 between the main contacts and
the normally closed auxiliary contacts. In other words, if the main contact
is welded, the normally closed auxiliary contact will not close.
Positively driven operation does not occur in the case of:
Electronically optimized auxiliary switch blocks in frame size S00
Positively driven operation is not compulsory for normal controllers. It is,
however, imperative for protective circuits.
3.1.3 Safe isolation
The term "safe isolation" occurs in connection with safety/protective extra-
low voltage (SELV/PELV) and functional extra-low voltage (FELV). Safe isola-
tion reliably prevents voltage that is capable of causing electric shock from
transferring to the safely isolated voltage (e.g. to safety extra-low voltage
that is applied to or switched to the same device).
Safe isolation is also becoming increasingly important due to the more wide-
spread use of electronic systems in high-voltage installations.
Definition Circuits are safely isolated when a single fault does not result in a transfer of
voltage from one circuit to another. Faults to be taken into account are, for
example, a bent or loose conductive part, a bent soldering pin, broken wind-
ing wire, a screw that has fallen out, or a broken partition wall in a device.
For contactors IEC 60 947-4-1, Appendix H (draft 17B/996/DC)
For control
relays
IEC 60 947-5-1, Amendment 2, Annex L,
edition 10.1999
ZH 1/457 Safety rules for controllers on power-operated
presses
•SUVA Accident prevention guidelines of the Schweizer
Unfallversicherungsanstalt (Swiss institute for acci-
dent insurance)
3RT1 Contactors/ 3RH1 Control relays
SIRIUS System Manual
3-8 A5E40534713002A/RS-AA/001
Regulations IEC 61 140 (replacing VDE 0106 Part 101/IEC 536) lists basic requirements
that can be met using safe isolation between circuits in electrical equip-
ment.
Basic requirements are, for example:
Double or reinforced insulation
Protective screening
Combination of double or reinforced insulation and protective screening
The insulation must be resistant to aging throughout the expected service
life.
Circuits without protective extra-low voltage or functional extra-low voltage
do not require safe isolation.
Safe isolation in the
case of 3RT1 and 3RH1
contactors
If the conducting paths of a contactor are operated with different voltages,
the requirements for safe isolation must be met.
In the case of the 3RT1 and 3RH1 contactors, safe isolation is ensured up to
the following voltage:
The values for the safe isolation between the main power circuit and the
auxiliary circuit/coil connection are found in the following tables:
I Main power circuit - Control circuit
II Main power circuit - Auxiliary circuit
III Control circuit - Auxiliary circuit
S00
Contactor/
Control relay
S0 S2 S3
3-pole devices 690 V* 400 V 400 V 690 V
4-pole devices 400 V 400 V 400 V 690 V
*with unused auxiliary circuit ——
S00 S0 S2 S3
Integ. auxiliary circuit 400 V ——
Front mount auxiliary
circuit
690 V* 500 V 500 V 500 V
Side mount auxiliary
circuit
No 690 V 500 V 690 V
*4-pole auxiliary contact block
S00 S0 S2 S3
Integ. auxiliary circuit 400 V ——
Front mount auxiliary
circuit
690 V* 690 V 690 V 690 V
Side mount auxiliary
circuit
No 500 V 690 V 690 V
*4-pole auxiliary contact block
3RT1 Contactors/ 3RH1 Control relays
SIRIUS System Manual
A5E40534713002A/RS-AA/001 3-9
IV Auxiliary circuit - Auxiliary circuit (contactor relay)
V Main power circuit - Main power circuit
All the data are power system specifications with 10 % overvoltage in volts [V].
400 V + 10 % corresponds to 415 V + 5 % and 500 V + 10 % corresponds
to 525 V + 5 %.
Attention
In the table, the voltage that can cause electric shock and that must be
safely isolated is critical. If the voltages 400 V and 24 V are to be safely iso-
lated from one another, contactors with safe isolation up to 400 V must be
used between the two points of connection used.
3.1.4 Explanation of terms
Safety extra-low
voltage
Safety extra-low voltage (SELV) allows circuits with a rated voltage of up to
50 V AC or 120 V DC to be operated ungrounded. The higher voltage is
safely isolated from the SELV circuits.
Safety extra-low voltage helps protect people.
Functional extra-low
voltage
Functional extra-low voltage (FELV) allows circuits with a rated voltage of up
to 50 V AC or 120 V DC to be operated. It does not, however, meet the
requirements of safety extra-low voltage and is therefore subject to addi-
tional conditions. FELV is implemented using a ground terminal.
Functional extra-low voltage helps protect devices (e.g. programmable con-
trollers).
PELV PELV (protective extra-low voltage) has the same requirements as safety
extra-low voltage, except for the fact that the circuit and/or exposed conduc-
tive part is/are grounded (so it is basically grounded SELV).
S00
Basic unit - contact
block
690 V* *4-auxiliary contact block
Basic unit 400 V
Contact block 400 V
S00 S0 S2 S3
400V 400V 400V 400V
3RT1 Contactors/ 3RH1 Control relays
SIRIUS System Manual
3-10 A5E40534713002A/RS-AA/001
3.2 Device description
The SIRIUS contactors are components of the SIRIUS modular system and
can therefore offer the typical benefits of SIRIUS when it comes to the
selection of components and the assembly and operation of controllers and
load feeders.
The SIRIUS range of contactors encompasses the following:
Contactors for switching motors of up to 45 kW/400 V (75 HP/460 V)
Auxiliary contactors with the contact variants 4 NO, 3 NO +1 NC, and
2NO + 2NC
Contactor relays for system-specific cooperation with electronic
controllers
Contactors for particular applications:
- Contactors with 4 main contacts
- Capacitor switching contactors
- Contactors for switching resistive loads up to 140 A
- Contactors with an extended operating range
- Contactor combinations
Frame sizes The SIRIUS range of contactors covers everything up to 45 kW (75 HP) in
4 sizes. Each frame size covers multiple standard motor ratings:
Fig. 3-1: Frame sizes of the 3RT10 contactors
Performance ranges The following table specifies the performance ranges for the frame sizes of
the 3RT10 and 3RT12 contactors:
S00 S0 S2 S3
Frame size S00 S0 S2 S3
Order-Number 3RT10.. 3RT10.. 3RT10.. 3RT10..
15 16 17 23 24 25 26 34 35 36 44 45 46
P/AC-3/400 kW 3 4 5,5 4 5,5 7,5 11 15 18,5 22 30 37 45
up to 400 V: up to 500 V:
Ie/AC-3 A 7 9 12 9 121725324050658095
Width mm 45 45 55 70
Table 3-5: Performance ranges of the 3RT10/3RT12 contactors
3RT1 Contactors/ 3RH1 Control relays
SIRIUS System Manual
A5E40534713002A/RS-AA/001 3-11
The following table provides an overview of the existing variants of the 3RT contactors and 3RH con-
trol relays:
1) Pre-wired and tested
Design Frame size
3RT10 contactors AC/DC operation
To operate motors, 3-pole, up to 45 kW/400 V (75 HP/460 V)
Ie/AC-1 up to 40 °C: up to 120 A up to 690 V
S00 to S3
3RT14 contactors AC/DC operation
To switch resistive loads, 3-pole
Ie/AC-1 up to 40 °C: up to 140 A to 690 V
S3
3RT13 contactors AC/DC operation, 4 main contacts (NO contacts)
To switch resistive loads, up to 92 kW/400 V
Ie/AC-1 up to 40 °C: up to 140 A to 690 V
S00 to S3
3RT15 contactors AC/DC operation, 4 main contacts (2 NO contacts + 2 NC contacts)
To switch three-phase induction motors up to 18.5 kW/400 V
Ie/AC-3 up to 60 °C: up to 40 A to 400 V
S00 to S2
3RT16 contactors AC operation
To switch three-phase capacitors up to 50 kvar/400 V
S00, S0 and S3
3RH control relays/3RT
contactors
DC operation with an extended operating range: 0.7 to 1.25 x US
3RT: to switch motors up to 45 kW/400 V
Ie/AC-3 up to 70 °C: 95 A to 400 V
3RH: to switch auxiliary circuits
Ie/AC-15/AC-14 up to 70 °C: 6 A/230 V
S00 to S3
3RT contactor relays
(interface)
DC operation with an extended operating range: 0.7 to 1.25 x US
To switch motors, 3-pole, up to 11 kW/400 V
Ie/AC-3 up to 60 °C: 25 A to 400 V
S00 and S0
3RA13 contactor combina-
tions
AC/DC operation
To reverse up to 45 kW/400 V, Ie/AC-3: 95 A/400 V
S00 to S31)
3RA14 contactor combina-
tions
AC/DC operation,
for wye-delta startup up to 75 kW/400 V, Ie/AC-3: 150 A/400 V
S00-S00-S00 to
S3-S3-S21)
3RH11 auxiliary contactors AC/DC operation,
to switch auxiliary circuits, 4-pole (basic unit)
Ie/AC-15/AC-14 up to 60 °C: 6 A/230 V
S00
3RH14 latched auxiliary
contactors
AC/DC operation,
to switch auxiliary circuits, 4-pole (basic unit)
Ie/AC-15/AC-14 up to 60 °C: 6 A/230 V
S00
3RH11 control relays
(interface)
DC operation with an extended operating range, 0.7 to 1.25 x US
to switch auxiliary circuits, 4-pole
Ie/AC-15/AC-14 up to 60 °C: 6 A/230 V
S00
Table 3-6: 3RT/3RH, designs
3RT1 Contactors/ 3RH1 Control relays
SIRIUS System Manual
3-12 A5E40534713002A/RS-AA/001
Auxiliary contacts and
snap-on accessories
A uniform and diverse range of auxiliary switches and accessories that
can be quickly upgraded and replaced is available for 3RT1 contactors up
to 45 kW for various applications.
The 3RH auxiliary contactors can be extended to form variants with a
maximum of 8 poles using attachable 2 or 4-pole auxiliary switch blocks.
Wiring kits with and without mechanical interlocking are available for put-
ting together 3RA contactor combinations for reversing and for wye-delta
starting.
The accessories are described in detail in Section 3.4, "Accessories".
3.2.1 Coil systems S00 to S3
Table 3-7: Coil systems
AC coil for
AC-control
Automatic reduction from high closing power to
low holding power
Short switching times
DC coil for
DC-control
Larger unit volumes (to achieve a tensile force
comparable to that of an AC coil)
Closing power = holding power
Longer switching times
3RT1 Contactors/ 3RH1 Control relays
SIRIUS System Manual
A5E40534713002A/RS-AA/001 3-13
3.2.2 Short-circuit protection for SIRIUS contactors
Section 3.7, "Technical specifications", has information on short-circuit pro-
tection. Fuses and circuit breakers can be used as short-circuit protective
devices for the contactors.
The test criteria that apply in this case are stipulated by EN 60 947-4-1
(VDE 0660 Part 102).
Coordination types Two types of assignment are defined in the standards that correspond to
two different levels of damage.
The following applies to both types of assignment:
In the event of a short-circuit, the short-circuit protective device used must
be able to disconnect the overcurrent that occurs. Persons or other parts of
the system must not be put at risk.
Coordination type 1 The load feeder (e.g. motor starter) can be inoperable after each short-cir-
cuit. Damage to the contactor and the overload relay is permissible and it is
only possible to continue operation after defective devices have been
repaired or replaced.
Coordination type 2 After a short-circuit, there must be no damage to the load feeder devices.
However, the contactor contacts can weld if they can be easily separated
again without distorting the contact pieces.
"weld free" There is information in the catalog, for weld free protection of the contac-
tors that needs to be taken into account.
Contactors with
overload relay
If contactors are combined with an overload relay, a smaller fuse should be
used as specified in the controls catalog for permissible short-circuit protec-
tion fuses for motor starters.