0713 BU-SB13728 Page 1 of 3 Data Sheet # 1017
FUSETRON™ 600V Class RK5
FRS-R — 600Vac/300Vdc, 110-60A, Dual Element, Time-Delay Fuses
Description: Advanced protection, energy efficient Class RK5
dual element, current-limiting, time-delay fuses with optional
open fuse indication on select ratings.
Time-delay – 10 second (minimum) at 500% of rated current.
Catalog Symbol: FRS-R-(amp) (non-inducating)
FRS-R-(amp)ID (indicating
Ratings:
Volts — 600Vac, 300Vdc (110-30A)
— 600Vac, 250Vdc (35-60A)
Amps 110-60A
IR — 200kA Vac RMS Sym.
— 20kA Vdc
Agency Information:
CE, UL Listed, Std. 248-12, Class RK5, Guide JDDZ,
File E4273
CSA Certified, C22.2 No. 248.12, Class 1422-02, File 53787
Catalog Numbers (amps) — Non-indictaing fuses
FRS-R-110 FRS-R-1810 FRS-R-8*
FRS-R-18FRS-R-2 FRS-R-9*
FRS-R-15100 FRS-R-214FRS-R-10*
FRS-R-210 FRS-R-212FRS-R-12*
FRS-R-14FRS-R-2810 FRS-R-15*
FRS-R-310 FRS-R-3 FRS-R-1712*
FRS-R-410 FRS-R-3210 FRS-R-20*
FRS-R-12FRS-R-312FRS-R-25*
FRS-R-610 FRS-R-4 FRS-R-30*
FRS-R-810 FRS-R-412FRS-R-35*
FRS-R-1 FRS-R-5 FRS-R-40*
FRS-R-118FRS-R-5610 FRS-R-45*
FRS-R-114FRS-R-6* FRS-R-50*
FRS-R-1410 FRS-R-614* FRS-R-60*
FRS-R-112FRS-R-7*
FRS-R-1610 FRS-R-712*
* Open fuse indication available by inserting the sufix “ID.” E.g., FRS-R-15ID.
Carton Quantity and Weight
Amp Rating Carton Qty.
110–15 10
1712–30 10
35-60 10
Dimensions - in
Features:
Provides motor overload, ground fault and short-circuit
protection. When used in circuits subject to surge currents
such as those caused by motors, transformers and other
inductive components, these fuses can be sized close to
full-load amps to give maximum overcurrent protection.
Permits the use of smaller and less costly switches. The
time-delay feature makes it possible to use fuse amp ratings
which are much smaller than those of non-time delay fuses.
Considerable cost saving occurs by permitting the use of
smaller size switches, panels and fuses themselves.
Provides a higher degree of short-circuit protection (greater
current-limitation) in circuits in which surge currents or
temporary overloads occur.
Helps protect motors against burnout from overloads
Gives motor running back-up protection to motors without
extra costs
Helps protect motors against burnout from single phasing
on three phase systems
Simplifies and improves blackout prevention
(selective coordination)
Dual-element fuses can be applied in circuits subject to
temporary motor overloads and surge currents to provide
both high-performance, short-circuit and overload
protection
The overload element provides protection against low level
overcurrent of overloads and will hold an overload which is
five times greater than the amp rating of the fuse for a
minimum of ten seconds
Recommended Fuse Blocks
Fuse Amps 1-Pole 2-Pole 3-Pole
0-30 R60030-1 R60030-2 R60030-3
35-60 R60060-1 R60060-2 R60060-3
For additional information on the R600 Series of 600 volt fuse
blocks, see Data Sheet # 1111.
Fuse Reducers For Class R Fuses
Equipment Desired Fuse Catalog Numbers
Fuse Clips (Case) Size (Pairs) 600V
60A 30A NO.663-R
100A 30A NO.216-R
60A NO.616-R
200A 60A NO.626-R
For additional information on Class R fuse reducers, see
Data Sheet # 1118.
0.81" (±0.008)
5"
(± 0.31)
1/10 to 30A
5.5"
(± 0.31)
35 to 60A
1.06" (±0.008)
0713 BU-SB13728 Page 2 of 3 Data Sheet # 1017
FUSETRON™ 600V Class RK5
Time-Current Curves - Average Melt
110 to 8 Amps
AMP RATING
CURRENT IN AMPS
TIME IN SECONDS
FRS-R — 600Vac/300Vdc, 110-60A, Dual Element, Time-Delay Fuses
0713 BU-SB13728 Page 3 of 3 Data Sheet # 1017
FUSETRON™ 600V Class RK5
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information
contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
Current-Limitation CurvesTime-Current Curves - Average Melt
10 to 60 Amps
400000
9000
8000
7000
7000
6000
6000
300000
200000
100000
5000
4000
4000
90000
3000
2000
1000
3000
70000
80000
70000
60000
B
A
50000
60000
200000
20000
2000
40000
100000
50000
10000
5000
1000
30000
90000
80000
40000
9000
8000
30000
20000
10000
30A
60A
AMP RATING
INSTANTANEOUS PEAK LET-THROUGH CURRENT IN AMPS
PROSPECTIVE SHORT-CIRCUIT CURRENT - SYMMETRICAL RMS AMPS
AMP RATING
CURRENT IN AMPS
TIME IN SECONDS
FRS-R — 600Vac/300Vdc, 110-60A, Dual Element, Time-Delay Fuses
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information
contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
Current-Limiting Effects
Prosp. Let-Through Current
S.C.C. (Apparent RMS Symmetrical Vs. Fuse Rating)
30A 60A
5000 1000 1000
10,000 1000 2000
15,000 1000 2000
20,000 2000 2000
25,000 2000 2000
30,000 2000 3000
35,000 2000 3000
40,000 2000 3000
50,000 2000 3000
60,000 2000 3000
70,000 3000 4000
80,000 3000 4000
90,000 3000 4000
100,000 3000 4000
150,000 3000 5000
200,000 4000 6000