Solid-state Relay G3CN PCB-mounting SSR for FA Equipment Requiring High Reliability Wide I/O voltage range: 3 to 28 VDC input and 75 to 264 VAC output or 3 to 28 VDC input and 3 to 52.8 VDC output. Two load currents available: 2 A and 3 A Flat and vertical models available for a variety of applications. Approved by UL and CSA. RC Ordering Information Isolation Photocoupler Zero cross function Yes Indicator No Rated output voltage (Applicable output load) 2 A at 100 to 240 VAC (2 A at 75 to 264 VAC) Rated input voltage 4 to 24 VDC Model G3CN-202P-US G3CN-202P1-US* 3 A at 100 to 240 VAC (3 A at 75 to 264 VAC) G3CN-203P-US G3CN-203P1-US* Phototriac No 2 A at 100 to 240 VAC (2 A at 75 to 264 VAC) 5, 12, 24 VDC** G3CN-202PL-US G3CN-202PL1-US* 3 A at 100 to 240 VAC (3 A at 75 to 264 VAC) G3CN-203PL-US G3CN-203PL1-US* Photocoupler --- 2 A at 4 to 48 VDC (2 A at 3 to 52.8 VDC) 4 to 24 VDC G3CN-DX02P-US G3CN-DX02P1-US* 3 A at 4 to 48 VDC (3 A at 3 to 52.8 VDC) G3CN-DX03P-US G3CN-DX03P1-US* *Vertical models. **When ordering, specify the input voltage 171 G3CN G3CN Specifications Ratings Input Model Rated voltage Operating voltage Impedance Voltage level Must operate voltage G3CN-202P(1)-US G3CN-203P(1)-US 4 to 24 VDC 3 to 28 VDC 1.5 k +20%/-10% 3 VDC max. G3CN-202PL(1)-US G3C 0 ( ) US G3CN 203PL(1) US G3CN-203PL(1)-US 5 VDC 4 to 6 VDC 390 20% 4 VDC max. 12 VDC 9.6 to 14.4 VDC 900 20% 9.6 VDC max. 24 VDC 19.2 to 28.8 VDC 2 k20% 19.2 VDC max. 4 to 24 VDC 3 to 28 VDC 1.5 k +20%/-10% 3 VDC max. G3CN-DX02P(1)-US G3CN-DX03P(1)-US Note: Must release voltage 1 VDC min. The input impedance is measured at the maximum value of the operating voltage. For example, with the model rated at 4 to 24 VDC, the input impedance is measured at 28 VDC. Output Model Applicable load Rated load voltage Load volage range Load current Inrush current Without heat sink G3CN-202P(1)-US G3CN-202PL(1)-US 100 to 240 VAC 75 to 264 VAC G3CN-203P(1)-US G3CN-203PL(1)-US G3CN-DX02P(1)-US 4 to 48 VDC 3 to 52.8 VDC G3CN-DX03P(1)-US 0.1 to 2 A 30 A (60 Hz, 1 cycle) 0.1 to 3 A 45 A (60 Hz, 1 cycle) 0.1 to 2 A 12 A (10 ms) 0.1 to 3 A 18 A (10 ms) Characteristics Item G3CN-202P(1)/203P(1)-US G3CN-202PL(1)/203PL(1)-US G3CN-DX02P(1)/03P(1)-US Operate time 1/2 of load power source cycle + 1 ms max. 1 ms max. 0.5 ms max. Release time 1/2 of load power source cycle + 1 ms max. 1/2 of load power source cycle + 1 ms max. 2 ms max. Output ON voltage drop 1.6 V (RMS) max. Leakage current 5 mA max. (at 100 VAC) 10 mA max. (at 200 VAC) Insulation resistance 100 M min. (at 500 VDC) Dielectric strength 2,500 VAC, 50/60 Hz for 1 min Vibration resistance Malfunction: 10 to 55 Hz, 1.5-mm double amplitude Shock resistance Malfunction: 1,000 m/s2 Ambient temperature Operating: -30C to 80C (with no icing nor condensation) Storage: -30C to 100C (with no icing nor condensation) Ambient humidity Operating: 45% to 85% Approved standards UL508, UL114 File No.E64562, CSA C22.2 (No.0, No.14) File No. LR35535 Weight Approx. 25 g 172 1.5 V max. 2.5 mA max. (at 100 VAC) 5 mA max. (at 200 VAC) 5 mA max. (at 50 VDC) G3CN G3CN Engineering Data Load Current vs. Ambient Temperature Characteristics G3CN-203P(1)/-203PL(1)/-DX03P(1)-US Load current (A) Load current (A) G3CN-202P(1)/-202PL(1)/-DX02P(1)-US Ambient temperature (C) Ambient temperature (C) Inrush Current Resistivity Non-repetitive (Keep the inrush current to half the rated value if it occurs repetitively.) G3CN-DX02P(1)-US Inrush current (A. Peak) Inrush current (A. Peak) G3CN-202P(1)/-202PL(1)-US Energizing time (ms) G3CN-DX03P(1)-US Inrush current (A. Peak) Inrush current (A. Peak) G3CN-203P(1)/-203PL(1)-US Energizing time (ms) Energizing time (ms) Energizing time (ms) 173 G3CN G3CN Dimensions Note: All units are in millimeters unless otherwise indicated. Flat Model 33 max. G3CN-20jP/-20jPL/-DX0jP Terminal Arrangement/ Mounting Holes (Bottom View) 25 max. Four 1.2-dia. holes Two, 4 dia. holes 25 12.5 10 14.5 20 max. max. 1.5 max. Two, 2-dia. holes 0.4 250.5 0.7 Terminal Arrangement/ Internal Connections (Bottom View) 0.7 100.5 12.50.5 + Input voltage 3 1 + (+) Input - Load (+) Load power supply - (-) 4 2 Note: Vertical Model Load (-) Values in parentheses apply to the DC-load versions. G3CN-20jP1/-20jPL1/-DX0jP1 33 max. Terminal Arrangement/ Mounting Holes (Bottom View) 14 max. Two, 2-dia. holes Four 1.2-dia. holes Pattern Pattern 5 26.5 max. 32 max. 1.5 max. 50.5 (17.5) 27.5 Terminal Arrangement/ Internal Connections (Bottom View) (17.5) 27.50.5 0.7 50.5 Input voltage 0.4 31 - (-) (+) Load 3 - 2 1 + Input Note: Load power supply + 4 174 5 (-) (+) Load Values in parentheses apply to the DC-load versions. G3CN G3CN Precautions Refer to pages 11 to 19 for general precautions. Connection Protective Component With the SSR for DC switching, the load can be connected to either positive or negative output terminal of the SSR. Since the SSR does not incorporate an overvoltage absorption component, be sure to connect an overvoltage absorption component when using the SSR under an inductive load. ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527. Cat. No. K063-E1-2A 175