Plug Output Time range Supply: 24 VAC Supply: 115 VAC Supply: 230 VAC Supply: 24 VDC
Circular SPDT 0.15 s-220 h S 1231 156 024 S 1231 156 115 S 1231 156 230 S 1231 156 724
DPDT 0.15 s-220 h S 1231 166 024 S 1231 166 115 S 1231 166 230 S 1231 166 724
Specifications are subject to change without notice (05.02.03) 1
Timers
Multi time range, plug-in,
asymmetrical ON/OFF recyc-
ler with 20 selectable time
ranges up to 220 h. Appli-
cable where loads are
desired to switch on or off
for short or very long cycles.
Time ranges 0.15 s - 1.5 s
Selectable by DIP-switch 0.3 s - 3 s
0.6 s - 6 s
1.2 s - 12 s
2.5 s - 25 s
5 s - 50 s
10 s - 100 s
20 s - 200 s
40 s - 400 s
1.3 m - 13 m
2.6 m - 26 m
5 m - 50 m
10 m - 100 m
20 m - 200 m
40 m - 400 m
1.4 h - 14 h
2.8 h - 28 h
5.5 h - 55 h
11 h - 110 h
22 h - 220 h
Accuracy 0 to +10% on max.
min. actual time set time
Repeatability deviation 1%
Time variation
Within rated power supply 0.05%/V
and ambient temperature 0.2%/°C
Reset Power supply interruption min.
Time and/or relay 200 ms
20 selectable time ranges: 0.15 s to 220 h
Automatic start (OFF- or ON-time first)
Separate setting for OFF- and ON-time periods
Oscillator-controlled time circuit
Repeatability deviation: 1%
Output: 10 A SPDT or 8 A DPDT relay
Plug-in type module
S-housing
LED-indication for relay and power supply on
AC or DC power supply
Asymmetrical Multi Recycler
Type S 1231
Housing
Type /function
Output
Power supply
Power supply AC types Installation cat. III (IEC 60664)
Rated operational voltage
through pins 2 & 10 230 230 VAC ± 15%, 45 to 65 Hz
115 115 VAC ± 15%, 45 to 65 Hz
024 24 VAC ± 15%, 45 to 65 Hz
Drop out tolerance 40 ms
Rated insulation voltage 2.0 kVAC (rms)
Rated transient protection volt. 4 kV (1.2/50 µs)
(line/neutral)
Power supply DC type Installation cat. III (IEC 60664)
Rated operational voltage 724 24 VDC ± 15% (pin 2 pos.)
Rated insulation voltage None
Rated transient protection volt. 800 V (1.2/50 µs)
Consumption AC supply 2.5 VA
DC supply 1.5 W
Product Description Ordering Key
Type Selection
Time Specifications Supply Specifications
S 1231 156 024
2Specifications are subject to change without notice (05.02.03)
OFF-time period first
The OFF-time period starts
when power supply is applied.
At the end of the set OFF-time
period, the relay operates and
the ON-time period starts.
At the end of the set ON-time
period, the relay releases and
the OFF-time period starts
again.
This sequence continues until
power supply is interrupted.
S 1231
ON-time period first
The relay operates and the
ON-time period starts when
power supply is applied.
At the end of the set ON-time
period, the relay releases and
the OFF-time period starts.
At the end of the set OFF-time
period the relay operates and
the ON-time period starts
again.
This sequence continues until
power supply is interrupted.
S 1231 156 S 1231 166
Output SPDT relay DPDT relay
Basic electrical insulation 250 VAC (rms) (contact/electronics) 250 VAC (rms) (contacts/elec., contact/contact)
Contact ratings (AgCdO) µ (micro gap) µ (micro gap)
Resistive loads AC 1 10 A/250 VAC (2500 VA) 8 A/250 VAC (2000 VA)
DC 1 1 A/250 VDC (250 W) 0.4 A/250 VDC (100 W)
or 10 A/25 VDC (250 W) 4 A/25 VDC (100 W)
Small inductive loads AC 15 2.5 A/230 VAC 2.5 A/230 VAC
DC 13 5 A/24 VDC 5 A/24 VDC
Mechanical life 30 x 10
6
operations 30 x 10
6
operations
Electrical life AC 1 2.5 x 10
5
operations (at max. load) 2.5 x 10
5
operations (at max. load)
Operating frequency 7200 operations/h 7200 operations/h
Insulation voltages
Rated insulation voltage 2.0 kVAC (rms) (contact/electronics) 2.0 kVAC (rms) (contact/electronics)
Rated transient protection volt. 4 kV (1.2/50 µs) (contact/electronics) (IEC 60664) 4 kV (1.2/50 µs) (contact/electronics) (IEC 60664)
Power-on delay 200 ms
Power-off delay 200 ms
Indication for
Power supply ON LED, green
Output ON LED, red
Environment IP 20 B
Pollution degree 2 (IEC 60664)
Operating temperature -20 to +50°C (-4 to +122°F)
Storage temperature -50 to +85°C (-58 to +185°F)
Weight
AC supply 200 g
DC supply 125 g
Approvals UL, CSA
CE-marking Yes
OFF-time first
Power supply
S 1231 156, S 1231 166
ON-time first
Power supply
S 1231 156, S 1231 166
SocketsS 411
Hold down springHF
Mounting rack SM 13
Socket covers BB 4
Front mounting bezel FRS2
Potentiometer lock PL 2
For further information refer to "Accessories".
For other AC/DC voltages refer to "General Information".
Output Specifications
General Specifications Mode of Operation
AccessoriesWiring Diagram
Specifications are subject to change without notice (05.02.03) 3
1 2 3 4 5 ON-time
6 7 8 9 10 OFF-time
Selection of function
OFF-time period first:
(no connection between pins
6 & 7).
ON-time period first:
Interconnect pins 6 and 7.
Selection of time range
DIP-switch selector:
ON-time ranges:
Switches 1 to 5.
OFF-time ranges:
Switches 6 to 10.
Time setting
Two independent knob-ad-
justable potentiometers for
OFF- and ON-time on scale
in per cent of max. time.
DIP-switches for selecting
function and time are placed
behind a small removable
front plate on the time relay.
S 1231
Example of time setting
ON: 0.15 - 1.5 s
OFF: 1.3 - 13 m
1 2 3 4 5 6 7 8 9 10
Function/Time Setting
Operation Diagram
0.15 s - 1.5 s
0.3 s - 3 s
0.6 s - 6 s
1.2 s - 12 s
2.5 s - 25 s
5 s - 50 s
10 s - 100 s
20 s - 200 s
40 s - 400 s
1.3 m - 13 m
2.6 m - 26 m
5 m - 50 m
10 m - 100 m
20 m - 200 m
40 m - 400 m
1.4 h - 14 h
2.8 h - 28 h
5.5 h - 55 h
11 h - 110 h
22 h - 220 h
Power supply
Relay on:
Pins 6 & 7 not connected
Relay on:
Pins 6 & 7 connected