Features: CBI2410A DC UPS * * * * * * * * INPUT OUTPUT PROTECTION LOAD OUTPUT BATTERY OUTPUT OTHERS Input: Single-phase 115 - 277 VAC Output Load: power supply 24 VDC; 10 A Output: Battery charging 24 VDC; 10 A Suited for the following battery types: Open Lead Acid, Sealed Lead Acid, lead Gel and Ni-Cd (option) Automatic diagnostic of battery status. Switching technology, output voltage 22-28.8 VDC Three charging levels: Boost, trickle and recovery Protection degree IP20 - DIN rail mountable Cat. No. CBI2410A Nominal Input Voltage Voltage range Inrush Current ( Vn - In nom. Load). I2t Frequency Input Current (115 - 230 VAC) Internal fuse (factory replaceable) External Fuse (recommended) MCB curve B 115 / 230 ~ 277 VAC 90-135 / 180-305 VAC 16 A 5 msec 47 - 63 Hz 3.3 ~ 2.2 A 6.3 A 16 A Output Voltage (Vn) / Nominal Current (In) Output Current In Efficiency (at 50% of rated current) Turn-On delay after applying input voltage Start up with Strong Load (capacitive load) Dissipation power load max 24 VDC / 10A 10 A 83 % 1.5 sec. (max) Yes, Unlimited 28 W Short-circuit protection Over Load protection Over Voltage Output protection Over Temperature protection Yes Yes Yes (typ. 35 VDC) Yes Output voltage (at In) Nominal current Iload Continuous current (without battery) Iload= In Continuous current (with battery) Iload= In+ Ibatt Max. Current Output Load (Main) Iload (4 sec.) Max. Current Output Load (Back Up) Iload (4 sec.) Push Button or Remote Input Control (RTCONN cable) Time Buffering; min (switch output off without main input) Protection alarm against total discharge Threshold alarm for battery almost flat 22 ~ 28.8 VDC 1.1 x In A 5% 10 A 20 A 30 A max. 20 A max. Start From Battery Without Main : standard 5 min.: Require SW 19-20V DC battery 20-21 V DC battery Boost charge (25 C) (at In) Max. time Bust Charge Min. time Bust Charge Trickle charge (25 C) (at In) Jumper Configuration battery type (V cell) Ni-Cd (optional) Recovery Charge Charging current max Ibatt Charging current limiting Iadj Reverse battery protection Sulfated battery check Detection of element in short circuit Quiescent Current Charging Curve automatic: IUoUo Remote Input Control (RTCONN cable) 28.8 VDC 15 h 1 min. 27.5 VDC 2.23; 2.25; 2.27; 2.30; NiCd: 1.50 (20 elem.) 2 ~ 16 VDC 10 A 5% 20 - 100 % / Ibatt Yes Yes by Jumper Yes 5 mA 3 stage Boost /Trickle / Recovery Ambient temperature (operation) De Rating Ta > 50C Ambient temperature Storage Humidity at 25C no condensation Cooling MTBF (IEC 61709) -25 - +70C - 2.5%(In) / C -40 - +85C 95% Auto convention > 300.000 h For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power. 154 CBI2410A DC UPS The Altech DC-UPS system is built to optimize power management. The available power is automatically allocated between load and battery, supplying power to the load is the first priority. For high inrush applications the charging power will reroute automatically to the load. In this case the maximum available current on the load output is two times the value of the device rated current. Jumper for Battery Type Selection 1 2 3 4 1 2 3 4 Signal Output Contacts 1 2 3 4 1 2 3 4 LOW BATTERY OR BATTERY REPLACEMENT 6 DIAGNOSIS BATTERY BRIDGE ONLY START 6 115Vac NiCd NiMh (1) L N 6 Jumper for Functional Setting Battery Life Test On1 1 2 3 4 1 2 3 6 Fast Charge Enable2 1 2 3 4 6 Jumper present: life test enabled. Jumper present: fast test enabled. Jumper present: fast recovery charge enabled only for size 3. Possibility to recharge the battery also when the voltage is close to zero with the maximum power of the device. Yes - Optional Yes - Optional No Environment Insulation voltage (IN/OUT) Insulation voltage (input / ground) Insulation voltage (Output / ground) Protection Class (EN/IEC 60529) Pollution Degree Environment Connection TB, Screw Terminal Protection class (Ground Connected) Dimensions (WxHxD) 2.95x4.53x5.32 in Weight (approx.) MAINS OR BACKUP Gel Battery (1) 1 2 3 4 MAINS LOW BATTERY OR OR BATTERY BACKUP REPLACEMENT ADJ. 6 Gel Battery RJ45 Connection Input/Output Temp. Comp. Battery (with ext. probe) Remote monitoring display Can Bus 1 2 3 4 5 6 7 8 9 10 - + - + 6 Sealed Lead High 1 2 3 4 Yes Yes Yes 1A 30 VDC/60 VAC 1mA @ 5 VDC Open Lead Sealed Lead Low The Battery Care concept based on algorithms that achieve rapid and automatic charging, battery optimization during charging time, flat batteries recovery and real time diagnostic The Real Time Auto-diagnostic system, monitors battery faults, sulfated battery, short circuit battery elements, reverse polarity connection, battery disconnect. This conditions are detected and identified by the number of blinks of the diagnosis Led. Main or Backup Power Battery Power Low Battery Fault Max. Current Rating (Resistive Load) Minimum Permissible Current Rating 6 3000 VAC 1605 VAC 500 VAC IP20 2 2,5 mm (24-14AWG) Class I 100x115x135 mm Battery Out 1 CBI In Vac Load Mains or Backup Out 2 Battery Low or Battery Replacement Start From Battery 0.85 kg (1.9 Lbs) Safety and EMC IEC/EN 60335-2-29 EN60950 / UL1950 / CE EN54-4 89/336/EEC DIN41773 IEC 61000-6-4 IEC 61000-6-2 The Altech DC-UPS system is designed to charge and monitor all battery types, by selecting the battery type via jumpers. The predefined curves include Open Lead Acid, Sealed Lead Acid, Gel, Ni-Cd (optional) battery types. The charging curve are programmed to automatically switch between Recovery Charge, Boost charge and Trickle charge. The continuous battery efficiency monitoring, reduces battery damage risk and allows a safe operation in permanent connection. Voltage Voltage / Current Battery charger standard compliance Safety standards compliance: Fire Detection and alarm compliance EMC Directive Charging cycle Emission Immunity Current Recovery Charge Fast / Boost Charge Tickle / Float Charge A compact and rugged metal case with DIN rail mounting bracket provide an easy installation and an IP20 protection. Altech Corp.(R) * 35 Royal Road * Flemington, NJ 08822-6000 * Phone (908)806-9400 * FAX (908)806-9490 155 Mouser Electronics Authorized Distributor Click to View Pricing, Inventory, Delivery & Lifecycle Information: Altech: CBI2410A