3 Phase RHP - Hybrid Solid State Contactors
Part Number Nomenclature
D54012RHP3
Nominal Coil
/Control Voltage
D5: 5 VDC
D12: 12 VDC
D24: 24 VDC
E: 24 VAC
F: 120 VAC
G: 220 VAC
Operating
Voltage VAC
50/60 Hz
12: 120 V 1-phase
24: 240 V 3-phase
or 1-phase
28: 280 V 3-phase
60: 600 V 3-phase
Three
Phase
Device
Load Current
40: 40 Amps
50: 50 Amps
SERIES
Derating Curves
3RHPXX40XX
25 35 45 55 65 75
Ambient Temperature, °C
20
25
30
35
40
45
Load Current, Amps rms
AWG # 6
AWG # 8
Power lead size
3RHPXX50XX
25 35 45 55 65 75
Ambient Temperature, °C
20
25
30
35
40
45
50
55
Load Current, Amps rms
AWG # 6
AWG # 8
Power lead size
Safe Operating Area
Safe Operating Area
3 Phase Contactor
DC Input
40-50 Amp
120/240 VAC
Combined SSR and EMR advantages
Lifetime >2 million operations @ full load
No heat sink required
DC logic compatible input
Input status LED indicator
Wire, lug or quick connect termination
DP contactor footprint
CE compliant & UL/cUL recognized
100k-cycle UL508 endurance rating
3 Phase Contactor
AC Input
40-50 Amp
280/600 VAC
Combined SSR and EMR advantages
Lifetime >2 million operations @ full load
No heat sink required
Input status LED indicator
Wire, lug or quick connect termination
DP contactor footprint
CE compliant & UL/cUL recognized
100k-cycle UL508 endurance rating
CONTROL SPECIFICATIONS
Coil Voltage Range
Coil Power Consumption, Inrush
Coil Power Consumption, Sealed
Control Voltage Suffix
Voltage suffix
Operating Voltage (50/60Hz)
Maximum Off-State Leakage Current per channel
Load Current suffix
Maximum Load Current per Phase @ 4C
Power terminals / wire range
28
24 - 280 VAC
0.05 mA @ 240 VAC
40
40 A Resistive
Dual quick connect and Binder
head screws / AWG#14 - AWG#8
Input to Output Dielectric Isolation.
Input/Output to Ground Dielectric Isolation.
Contacts (Double Break )
Ambient Operating Temperature Range
Ambient Storage Temperature Range
Maximum Number of Operations per Minute
Lifetime @ Rated Load Current, 4C ambient
temp, 30 operations/min, Rated Vcontrol
Weight (typical)
See Derating Curves for additional operational conditions.
The RHP includes a Solid-State Relay. Therefore, the output is never completely open.
The RHP includes an overtemperature protection for the Solid-State Module.
GENERAL SPECIFICATIONS
540 grs (1.19 lb)
2500 VAC
-20°C to 7C
4000 VAC
Three Normally Open
30 operations per min
> 2 Million operations
-40°C to 10C
OUTPUT SPECIFICATIONS
Dual quick connect and Box
lugs / AWG#14 - AWG#6
)mN 9.2( sbl ni 52)mN 1.2( sbl ni 81stnemeriuqer euqrot wercS
60
48 - 600 VAC
0.06 mA @ 480 VAC
50
50 A Resistive
2
3
3
1
1
1
4
2
Specificationts @ 25°C unless otherwise noted.
1
3
4
Min. Turn-On Voltage
Min. Turn-Off Voltage
E
20 - 26 VAC, 50/60 Hz
56 VA @ 24 VAC
6.6 VA @ 24 VAC
Coil Terminals 10 in lb (1.13 Nm) 10 in lb (1.13 Nm)10 in lb (1.13 Nm) )mN 6.0( bl ni 13.5)mN 6.0( bl ni 13.5)mN 6.0( bl ni 13.5rotcennoC tupnI
20 VAC
12 VAC
F
100 - 130 VAC, 50/60 Hz
56 VA @ 120 VAC
6.6 VA @ 120 VAC
100 VAC
24 VAC
G
208 - 240 VAC, 50/60 Hz
56 VA @ 220 VAC
6.6 VA @ 220 VAC
208 VAC
48 VAC
Max. Turn-On Time
Max. Turn-Off Time
16.6 mS @ 60 Hz / 20 mS @ 50 Hz
32 mS @ 60 Hz / 40 mS @ 50 Hz
CONTROL SPECIFICATIONS
Control Voltage Range
Control Voltage Suffix
Max. Reverse Voltage
Min. Turn-On Voltage
Min. Turn-Off Voltage
Input Current
D5
4.5 - 5.5 VDC
-5.5 VDC
4.5 VDC
1 VDC
12mA @ 5 VDC
D12
10 - 15 VDC
-15.5 VDC
9.5 VDC
2 VDC
12mA @ 12 VDC
D24
22 - 27 VDC
-27.5 VDC
9.5 VDC
2 VDC
12mA @ 24 VDC
Voltage suffix
Operating Voltage (50/60Hz)
Maximum Off-State Leakage Current per channel
Load Current suffix
Maximum Load Current per Phase @ 4C
Power terminals / wire range
Input to Output Dielectric Isolation
Input/Output to Ground Dielectric Isolation
Contacts (Double Break)
Ambient Operating Temperature Range
Ambient Storage Temperature Range
Maximum Number of Operations per Minute
Lifetime @ Rated Load Current, 40°C ambient
temp, 30 operations/min, Rated Vcontrol
Weight (typical)
OUTPUT SPECIFICATIONS
12
100 - 120 VAC
40
40 A Resistive
Dual quick connect and Binder
head screws / AWG#14 - AWG#8
0.05 mA @ 120 VAC
Three Normally Open
30 operations per min
> 2 Million operations
-40°C to 100°C
4000 VAC
GENERAL SPECIFICATIONS
24
208 - 240 VAC
0.06 mA @ 240 VAC
50
50 A Resistive
Dual quick connect and Box
lugs / AWG#14 - AWG#6
540 grs (1.19 lb)
2500 VAC
-20°C to 7C
2
3
3
4
Max. Turn-On Time
Max. Turn-Off Time
16.6 mS @ 60 Hz / 20 mS @ 50 Hz
32 mS @ 60 Hz / 40 mS @ 50 Hz
)mN 9.2( sbl ni 52)mN 1.2( sbl ni 81stnemeriuqer euqrot wercS
See Derating Curves for additional operational conditions.
The RHP includes a Solid-State Relay. Therefore, the output is never completely open.
The RHP includes an overtemperature protection for the Solid-State Module.
1
1
1
2
Specificationts @ 2C unless otherwise noted.
1
3
4
PATENT
PENDING
PATENT
PENDING
Obsolete
3 Phase RHP - Hybrid Solid State Contactors
Typical Electrical Connection for 3 Phase Applications
Optional Electrical Connections for Single Phase Applications
~
HYBRID SOLID STATE
CONTACTOR
120/240 VAC
Single Phase
Operating Voltage
I L1
R1
1L1
3L2
5L3=NC
IL1 ≤ Rated current
6T3=NC
Line
Neutral
DC Input/Control Voltage
(D5, D12, D24 input versions)
-+
~
HYBRID SOLID STATE
CONTACTOR
120/240 VAC
Single Phase
Operating Voltage
IL2 ≤ Rated current
IL3 ≤ Rated current
IL2 + IL3 > Rated current
I L3
I L2
R1
R2
NC
Line
Neutral
1L1
3L2
5L3
DC Input/Control Voltage
(D5, D12, D24 input versions)
-+
~
HYBRID SOLID STATE
CONTACTOR
-+
120/240 VAC
Single Phase
Operating Voltage
IL1 = (IL2 + IL3) ≤ Rated current
I L3
I L1
I L2
R1
R2
1L1
3L2
5L3
DC Input/Control Voltage
(D5, D12, D24 input versions)
Line
Neutral
HYBRID SOLID STATE
CONTACTOR
~
~
~
-+
VLL
I L1
I L3
DC Input/Control Voltage
(D5, D12, D24 input versions)
Load
I L1
5L3
3L2
1L1
6T3
4T2
2T1
3 Phase AC
Operating Voltage
AC Input/Control Voltage
(E, F, G input versions)
AC Input/Control Voltage
(E, F, G input versions)
AC Input/Control Voltage
(E, F, G input versions)
AC Input/Control Voltage
(E, F, G input versions)
The single phase supply voltage must be wired to terminal 1L1 and 3L2 for proper single phase operation.
In applications switching two single phase loads (R1 and R2) where the combined load current exceeds
the contactor’s rating (40 or 50 Amps) the return/neutral lead must not be wired through the contactor
(see above drawing).
6
Match VLL to voltage suffixes 28 & 60 for options E, F & G and 12 & 24 for options DX.
5
5
7
7
6
(For output voltage options 24, 28, 60)
(For output voltage options 12, 24, 28, 60)
DO NOT apply any AC voltage to contactor coil connections, for DC versions only.