SITOP PSU8200 1ph ___________________ Overview 1 ___________________ Safety instructions SITOP power supply Description, device design, 2 ___________________ dimension drawing 3 ___________________ Mounting/removal SITOP PSU8200 1ph Manual Mounting position, mounting 4 ___________________ clearances 5 ___________________ Installation 6 ___________________ Technical data ___________________ 7 Safety, approvals, EMC ___________________ 8 Ambient conditions ___________________ 9 Applications ___________________ 10 Environment ___________________ 11 Service & Support SITOP PSU8200 24 V/5 A 6EP3333-8SB00-0AY0 SITOP PSU8200 24 V/10 A 6EP3334-8SB00-0AY0 SITOP PSU8200 24 V/20 A 6EP1336-3BA10 SITOP PSU8200 24 V/40 A 6EP3337-8SB00-0AY0 08.2016 C98130-A7633-A1-5-7629 Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger. DANGER indicates that death or severe personal injury will result if proper precautions are not taken. WARNING indicates that death or severe personal injury may result if proper precautions are not taken. CAUTION indicates that minor personal injury can result if proper precautions are not taken. NOTICE indicates that property damage can result if proper precautions are not taken. If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage. Qualified Personnel The product/system described in this documentation may be operated only by personnel qualified for the specific task in accordance with the relevant documentation, in particular its warning notices and safety instructions. Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with these products/systems. Proper use of Siemens products Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems. The permissible ambient conditions must be complied with. The information in the relevant documentation must be observed. Trademarks All names identified by (R) are registered trademarks of Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner. Disclaimer of Liability We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions. Siemens AG Division Process Industries and Drives Postfach 48 48 90026 NURNBERG GERMANY C98130-A7633-A1-5-7629 09/2016 Subject to change Copyright (c) Siemens AG 2016. All rights reserved Overview 1-phase SITOP PSU8200 power supplies from the SITOP modular product line are highperformance, regulated technology power supplies for automated systems and machines. In addition to the basic functions required, these low-profile power supply units have an outstanding overload behavior. The key benefits of the product include: Suitable for connecting to almost any 1-phase line supply around the world AC and DC input voltages possible (only for 6EP1336-3BA10) Output voltage can be adjusted in the range 24 - 28 (28.8) V Power-Boost in operation with 3x rated current for 25 ms Extra-Power with 1.5x rated current for 5 seconds for switching on loads with a high inrush current Especially low width without requiring any lateral mounting clearances Ambient temperature -25 ... 70 C (derating from 60 C) Selectable short-circuit response (constant current or latching shutdown) A soft characteristic can be selected for a parallel connection (for uniform load distribution of power supply units of the same type) 3 LEDs are used to display the operating state Signaling contact "24 V O.K." SITOP PSU8200 1ph Manual, 08.2016, C98130-A7633-A1-5-7629 3 Overview Remote "ON/OFF" contact for switching the power supply output into a no current condition (only for 6EP3333-8SB00-0AY0 and 6EP3334-8SB00-0AY0) To increase the system availability, these reliable power supplies can be expanded using SITOP supplementary modules (redundancy module, selectivity module, buffer module), as well as SITOP DC-USV modules Ordering data The following device versions are available: Regulated power supply unit SITOP PSU*8200 1ph Type Order number 1-phase 120/230 V AC input, 6EP3333-8SB00-0AY0 24 V / 5 A output 1-phase 120/230 V AC input, 6EP3334-8SB00-0AY0 24 V / 10 A output 1 and 2-phase AC or DC input, 6EP1336-3BA10 24 V DC / 20 A output 1 and 2-phase 120/230 V AC input, 6EP3337-8SB00-0AY0 24 V /40 A output Accessories Type Order number Device identification labels 20 mm x 7 mm, Ti grey 3RT2900-1SB20 SITOP PSU8200 1ph 4 Manual, 08.2016, C98130-A7633-A1-5-7629 Table of contents Overview................................................................................................................................................. 3 1 Safety instructions ................................................................................................................................... 7 2 Description, device design, dimension drawing........................................................................................ 9 2.1 Device description..................................................................................................................... 9 2.2 Connections and terminal designation....................................................................................12 2.3 Potentiometer ..........................................................................................................................14 2.4 Status displays and signaling .................................................................................................15 2.5 Change-over switch ................................................................................................................18 2.6 Remote contact .......................................................................................................................20 2.7 Block diagram .........................................................................................................................21 2.8 Dimensions and weight ...........................................................................................................24 3 Mounting/removal ................................................................................................................................. 27 4 Mounting position, mounting clearances ................................................................................................ 29 5 6 4.1 Standard mounting position ....................................................................................................29 4.2 4.2.1 4.2.2 4.2.3 4.2.4 Other mounting positions ........................................................................................................31 6EP3333-8SB00-0AY0 ...........................................................................................................31 6EP3334-8SB00-0AY0 ...........................................................................................................33 6EP1336-3BA10 .....................................................................................................................35 6EP3337-8SB00-0AY0 ...........................................................................................................37 Installation ............................................................................................................................................ 39 5.1 Line-side connection ...............................................................................................................39 5.2 Output-side connection ...........................................................................................................41 Technical data ...................................................................................................................................... 43 6.1 Input ........................................................................................................................................43 6.2 Output .....................................................................................................................................45 6.3 Efficiency .................................................................................................................................53 6.4 Closed-loop control .................................................................................................................55 6.5 Protection and monitoring .......................................................................................................56 6.6 MTBF ......................................................................................................................................56 6.7 Mechanical system .................................................................................................................57 6.8 Accessories .............................................................................................................................58 6.9 Dimension drawing .................................................................................................................58 SITOP PSU8200 1ph Manual, 08.2016, C98130-A7633-A1-5-7629 5 Table of contents 7 Safety, approvals, EMC ........................................................................................................................ 59 7.1 Safety ..................................................................................................................................... 59 7.2 Test voltage............................................................................................................................ 60 7.3 Approvals ............................................................................................................................... 61 7.4 EMC ....................................................................................................................................... 62 8 Ambient conditions................................................................................................................................ 63 9 Applications .......................................................................................................................................... 65 9.1 Parallel connection to increase power rating ......................................................................... 65 9.2 Parallel connection for redundancy ....................................................................................... 67 9.3 Series connection for increased voltage ................................................................................ 68 9.4 Overload protection in the 24 V output circuit ........................................................................ 69 9.5 Protection against short-time voltage dips ............................................................................. 70 9.6 Protecting against longer power failures ................................................................................ 71 10 Environment ......................................................................................................................................... 73 11 Service & Support ................................................................................................................................. 75 SITOP PSU8200 1ph 6 Manual, 08.2016, C98130-A7633-A1-5-7629 Safety instructions 1 WARNING Correct handling of the devices When operating electrical devices, it is inevitable that certain components will carry dangerous voltages. Therefore, failure to handle the units properly can result in death or serious physical injury as well as extensive property damage. Only appropriately qualified personnel may work on or in the vicinity of this equipment. Perfect, safe, and reliable operation of this equipment is dependent on proper transportation, storage, installation and mounting. Before installation or maintenance work can begin, the system's main switch must be switched off and measures taken to prevent it being switched on again. If this instruction is not observed, touching live parts can result in death or serious injury. SITOP PSU8200 1ph Manual, 08.2016, C98130-A7633-A1-5-7629 7 Safety instructions SITOP PSU8200 1ph 8 Manual, 08.2016, C98130-A7633-A1-5-7629 Description, device design, dimension drawing 2.1 2 Device description SITOP PSU8200 5 A 1ph and SITOP PSU8200 10 A 1ph are primary-clocked power supplies for connection to 1-phase AC line supplies. An electronically regulated DC voltage that can be set via a potentiometer is available at the output of the device. The output of the device is isolated, no-load proof and short-circuit proof. The LEDs indicate the operating state. The operating state of the device can be processed via the signaling contact. The device can be switched ON/OFF remotely using a remote contact. AC input DC output 24 - 28.8 V potentiometer Signaling contact (13, 14), remote contact (15, 16) Indicator lights (24 V O.K., OVERLOAD, SHUT DOWN) A/B selector switch DIN rail slider Convection Clearance above/below Figure 2-1 Design (example: 6EP3334-8SB00-0AY0) SITOP PSU8200 1ph Manual, 08.2016, C98130-A7633-A1-5-7629 9 Description, device design, dimension drawing 2.1 Device description SITOP PSU8200 20 A 1ph is a primary-clocked power supply for connection to a 1-phase or 2-phase AC line supply or a DC supply. An electronically regulated DC voltage that can be set via a potentiometer is available at the output of the device. The output of the device is isolated, no-load proof and short-circuit proof. The LEDs indicate the operating state. The operating state of the device can be processed via the signaling contact. AC/DC input DC output 24 - 28.8 V potentiometer Signaling contact (13, 14) Indicator lights (24 V O.K., OVERLOAD, SHUT DOWN) A/B selector switch DIN rail slider Convection Clearance above/below Figure 2-2 Design 6EP1336-3BA10 SITOP PSU8200 1ph 10 Manual, 08.2016, C98130-A7633-A1-5-7629 Description, device design, dimension drawing 2.1 Device description SITOP PSU8200 40 A 1ph is a primary-clocked power supply for connection to a 1-phase or 2-phase AC line supply. An electronically regulated DC voltage that can be set via a potentiometer is available at the output of the device. The output of the device is isolated, no-load proof and short-circuit proof. The LEDs indicate the operating state. The operating state of the device can be processed via the signaling contact. AC input DC output 24 - 28 V potentiometer Signaling contacts (13, 14) Indicator lights (24 V O.K., OVERLOAD, SHUT DOWN) Selector switch Mounting rail slider Convection Clearance above/below Figure 2-3 Design of the 6EP3337-8SB00-0AY0 SITOP PSU8200 1ph Manual, 08.2016, C98130-A7633-A1-5-7629 11 Description, device design, dimension drawing 2.2 Connections and terminal designation 2.2 Connections and terminal designation The line input terminals can be used to establish the connection to the supply voltage. The output terminals are used to connect to the loads to be supplied (see also Section Installation (Page 39)). Connections and terminal designations for 6EP3333-8SB00-0AY0 and 6EP3334-8SB00-0AY0 Line input L1, N, PE One screw terminal each output "+" 2 screw terminals output "-" 2 screw terminals signaling contact 13, 14 One screw terminal each remote contact 15, 16 One screw terminal each *1) Do not subject the end stop to higher loads Figure 2-4 Terminal data for 6EP3333-8SB00-0AY0 and 6EP3334-8SB00-0AY0 SITOP PSU8200 1ph 12 Manual, 08.2016, C98130-A7633-A1-5-7629 Description, device design, dimension drawing 2.2 Connections and terminal designation Connections and terminal designations for the 6EP1336-3BA10 Line input L1, N(L2),PE One screw terminal each output "+" 2 screw terminals output "-" 2 screw terminals signaling contact 13, 14 One screw terminal each *1) Do not subject the end stop to higher loads Figure 2-5 Terminal data for 6EP1336-3BA10 Connections and terminal designations for 6EP3337-8SB00-0AY0 Line input L1, N(L2),PE One screw terminal each output "+" 2 screw terminals output "-" 2 screw terminals signaling contact 13, 14 One screw terminal each *1) Do not subject the end stop to higher loads Figure 2-6 Terminal data for 6EP3337-8SB00-0AY0 SITOP PSU8200 1ph Manual, 08.2016, C98130-A7633-A1-5-7629 13 Description, device design, dimension drawing 2.3 Potentiometer 2.3 Potentiometer The potentiometer on the front of the device is used to adjust the output voltage. The output voltage is set to 24 V in the factory, and can be adjusted in the range 24 - 28.8 V (for 6EP3337-8SB00-0AY0, 24 - 28 V); for example, to compensate voltage drops across long supply lines to the connected load. Figure 2-7 Potentiometer (example: 6EP3334-8SB00-0AY0) NOTICE Thermal overload possible When adjusting the output voltage to > 24 V, the output current must be derated by 4 %/V, or the permissible ambient temperature must be taken into account with 3 C/V. Note It is only permissible to use an insulated screwdriver when actuating the potentiometer. For information on actuating the potentiometer (screwdriver, torque), see Figure 2-5 Terminal data for 6EP1336-3BA10 (Page 13), Figure 2-6 Terminal data for 6EP3337-8SB000AY0 (Page 13), Figure 2-4 Terminal data for 6EP3333-8SB00-0AY0 and 6EP3334-8SB000AY0 (Page 12) SITOP PSU8200 1ph 14 Manual, 08.2016, C98130-A7633-A1-5-7629 Description, device design, dimension drawing 2.4 Status displays and signaling 2.4 Status displays and signaling 6EP3333-8SB00-0AY0 (24 V/5 A) 6EP3334-8SB00-0AY0 (24 V/10 A) Operating display Green LED for "24 V O.K." Yellow LED for overload in "constant current" mode Red LED for latching shutdown in "shut down" mode Signaling contact (13, 14) Figure 2-8 Relay contact (NO contact, contact rating 30 V AC / 0.5 A, 60 V DC / 0.3 A, 30 V DC / 1 A) for "24 V O.K." Operating display and signaling contact for 6EP3333-8SB00-0AY0 and 6EP33348SB00-0AY0 Signaling 6EP3333-8SB00-0AY0 (24 V/5 A) 6EP3334-8SB00-0AY0 (24 V/10 A) Green LED lit Normal operation, output voltage > 20 V 0.5 V Signaling contact, contact 13 - 14 closed LED off No supply voltage Signaling contact, contact 13 - 14 opened (quiescent position) Yellow LED lit Signaling contact, contact 13 - 14 opened (quiescent position) Red LED lit Overload, output voltage < 20 V 0.5 V (only in the "constant current" mode) Latching shut down or remote OFF Signaling contact, contact 13 - 14 opened (quiescent position) SITOP PSU8200 1ph Manual, 08.2016, C98130-A7633-A1-5-7629 15 Description, device design, dimension drawing 2.4 Status displays and signaling 6EP1336-3BA10 (24 V/20 A) Operating display Green LED lit for "24 V O.K." Yellow LED lit for overload condition (Uout < 20 V 0.5 V) Red LED lit for latching shutdown as a result of overload (only for selector switch B in the "ON" position) Signaling contact Figure 2-9 Relay contact (NO contact, contact rating 30 V AC / 0.5 A; 60 V DC / 0.3 A; 30 V DC / 1 A) for "24 V O.K." Operating display and signaling contact for 6EP1336-3BA10 Signaling 6EP1336-3BA10 (24 V/20 A) LED green (5.1) off No supply voltage Signaling contact, contact 13 - 14 opened (quiescent position) Green LED (5.1) lit Signaling contact, contact 13 - 14 closed Normal operation, output voltage > 20 V 0.5 V Yellow LED (5.2) lit Overload (Uout < 20 V 0.5 V) Signaling contact, contact 13 - 14 opened (quiescent position) Red LED (5.3) lit Latching shutdown due to overload Signaling contact, contact 13 - 14 opened (quiescent position) SITOP PSU8200 1ph 16 Manual, 08.2016, C98130-A7633-A1-5-7629 Description, device design, dimension drawing 2.4 Status displays and signaling 6EP3337-8SB00-0AY0 (24 V/40 A) Operating display Green LED lit for "24 V O.K." Yellow LED lit for overload condition (Uout < 20 V 0.5 V) Red LED lit for latching shutdown as a result of overload (only for selector switch B in the "ON" position) Signaling contact Figure 2-10 Relay contact (NO contact, contact rating 30 V AC / 0.5 A; 60 V DC / 0.3 A; 30 V DC / 1 A) for "24 V O.K." Operating display and signaling contact for 6EP3337-8SB00-0AY0 Signaling 6EP3337-8SB00-0AY0 (24 V/40 A) Green LED off Supply voltage missing Signaling contact, contact 13 - 14 opened (quiescent position) Green LED lit Signaling contact, contact 13 - 14 closed Normal operation, output voltage > 20 V 0.5 V Yellow LED lit Overload (Uout < 20 V 0.5 V) Signaling contact, contact 13 - 14 opened (quiescent position) Red LED lit Latching shutdown due to overload Signaling contact, contact 13 - 14 opened (quiescent position) SITOP PSU8200 1ph Manual, 08.2016, C98130-A7633-A1-5-7629 17 Description, device design, dimension drawing 2.5 Change-over switch 2.5 Change-over switch Figure 2-11 Selector switch The two switches A and B are used to influence the output characteristic: SITOP PSU8200 1ph 18 Manual, 08.2016, C98130-A7633-A1-5-7629 Description, device design, dimension drawing 2.5 Change-over switch Switch ON OFF A influences the output characteristic in the load range Parallel operation: "Soft" characteristic curve (see, e.g. Figure 6-8 Output characteristic curve 6EP3333-8SB00-0AY0 parallel operation (Page 50)) for operating two or more devices in parallel: The output voltage falls with increasing output current (namely, also for the overcurrent pulse!). This means that for full output current the highest output voltage can normally no longer be attained. Single operation: B influences the output characteristic in the overload range Latching shutdown: If the output current rises above the rated value and above the current limit, the device reduces the output voltage (see, e.g. Figure 6-12 Output characteristic curve 6EP3333-8SB00-0AY0 latching shutdown (Page 51)). If the output voltage falls below 20 V, the device shuts down latching, the red LED lights up. This limit voltage of 20 V is independent of the set output voltage. The "Short-term overload current" feature is not available in this operating mode. 6EP3333-8SB00-0AY0 and 6EP3334-8SB00-0AY0 are reset using power supply OFF for a minimum of 60 s or remote OFF and ON at the remote contact. 6EP1336-3BA10 is reset by switching off the power supply for longer than 5 s. For 6EP3337-8SB00-0AY0, for an overload condition, the device is shutdown. A reset is initiated by switching off the line supply and then switching it on again after the red LED goes the dark. In order to also be able to charge large capacitances in this operating mode at the output, non-latching shutdown is performed during the first 10 seconds after switching on the power or after a remote on. During these first 10 s, the device responds for overload as if the switch is OFF. Constant current: Delivery state "Hard" characteristic curve (see, e.g. Figure 6-4 Output characteristic curve 6EP3333-8SB00-0AY0 stand-alone operation (Page 48)) for normal operation (single operation): The output voltage is independent of the output current. Delivery state If the output current rises above the rated value and above the current limit, the device reduces the output voltage. The yellow LED lights up if the output voltage falls below 20 V. Delivery condition: A-OFF; B-OFF Note Selector switches may only be activated when the device is switched off. SITOP PSU8200 1ph Manual, 08.2016, C98130-A7633-A1-5-7629 19 Description, device design, dimension drawing 2.6 Remote contact 2.6 Remote contact 6EP3333-8SB00-0AY0 (24 V/5 A) 6EP3334-8SB00-0AY0 (24 V/10 A) Remote contact (15, 16) Figure 2-12 Non-isolated input for remote ON/OFF switching of the power supply. Function: The device is remotely switched off when contacts 15 - 16 are short-circuited (R < 8 k). If the power supply is shut down and latched in the "latching shutdown" mode as a result of an overload, then it can be restarted using remote OFF followed by remote ON. Remote contact for 6EP3333-8SB00-0AY0 and 6EP3334-8SB00-0AY0 SITOP PSU8200 1ph 20 Manual, 08.2016, C98130-A7633-A1-5-7629 Description, device design, dimension drawing 2.7 Block diagram 2.7 Figure 2-13 Block diagram Block diagram for 6EP3333-8SB00-0AY0 and 6EP3334-8SB00-0AY0 SITOP PSU8200 1ph Manual, 08.2016, C98130-A7633-A1-5-7629 21 Description, device design, dimension drawing 2.7 Block diagram Figure 2-14 Block diagram for 6EP1336-3BA10 SITOP PSU8200 1ph 22 Manual, 08.2016, C98130-A7633-A1-5-7629 Description, device design, dimension drawing 2.7 Block diagram Figure 2-15 Block diagram for 6EP3337-8SB00-0AY0 SITOP PSU8200 1ph Manual, 08.2016, C98130-A7633-A1-5-7629 23 Description, device design, dimension drawing 2.8 Dimensions and weight 2.8 Dimensions and weight Figure 2-16 Dimension drawing 6EP3333-8SB00-0AY0 Figure 2-17 Dimension drawing 6EP3334-8SB00-0AY0 SITOP PSU8200 1ph 24 Manual, 08.2016, C98130-A7633-A1-5-7629 Description, device design, dimension drawing 2.8 Dimensions and weight Figure 2-18 Dimension drawing for 6EP1336-3BA10 Figure 2-19 Dimension drawing for 6EP3337-8SB00-0AY0 6EP3333-8SB00-0AY0 (24 V/5 A) 6EP3334-8SB00-0AY0 (24 V/10 A) Dimensions (W x H x D) in mm 45 x 125 x 125 55 x 125 x 125 Weight approx. 0.8 kg approx. 1.0 kg SITOP PSU8200 1ph Manual, 08.2016, C98130-A7633-A1-5-7629 25 Description, device design, dimension drawing 2.8 Dimensions and weight 6EP1336-3BA10 (24 V/20 A) 6EP3337-8SB00-0AY0 (24 V/40 A) Dimensions (W x H x D) in mm 90 x 125 x 120 145 x 145 x 150 Weight approx. 1.2 kg approx. 3 kg SITOP PSU8200 1ph 26 Manual, 08.2016, C98130-A7633-A1-5-7629 Mounting/removal 3 WARNING Installing the device in a housing or a control cabinet The SITOP PSU8200 1ph power supply is a built-in device. It must be installed in a housing or control cabinet, to which only qualified personnel have access. The device can be mounted in a control cabinet on standard mounting rails. Mounting To mount the device, position it with the mounting rail guide at the upper edge of the standard mounting rail and press down to lock it into place. If it is too difficult to snap them into place, press the slider at the same time, as described under "Removal". Removal To remove, pull up the slider using a screwdriver and disengage the device at the bottom edge of the standard mounting rail. Then you can remove the device from the upper edge of the standard mounting rail. Figure 3-1 Mounting/removal (example): 6EP3334-8SB00-0AY0) SITOP PSU8200 1ph Manual, 08.2016, C98130-A7633-A1-5-7629 27 Mounting/removal WARNING Use in hazardous zones If the devices are to be used in hazardous zones (II 3G Ex nA nC IIC T3 Gc or II 3G Ex nA nC IIC T4 Gc), they must be installed in a distribution box with degree of protection IP54 or higher. This distribution box must comply with the requirements of EN 60079-15. SITOP PSU8200 1ph 28 Manual, 08.2016, C98130-A7633-A1-5-7629 Mounting position, mounting clearances 4.1 4 Standard mounting position The device is mounted on standard mounting rails according to EN 60715. The device must be mounted vertically in such a way that the input terminals and the output terminals are at the bottom to ensure correct cooling. A clearance of at least 50 mm should be maintained above and below the device (maximum depth of the cable duct, 50 mm). No space is required at the side. Output current as a function of the ambient temperature and mounting height Figure 4-1 6EP3333-8SB00-0AY0 standard mounting position Figure 4-2 6EP3334-8SB00-0AY0 standard mounting position SITOP PSU8200 1ph Manual, 08.2016, C98130-A7633-A1-5-7629 29 Mounting position, mounting clearances 4.1 Standard mounting position Figure 4-3 6EP1336-3BA10 standard mounting position Figure 4-4 6EP3337-8SB00-0AY0 standard mounting position Figure 4-5 Mounting height derating For details, see Ambient conditions (Page 63) SITOP PSU8200 1ph 30 Manual, 08.2016, C98130-A7633-A1-5-7629 Mounting position, mounting clearances 4.2 Other mounting positions 4.2 Other mounting positions For mounting positions that deviate from the standard mounting position, derating factors (reduction of the output power or the permissible ambient temperature) must be observed in accordance with the following diagrams. Note In the case of mounting positions that deviate from the standard mounting position, reduced mechanical resistance of the devices against vibration and shock must be expected. Particularly when installing on a vertically fastened standard mounting rail, additional measures may be required, e.g. to prevent the device from slipping on the standard mounting rail. 4.2.1 6EP3333-8SB00-0AY0 Figure 4-6 6EP3333-8SB00-0AY0 mounting position (1) Figure 4-7 6EP3333-8SB00-0AY0 mounting position (2) SITOP PSU8200 1ph Manual, 08.2016, C98130-A7633-A1-5-7629 31 Mounting position, mounting clearances 4.2 Other mounting positions Figure 4-8 6EP3333-8SB00-0AY0 mounting position (3) Figure 4-9 6EP3333-8SB00-0AY0 mounting position (4) Figure 4-10 6EP3333-8SB00-0AY0 mounting position (5) SITOP PSU8200 1ph 32 Manual, 08.2016, C98130-A7633-A1-5-7629 Mounting position, mounting clearances 4.2 Other mounting positions 4.2.2 6EP3334-8SB00-0AY0 Figure 4-11 6EP3334-8SB00-0AY0 mounting position (1) Figure 4-12 6EP3334-8SB00-0AY0 mounting position (2) Figure 4-13 6EP3334-8SB00-0AY0 mounting position (3) SITOP PSU8200 1ph Manual, 08.2016, C98130-A7633-A1-5-7629 33 Mounting position, mounting clearances 4.2 Other mounting positions Figure 4-14 6EP3334-8SB00-0AY0 mounting position (4) Figure 4-15 6EP3334-8SB00-0AY0 mounting position (5) SITOP PSU8200 1ph 34 Manual, 08.2016, C98130-A7633-A1-5-7629 Mounting position, mounting clearances 4.2 Other mounting positions 4.2.3 6EP1336-3BA10 Figure 4-16 6EP1336-3BA10 mounting position (1) Figure 4-17 6EP1336-3BA10 mounting position (2) Figure 4-18 6EP1336-3BA10 mounting position (3) SITOP PSU8200 1ph Manual, 08.2016, C98130-A7633-A1-5-7629 35 Mounting position, mounting clearances 4.2 Other mounting positions Figure 4-19 6EP1336-3BA10 mounting position (4) Figure 4-20 6EP1336-3BA10 mounting position (5) SITOP PSU8200 1ph 36 Manual, 08.2016, C98130-A7633-A1-5-7629 Mounting position, mounting clearances 4.2 Other mounting positions 4.2.4 6EP3337-8SB00-0AY0 Figure 4-21 6EP3337-8SB00-0AY0 mounting position (1) Figure 4-22 6EP3337-8SB00-0AY0 mounting position (2) Figure 4-23 6EP3337-8SB00-0AY0 mounting position (3) SITOP PSU8200 1ph Manual, 08.2016, C98130-A7633-A1-5-7629 37 Mounting position, mounting clearances 4.2 Other mounting positions Figure 4-24 6EP3337-8SB00-0AY0 mounting position (4) Figure 4-25 6EP3337-8SB00-0AY0 mounting position (5) SITOP PSU8200 1ph 38 Manual, 08.2016, C98130-A7633-A1-5-7629 5 Installation WARNING Hazard due to electric shock Before installation or maintenance work can begin, the system's main switch must be switched off and measures taken to prevent it being switched on again. If this instruction is not observed, touching live parts can result in death or serious injury. 5.1 Line-side connection The SITOP PSU8200 1ph (6EP3333-8SB00-0AY0 and 6EP3334-8SB00-0AY0) power supply is designed for connection to a 1-phase AC line supply with a rated voltage of 120/230 V AC, 50 - 60 Hz. Figure 5-1 Line connection for 6EP3333-8SB00-0AY0 and 6EP3334-8SB00-0AY0 The SITOP PSU8200 1ph (6EP1336-3BA10) power supplies are designed to be connected to a 1-phase AC line voltage or to 2 line conductors of three-phase line supplies (TN, TT or IT system according to VDE 0100 T 300/IEC 364-3) with a rated voltage of 120 - 230 V, 50 - 60 Hz or a DC voltage. SITOP PSU8200 1ph Manual, 08.2016, C98130-A7633-A1-5-7629 39 Installation 5.1 Line-side connection Figure 5-2 Line connection for 6EP1336-3BA10 The SITOP PSU8200 1ph (6EP3337-8SB00-0AY0) power supplies are designed to be connected to a 1-phase AC line voltage or to 2 line conductors of three-phase line supplies (TN, TT or IT system according to VDE 0100 T 300/IEC 364-3) with a rated voltage of 120/230 V, 50 - 60 Hz. The line supply is connected using terminals L1, N and PE (see Figure 5-1 Line connection for 6EP3333-8SB00-0AY0 and 6EP3334-8SB00-0AY0 (Page 39)) or L1, N(L2) and PE (Figure 5-2 Line connection for 6EP1336-3BA10 (Page 40)) and must be implemented according to IEC 60364 and EN 50178 . A protective device (miniature circuit-breaker or circuit-breaker) and a disconnection unit to switch off the power supply must be provided. A ground-fault circuit interrupter is not permissible against indirect contact as the only protective measure. This applies for the complete line supply protected by the ground-fault circuit interrupter. Protection SITOP PSU8200 1ph Line-side protection 6EP3333-8SB00-0AY0 (24 V/5 A) Recommended: Miniature circuit breaker (IEC 898), characteristic C, 6 A 6EP3334-8SB00-0AY0 (24 V/10 A) Recommended: Miniature circuit breaker (IEC 898), characteristic C, 10 A 6EP1336-3BA10 (24 V/20 A) Recommended: Miniature circuit breaker for single-phase operation: 10 A, characteristic C; required for two-phase operation: Miniature circuit breaker two-pole coupled or circuit breaker for the US according to UL489, DIVQ: 3RV2711-1HD10 (120 V) or 3RV27111ED10 (230 V) 6EP3337-8SB00-0AY0 (24 V/40 A) Recommended: Miniature circuit breaker for single-phase operation: 16 A, characteristic C; required for two-phase operation: Miniature circuit breaker two-pole coupled or circuit breaker for the US according to UL489, DIVQ: 3RV2421-4BA10 (120 V) or 3RV24111JA10 (230 V) The protective conductor of the line supply must be connected at the PE terminal. Other country-specific regulations may have to be observed when installing the device. SITOP PSU8200 1ph 40 Manual, 08.2016, C98130-A7633-A1-5-7629 Installation 5.2 Output-side connection 5.2 Output-side connection At its output, the SITOP PSU8200 1ph power supply provides an isolated (= non-grounded) SELV output voltage (Safety Extra Low Voltage). The output of the power supply is no-load, overload, and short-circuit proof. If an overload occurs, the electronic current limiting function limits the output current to a maximum value (see Section Technical data (Page 43)). Figure 5-3 Output connection (example: 6EP3334-8SB00-0AY0) The output voltage is connected via the + and - terminals at the output of the power supply (see Figure 5-3 Output connection (example: 6EP3334-8SB00-0AY0) (Page 41)). Ensure that the output cables are dimensioned correctly for the maximum output current rms value and fused accordingly. Note If the safety concept of the plant or system specifies that the DC output circuit should be grounded (PELV, Protected Extra Low Voltage), then it is permissible that the output voltage of the SITOP power supply is grounded. In this case, ideally, the grounding at the output should be directly connected from terminal "-" of the power supply to a suitable connection point of the protective conductor system (PE) of the plant or system. SITOP PSU8200 1ph Manual, 08.2016, C98130-A7633-A1-5-7629 41 Installation 5.2 Output-side connection SITOP PSU8200 1ph 42 Manual, 08.2016, C98130-A7633-A1-5-7629 6 Technical data Note Technical data apply for a rated input voltage, rated load and 25 C ambient temperature if nothing else is specified. 6.1 Input 6EP3333-8SB00-0AY0 (24 V/5 A) 6EP3334-8SB00-0AY0 (24 V/10 A) Input 1-phase, AC 1-phase, AC Rated voltage Uin rated 120/230 V 120/230 V Rated voltage Uin rated for DC - - Voltage range for AC 85 - 132/170 - 264 V 85 - 132/170 - 264 V Automatic voltage switchover Automatic voltage switchover - - Wide-range input No No Overvoltage strength - - Line failure buffering at Iout rated, min at 230 V 35 ms 35 ms Rated line frequency 50 - 60 Hz 50 - 60 Hz Line frequency range 47 - 63 Hz 47 - 63 Hz Input current / at rated value of input voltage 120 V 2.1 A 4A Input current / at rated value of input voltage 230 V 1.2 A 1.9 A Inrush current limiting (25 C), max. 10 A 10 A * Remark Voltage range for DC * I2t, Remark max 0.2 A2s 0.3 A2s Integrated input fuse Fuse T 3.15 A Fuse T 6.3 A Protection in the line feeder cable (IEC 898) Recommended: Circuit breaker, characteristic C, 6 A Recommended: Miniature circuit breaker characteristic C, 10 A SITOP PSU8200 1ph Manual, 08.2016, C98130-A7633-A1-5-7629 43 Technical data 6.1 Input 6EP1336-3BA10 (24 V/20 A) 6EP3337-8SB00-0AY0 (24 V/40 A) Input 1 and 2-phase AC or DC 1 and 2-phase AC Rated voltage Uin rated 120 - 230 V 120/230 V Rated voltage Uin rated for DC 110 - 220 V - 85 - 275 V 85 - 132/170 - 264 V Voltage range for AC * Remark Voltage range for DC * Remark Temperature derating for Uin < 100 V for 50 C necessary 88 - 350 V - Temperature derating for Uin < 100 V for 50 C necessary Wide-range input Yes No Overvoltage strength 2.3 x Uin rated, 1.3 ms - Line failure buffering at Iout rated, min at 230 V 20 ms 15 ms Rated line frequency 50 - 60 Hz 50 - 60 Hz Line frequency range 45 - 65 Hz 45 - 65 Hz Input current / at rated value of input voltage 120 V 4.6 A 15 A Input current / at rated value of input voltage 230 V 2.5 A 9A Inrush current limiting (25 C), max. 20 A 50 A I2t, max 5 A2s 30 A2s Integrated input fuse Fuse T 10 A Fuse T 16 A Protection in the line feeder cable (IEC 898) Recommended miniature circuit breaker for single-phase operation: 10 A, characteristic C; required for two-phase operation: Miniature circuit breaker two-pole coupled or circuit breaker for the US according to UL489, DIVQ: 3RV2711-1HD10 (120 V) or 3RV2711-1ED10 (230 V) Recommended miniature circuit breaker for single-phase operation: 16 A, characteristic C; required for two-phase operation: Miniature circuit breaker two-pole coupled or circuit breaker for the US according to UL489, DIVQ: 3RV2421-4BA10 (120 V) or 3RV2411-1JA10 (230 V) Power consumption (active power) at full load 515 W 1055 W SITOP PSU8200 1ph 44 Manual, 08.2016, C98130-A7633-A1-5-7629 Technical data 6.2 Output Figure 6-1 6.2 Power failure buffering Output 6EP3333-8SB00-0AY0 (24 V/5 A) 6EP3334-8SB00-0AY0 (24 V/10 A) Output Regulated and isolated DC voltage Regulated and isolated DC voltage Rated voltage Uout rated DC 24 V 24 V Total tolerance, static 3% 3% Static line regulation, approx. 0.03 % 0.05 % Static load regulation, approx. 0.2 % 0.3 % Residual ripple in the load range 50 mV 50 mV Spikes peak-peak, max. (bandwidth, approx. 20 MHz) 200 mV 200 mV Adjustment range 24 - 28.8 V 24 - 28.8 V Product function / output voltage can be adjusted Yes Yes Output voltage setting Via potentiometer Via potentiometer Max. 120 W Max. 240 W Operating display Green LED for "24 V O.K." Green LED for "24 V O.K." Signaling Relay contact (NO contact, contact Relay contact (NO contact, contact rating 30 V AC / 0.5 A; 60 V DC / 0.3 A; rating 30 V AC / 0.5 A; 60 V DC / 0.3 A; 30 V DC / 1 A) for "24 V O.K." 30 V DC / 1 A) for "24 V O.K." Response when switching on/off Uout overshoots by approximately 3 % Uout overshoots by approximately 3 % Starting delay, max. 1s 1s Voltage rise, typ. 30 ms 70 ms Voltage rise time of the output voltage, maximum 500 ms 500 ms Peak-peak, max. * Remark SITOP PSU8200 1ph Manual, 08.2016, C98130-A7633-A1-5-7629 45 Technical data 6.2 Output 6EP3333-8SB00-0AY0 (24 V/5 A) 6EP3334-8SB00-0AY0 (24 V/10 A) Rated current Iout rated 5A 10 A Current range 0-5A 0 - 10 A for Uin < 100 V/< 200 V: 80 % Iout rated 60 ... 70 C derating approx. 2 % Iout rated/K; for Uin < 100 V/< 200 V: 80 % Iout rated Output active power / typical 120 W 240 W Constant overload current for a short circuit when powering up, typical 6A 12 A Short-time overload current for a short circuit during operation, typical 15 A 30 A Duration of the overload capability, overcurrent / for a short circuit while powering up 150 ms 150 ms Duration of the overload capability, overcurrent / for a short circuit while in operation 25 ms 25 ms per 1 min per 1 min Yes Yes Switchable characteristic Switchable characteristic * * Remark Remark Can be connected in parallel to increase the power rating * Remark Number of devices that can be con2 nected in parallel to increase the power rating, units 2 Output characteristic See Figure 6-4 Output characteristic curve 6EP3333-8SB00-0AY0 standalone operation (Page 48) See Figure 6-5 Output characteristic curve 6EP3334-8SB00-0AY0 standalone operation (Page 49) 6EP1336-3BA10 (24 V/20 A) 6EP3337-8SB00-0AY0 (24 V/40 A) Output Regulated and isolated DC voltage Regulated and isolated DC voltage Rated voltage Uout rated DC 24 V 24 V Total tolerance, static 3% 3% Static line regulation, approx. 0.1 % 0.1 % Static load regulation, approx. 0.3 % 0.3 % Residual ripple in the load range 100 mV 100 mV Spikes peak-peak, max. (bandwidth, approx. 20 MHz) 200 mV 240 mV Adjustment range 24 - 28.8 V 24 - 28 V Product function / output voltage can be adjusted Yes Yes Peak-peak, max. SITOP PSU8200 1ph 46 Manual, 08.2016, C98130-A7633-A1-5-7629 Technical data 6.2 Output 6EP1336-3BA10 (24 V/20 A) 6EP3337-8SB00-0AY0 (24 V/40 A) Via potentiometer Via potentiometer Max. 480 W Max. 960 W Operating display Green LED for "24 V O.K." Green LED for "24 V O.K." Signaling Relay contact (NO contact, contact Relay contact (NO contact, contact rating 30 V AC / 0.5 A; 60 V DC / 0.3 A; rating 30 V AC / 0.5 A; 60 V DC / 0.3 A; 30 V DC / 1 A) for "24 V O.K." 30 V DC / 1 A) for "24 V O.K." Response when switching on/off No overshoot of Uout (Soft-Start) No overshoot of Uout (Soft-Start) Starting delay, max. 0.25 s 0.5 s Voltage rise, typ. 50 ms 50 ms Voltage rise time / of the output voltage / maximum 150 ms 150 ms Rated current Iout rated 20 A 40 A Output voltage setting * Remark 0 - 20 A 0 - 40 A 60 ... 70 C derating:3 % Iout rated/K 60 ... 70 C derating 1 % Iout rated/K; derating for Uin < 120 V: see Figure 6-3 Output derating for 6EP3337-8SB000AY0 (Page 48) Output active power / typical 480 W 960 W Constant overload current/for a short circuit when powering up/typical 30 A - Short-time overload current / for a short 60 A circuit in operation / typical - Duration of the overload capability, overcurrent / for a short circuit while powering up 150 ms - Duration of the overload capability, overcurrent / for a short circuit while in operation 25 ms - Current range * * Remark Remark Can be connected in parallel to increase the power rating * Remark per 1 min Yes Yes Switchable characteristic Switchable characteristic Number of devices that can be con2 nected in parallel to increase the power rating, units 2 Power Boost in operation: 60 A for 25 ms 120 A for 25 ms Extra Power in operation 30 A for 5 s (pro min) 60 A for 5 s (pro min) Output characteristic See Figure 6-6 6EP1336-3BA10 single operation output characteristic (Page 49) See Figure 6-7 6EP3337-8SB00-0AY0 single operation output characteristic (Page 49) SITOP PSU8200 1ph Manual, 08.2016, C98130-A7633-A1-5-7629 47 Technical data 6.2 Output Figure 6-2 Starting delay/voltage rise Figure 6-3 Output derating for 6EP3337-8SB00-0AY0 Figure 6-4 Output characteristic curve 6EP3333-8SB00-0AY0 stand-alone operation SITOP PSU8200 1ph 48 Manual, 08.2016, C98130-A7633-A1-5-7629 Technical data 6.2 Output Figure 6-5 Output characteristic curve 6EP3334-8SB00-0AY0 stand-alone operation Figure 6-6 6EP1336-3BA10 single operation output characteristic Figure 6-7 6EP3337-8SB00-0AY0 single operation output characteristic The device supplies a constant output voltage until the current limit is reached. In the event of an overload, the output current and the output voltage are reduced. SITOP PSU8200 1ph Manual, 08.2016, C98130-A7633-A1-5-7629 49 Technical data 6.2 Output Selector switch A on (parallel operation): The output voltage falls with increasing output current. Figure 6-8 Output characteristic curve 6EP3333-8SB00-0AY0 parallel operation Figure 6-9 Output characteristic curve 6EP3334-8SB00-0AY0 parallel operation Figure 6-10 6EP1336-3BA10 parallel operation output characteristic SITOP PSU8200 1ph 50 Manual, 08.2016, C98130-A7633-A1-5-7629 Technical data 6.2 Output Figure 6-11 6EP3337-8SB00-0AY0 parallel operation output characteristic Selector switch B on (latching shutdown): The device is shutdown if the overload lasts longer than 100 ms. 6EP3333-8SB00-0AY0 and 6EP3334-8SB00-0AY0 are reset using power supply OFF for a minimum of 60 s or remote OFF and ON at the remote contact. 6EP1336-3BA10 is reset using power supply OFF for a minimum of 5 s or remote OFF and ON at the remote contact. 6EP3337-8SB00-0AY0 is reset using power supply OFF and ON again after the red LED has gone dark. Figure 6-12 Output characteristic curve 6EP3333-8SB00-0AY0 latching shutdown Figure 6-13 Output characteristic curve 6EP3334-8SB00-0AY0 latching shutdown SITOP PSU8200 1ph Manual, 08.2016, C98130-A7633-A1-5-7629 51 Technical data 6.2 Output Figure 6-14 6EP1336-3BA10 latching shutdown output characteristic Figure 6-15 6EP3337-8SB00-0AY0 latching shutdown output characteristic SITOP PSU8200 1ph 52 Manual, 08.2016, C98130-A7633-A1-5-7629 Technical data 6.3 Efficiency 6.3 Efficiency 6EP3333-8SB00-0AY0 (24 V/5 A) 6EP3334-8SB00-0AY0 (24 V/10 A) Efficiency at Uout rated, Iout rated, approx. 93 % 94 % Power loss at Uout rated, Iout rated, approx. 9W 18 W No-load operation power loss, approx. 1.5 W 1.5 W Power loss in the "latching shutdown" state 1.2 W 1.2 W 6EP1336-3BA10 (24 V/20 A) 6EP3337-8SB00-0AY0 (24 V/40 A) Efficiency at Uout rated, Iout rated, approx. 93 % 92 % Power loss at Uout rated, Iout rated, approx. 42 W 83 W No-load operation power loss, approx. 10 W 7W Power loss in the "latching shutdown" state 6.5 W 3W Figure 6-16 Power efficiency 6EP3333-8SB00-0AY0 SITOP PSU8200 1ph Manual, 08.2016, C98130-A7633-A1-5-7629 53 Technical data 6.3 Efficiency Figure 6-17 Power efficiency 6EP3334-8SB00-0AY0 Figure 6-18 Efficiency 6EP1336-3BA10 SITOP PSU8200 1ph 54 Manual, 08.2016, C98130-A7633-A1-5-7629 Technical data 6.4 Closed-loop control Figure 6-19 6.4 Efficiency 6EP3337-8SB00-0AY0 Closed-loop control 6EP3333-8SB00-0AY0 (24 V/5 A) 6EP3334-8SB00-0AY0 (24 V/10 A) 6EP1336-3BA10 (24 V/20 A) 6EP3337-8SB00-0AY0 (24 V/40 A) Dyn. line regulation (Uin rated 15 %), max. 0.1 % 0.1 % 1% 1% Dyn. load regulation (Iout: 50/100/50 %), Uout typ. 2% 4% 1% 1% Load step regulation time 50 to 100%, typ. 250 s 250 s 1 ms 1 ms Load step regulation time 100 to 50%, typ. 500 s 500 s 1 ms 1 ms Regulation time / maximum 1 ms 1 ms 5 ms 5 ms Dyn. load regulation (Iout: 10/90/10 %), Uout typ. - - 2% 2% Load step regulation time 10 to 90 %, typ. - - 1 ms 1 ms Load step regulation time 90 to 10 %, typ. - - 1 ms 1 ms SITOP PSU8200 1ph Manual, 08.2016, C98130-A7633-A1-5-7629 55 Technical data 6.5 Protection and monitoring 6.5 Protection and monitoring 6EP3333-8SB00-0AY0 (24 V/5 A) 6EP3334-8SB00-0AY0 (24 V/10 A) Output overvoltage protection < 33 V < 33 V Current limitation, typ. 6A 12 A Property of the output / short-circuit proof Yes Yes Short-circuit protection Optional constant current characteristic curve or latching shutdown Optional constant current characteristic curve or latching shutdown Continuous short-circuit current / rms value / typical 3.5 A 7A Overload capability 150 % Iout rated up to 5 s/min Overload capability 150 % Iout rated up to 5 s/min * Remark Overload/short-circuit indicator Yellow LED for "overload", red LED for "latching shutdown" 6EP1336-3BA10 (24 V/20 A) 6EP3337-8SB00-0AY0 (24 V/40 A) Output overvoltage protection < 33 V < 32 V Current limitation, typ. 21.5 A 41 A Property of the output / short-circuit proof Yes Yes Short-circuit protection Optional constant current characteristic approx. 23 A or latching shutdown Optional constant current characteristic approx. 41 A or latching shutdown Continuous short-circuit current / rms value / typical 23 A 41 A Overload capability 150 % Iout rated up to 5 s/min Overload capability 150 % Iout rated up to 5 s/min Yellow LED for "overload", red LED for "latching shutdown" Yellow LED for "overload", red LED for "latching shutdown" * Remark Overload / short-circuit indicator 6.6 MTBF 6EP3333-8SB00-0AY0 (24 V/5 A) 6EP1336-3BA10 (24 V/20 A) 6EP3333-8SB00-0AY0 (24 V/40 A) 6EP3334-8SB00-0AY0 (24 V/10 A) Mean Time Between Failures SN29500: > 1200000 hours at 40 C, rated load, 24-hour operation SN29500: > 620000 hours at SN29500: > 800000 hours at 40 C, rated load, 24-hour 40 C, rated load, 24-hour operation operation SITOP PSU8200 1ph 56 Manual, 08.2016, C98130-A7633-A1-5-7629 Technical data 6.7 Mechanical system 6.7 Mechanical system 6EP3333-8SB00-0AY0 (24 V/5 A) 6EP3334-8SB00-0AY0 (24 V/10 A) Connection system Screw-type terminal Screw-type terminal Connections/line input L1, N, PE: 1 screw terminal each for 0.2 - 2.5 mm solid (finely stranded) L1, N, PE: 1 screw terminal each for 0.2 - 2.5 mm solid (finely stranded) Connections/output +, -: 2 screw terminals each for 0.2 - 2.5 mm solid (finely stranded) +, -: 2 screw terminals each for 0.2 - 2.5 mm solid (finely stranded) Width /of the housing 45 mm 55 mm Height/of the housing 125 mm 125 mm Depth/of the housing 125 mm 125 mm Mounting width 45 mm 55 mm Mounting height 225 mm 225 mm Weight, approx. 0.8 kg 1.0 kg Product properties/of the housing/ housing that can be lined up next to other housings Yes Yes Type of mounting / panel mounting No No Type of mounting / rail mounting Yes Yes Type of mounting / S7-300 rail mounting No No Mounting Can be snapped onto standard TH35 x 7,5/15 (EN 60715) mounting rails Can be snapped onto standard TH35 x 7,5/15 (EN 60715) mounting rails 6EP1336-3BA10 (24 V/20 A) 6EP33337-8SB00-0AY0 (24 V/40 A) Connection system Screw-type terminal Screw-type terminal Connections/line input L, N(L2), PE: 1 screw terminal each for 0.2 - 6 (4) mm solid (finely stranded) L, N(L2), PE: 1 screw terminal each for 0.2 - 6 (4) mm solid (finely stranded) Connections/output +, -: 2 screw terminals each for 0.2 - 6 (4) mm solid (finely stranded) +, -: 2 screw terminals each for 0.5 - 16 mm solid (finely stranded) Width /of the housing 90 mm 145 mm Height/of the housing 125 mm 145 mm Depth/of the housing 125 mm 150 mm Mounting width 90 mm 145 mm Mounting height 225 mm 245 mm Weight, approx. 1.2 kg 3 kg Product properties/of the housing/ housing that can be lined up next to other housings Yes Yes Type of mounting / panel mounting No No Type of mounting / rail mounting Yes Yes SITOP PSU8200 1ph Manual, 08.2016, C98130-A7633-A1-5-7629 57 Technical data 6.8 Accessories 6EP1336-3BA10 (24 V/20 A) 6EP33337-8SB00-0AY0 (24 V/40 A) Type of mounting / S7-300 rail mounting No No Mounting Can be snapped onto standard TH35 x 7,5/15 (EN 60715) mounting rails Can be snapped onto standard TH35 x 15 (EN 60715) mounting rails 6.8 Accessories 6EP3333-8SB00-0AY0 (24 V/5 A) 6EP3334-8SB00-0AY0 (24 V/10 A) 6EP1336-3BA10 (24 V/20 A) 6EP3337-8SB00-0AY0 (24 V/40 A) Electrical accessories Buffer module, redundancy module Mechanical accessories Device identification labels 20 mm x 7 mm, Ti grey 3RT2900-1SB20 6.9 Dimension drawing See Section Dimensions and weight (Page 24) CAD data that can be downloaded from the Internet: 6EP3333-8SB00-0AY0 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00963) 6EP3334-8SB00-0AY0 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00966) 6EP1336-3BA10 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00385) 6EP3337-8SB00-0AY0 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_01213) SITOP PSU8200 1ph 58 Manual, 08.2016, C98130-A7633-A1-5-7629 Safety, approvals, EMC 7.1 7 Safety 6EP3333-8SB00-0AY0 (24 V/5 A) 6EP3334-8SB00-0AY0 (24 V/10 A) 6EP1336-3BA10 (24 V/20 A) 6EP3337-8SB00-0AY0 (24 V/40 A) Primary/secondary galvanic isolation Yes Electrical isolation SELV output voltage Uout acc. to EN 60950-1 and EN 50178 Protection class Class I Degree of protection (EN 60529) IP20 Leakage current, typ. 1 mA Leakage current, max. 3.5 mA Test voltage See Table 7-1 Test voltage for 6EP3333-8SB00-0AY0 and 6EP3334-8SB00-0AY0 (Page 60) See Table 7-2 Test voltage for 6EP1336-3BA10 and 6EP3337-8SB00-0AY0 (Page 61) SITOP PSU8200 1ph Manual, 08.2016, C98130-A7633-A1-5-7629 59 Safety, approvals, EMC 7.2 Test voltage 7.2 Test voltage Figure 7-1 Test voltage diagram Only the manufacturer can perform the type test and production test; users can also perform the field test. Preconditions for performing the field test: Tests (A) & (B) Connect the input terminals with one another Connect the output terminals, signaling contact and PE with one another Test (C) Connect the output terminals and signaling contact with one another and measure with respect to PE Table 7- 1 Test voltage for 6EP3333-8SB00-0AY0 and 6EP3334-8SB00-0AY0 Type test Production test Field test Test time Prim sec (A) Prim PE (B) Sec PE (C) 60 s 4200 V DC 2200 V DC 700 V DC 60 s 3000 V AC 1500 V AC 500 V AC 1s 4200 V DC 4200 V DC 500 V DC 1s 3000 V AC 3000 V AC 350 V AC 1s 2200 V DC 2200 V DC 500 V DC 1s 1500 V AC 1500 V AC 350 V AC Note: Tripping current for DC measurement: 0 mA Tripping current for AC measurement: < 100 mA SITOP PSU8200 1ph 60 Manual, 08.2016, C98130-A7633-A1-5-7629 Safety, approvals, EMC 7.3 Approvals Table 7- 2 Test voltage for 6EP1336-3BA10 and 6EP3337-8SB00-0AY0 Test time Type test Production test Field test Prim sec (A) Prim PE (B) Sec PE (C) 60 s 4200 V DC 2200 V DC 700 V DC 60 s 3000 V AC 1500 V AC 500 V AC 1s 2200 V DC 2200 V DC 500 V DC 1s 1500 V AC 1500 V AC 350 V AC 1s 2200 V DC 2200 V DC 500 V DC 1s 1500 V AC 1500 V AC 350 V AC Remark: Tripping current for DC measurement: 0 mA Tripping current for AC measurement: < 100 mA 7.3 Approvals 6EP3333-8SB00-0AY0 (24 V/5 A) 6EP1336-3BA10 (24 V/20 A) 6EP3337-8SB00-0AY0 (24 V/40 A) 6EP3334-8SB00-0AY0 (24 V/10 A) CE marking Yes, (2014/35/EG and 2014/30/EG) Yes, (2014/35/EG and 2014/30/EG) Yes, (2014/35/EG and 2014/30/EG) UL/cUL (CSA) approval cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259 cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259 cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259 Explosion protection EPS 12 ATEX 1 640 X IECEx EPS 14.0057X II 3G Ex nA nC IIC T4 Gc cCSAus HazLoc Class I, Div 2, Group A,B,C,D T4 EPS 12 ATEX 1 442 X IECEx EPS 14.0062X II 3G Ex nA nC IIC T3 Gc cCSAus HazLoc Class I, Div 2, Group A,B,C,D T3 EPS 11 ATEX 1 309 X IECEx EPS 14.0071X II 3G Ex nA nC IIC T3 Gc cULus HazLoc Class I, Div 2, Group A,B,C,D T3 CB approval Yes, (IEC 60950-1) No Yes, (IEC 60950-1) SEMI F47 compliance Fulfilled - - Marine approvals GL, ABS GL, ABS Available soon SITOP PSU8200 1ph Manual, 08.2016, C98130-A7633-A1-5-7629 61 Safety, approvals, EMC 7.4 EMC 7.4 EMC 6EP3333-8SB00-0AY0 (24 V/5 A) 6EP3334-8SB00-0AY0 (24 V/10 A) Electrostatic discharge EN 61000-4-2 8 kV contact, 8 kV air Electromagnetic fields EN 61000-4-3 80 - 1000 MHz 25 V/m 1000 - 2700 MHz 10 V/m High-speed transient disturbance variables (burst) EN 61000-4-4 4 kV at line supply connections 2 kV at the DC output Surge voltages EN 61000-4-5 3 kV symmetrical at the line supply connections 6 kV symmetrical at the line supply connections 500 V symmetrical/asymmetrical on DC output cables High-frequency fields EN 61000-4-6 10 V; 0.15 - 80 MHz Magnetic fields EN 61000-4-8 30 A/m; 50 Hz Voltage dips EN 61000-4-11 - Voltage interruptions EN 61000-4-11 - Emitted interference EN 55022 Class B Line harmonics limit EN 61000-3-2 Class A Generic standards EN61000-6-2 Immunity for industrial environments EN61000-6-3 Emission for residential areas 6EP1336-3BA10 (24 V/20 A) 6EP3337-8SB00-0AY0 (24 V/40 A) Electrostatic discharge EN 61000-4-2 8 kV contact, 8 kV air Electromagnetic fields EN 61000-4-3 80 - 1000 MHz 25 V/m 1000 - 2700 MHz 10 V/m High-speed transient disturbance variables (burst) EN 61000-4-4 4 kV at line supply connections 2 kV at the DC output Surge voltages EN 61000-4-5 3 kV symmetrical at the line supply connections 5 kV asymmetrical at the line supply connections 500 V symmetrical/asymmetrical on DC output cables High-frequency fields EN 61000-4-6 10 V; 0.15 - 80 MHz Magnetic fields EN 61000-4-8 30 A/m; 50 Hz Voltage dips EN 61000-4-11 100 % for 20 ms 60 % for 200 ms 30 % for 500 ms Voltage interruptions EN 61000-4-11 100 % for 5000 ms Emitted interference EN 55022 Class B Line harmonics limit EN 61000-3-2 Class A Generic standards EN61000-6-2 Noise immunity for industrial environments EN61000-6-3 Emission for residential areas SITOP PSU8200 1ph 62 Manual, 08.2016, C98130-A7633-A1-5-7629 Ambient conditions 8 6EP3333-8SB00-0AY0 (24 V/5 A) 6EP3334-8SB00-0AY0 (24 V/10 A) 6EP1336-3BA10 (24 V/20 A) 6EP3337-8SB00-0AY0 (24 V/40 A) Ambient temperature -25 ... 70 C for natural convection (self convection) Tested according to: Transport and storage temperature * EN 60068-2-1 cold * EN 60068-2-2 dry heat * EN 60068-2-78 humid heat, constant * EN 60068-2-14 temperature change -40 ... 85 C Tests (packed for shipping) according to: * EN 60068-2-1 cold * EN 60068-2-2 dry heat * EN 60068-2-30 humid heat, cyclic Humidity class Climatic class 3K3 according to EN 60721, without condensation Degree of pollution 2 Mechanical stressing during operation Tested according to: * EN 60068-2-6 vibration, test Fc: 7 mm deflection in the range 5 - 8.4 Hz 2 g acceleration in the range 8.4 - 150 Hz * EN 60068-2-27 shock, test Ea: acceleration 150 m/s2 , test duration 11 ms SITOP PSU8200 1ph Manual, 08.2016, C98130-A7633-A1-5-7629 63 Ambient conditions 6EP3333-8SB00-0AY0 (24 V/5 A) 6EP3334-8SB00-0AY0 (24 V/10 A) 6EP1336-3BA10 (24 V/20 A) 6EP3337-8SB00-0AY0 (24 V/40 A) Damaging gases Atmospheric pressure Tested according to: * EN 60068-2-42 sulfur dioxide * EN 60068-2-43 hydrogen sulfide Operation: * 1080 - 795 hPa (-1000 - 2000 m) * For operation at installation altitudes from 2000 m up to 6000 m: : output power must be derated by -7.5 % / 1000 m or the ambient temperature must be reduced by 5 K / 1000 m see Figure 4-5 Mounting height derating (Page 30) Overvoltage category: III to 2000 m (EN 50178) II from 2000 m to 6000 m (EN 50178) II to 2000 m (EN 60950-1) I from 2000 m to 6000 m (EN 60950-1) Storage: * * 1080 - 660 hPa (-1000 - 3500 m) SITOP PSU8200 1ph 64 Manual, 08.2016, C98130-A7633-A1-5-7629 9 Applications 9.1 Parallel connection to increase power rating To increase the power rating, SITOP PSU8200 power supplies of the same type can be directly connected in parallel. The following must be observed: The cables connected to each power supply at terminals "+" and "-" must have identical lengths and the same cable cross-sections (or the same impedance) up to a common external connection point (terminal strip) if possible. The power supplies connected in parallel must be switched on simultaneously with a common switch in the line feeder cable (e.g. with the main switch available in control cabinets). The output voltages measured in no-load operation for the power supplies that are not yet connected in parallel should not deviate more than a maximum of 50 mV. This usually corresponds to the factory setting. If the output voltage is changed, you should connect the "-" terminals and then, in no-load operation, measure the voltage difference between the "+" terminals that have not yet been connected. The voltage difference should not exceed 50 mV. Switch selector switch "A" (see ) to "Parallel operation". Figure 9-1 Parallel connection SITOP PSU8200 1ph Manual, 08.2016, C98130-A7633-A1-5-7629 65 Applications 9.1 Parallel connection to increase power rating NOTICE Protective circuit for the parallel connection of more than two power supplies When connecting more than two power supplies in parallel, additional measures must be taken to prevent high backward feeding currents in the event of a secondary device fault. For this purpose, a suitable protective circuit (e.g. decoupling diode or DC-conform circuit breaker) must be installed between each "+" terminal of the power supply and the common connection point. SITOP PSU8200 1ph 66 Manual, 08.2016, C98130-A7633-A1-5-7629 Applications 9.2 Parallel connection for redundancy 9.2 Parallel connection for redundancy Connecting several SITOP PSU8200 power supplies in parallel for redundancy purposes is required if especially high demands are placed regarding the availability of a reliable 24 V power supply. Using the SITOP PSE202Uredundancy module, two 24 V power supplies of the same type up to 20 A can be decoupled (Figure 9-2 Redundant configuration with two power supplies and SITOP PSE202U redundancy module (Page 67)). When one of the devices fails, then the other automatically takes over the power supply. If one of the power supplies fails, then this is signaled using an LED on the redundancy module as well as an isolated relay contact. When dimensioning the system, it must be ensured that n+1 redundant connected power supplies can handle the total power requirement of the remaining n power supplies. Note For a high reliability of the supply, it is recommended that the redundant switched power supplies are fused separately on the line-side and, if possible, connected to different power supply networks. Figure 9-2 Redundant configuration with two power supplies and SITOP PSE202U redundancy module You can find additional information in the: SITOP PSE202U manual (https://support.industry.siemens.com/cs/ww/en/view/42248598) SITOP PSU8200 1ph Manual, 08.2016, C98130-A7633-A1-5-7629 67 Applications 9.3 Series connection for increased voltage 9.3 Series connection for increased voltage To achieve an output voltage of 48 V DC, two 24 V SITOP PSU8200 power supplies of the same type can be connected in series. In this case, connect the "-" terminal of the first power supply to the "+" terminal of the second power supply. The "+" terminal of the first power supply and the "-" terminal of the second power supply are routed to the load. Depending on the grounding point of the secondary output voltages, voltages of +48 V, 24 V or -48 V can be realized. In the case of an asymmetric load distribution, it is not possible to guarantee correct functionality. WARNING SELV is not guaranteed in the case of a fault When connecting two power supplies in series, the continuous, permissible SELV voltage of a maximum of 60 VDC according to EN 60950 cannot be guaranteed in the case of a fault. Figure 9-3 Series connection SITOP PSU8200 1ph 68 Manual, 08.2016, C98130-A7633-A1-5-7629 Applications 9.4 Overload protection in the 24 V output circuit 9.4 Overload protection in the 24 V output circuit If an overload occurs, the electronic current limiting function limits the SITOP PSU8200 output current to a maximum value (see Section Technical data (Page 43)). The output cables are protected against a thermal overload if they are dimensioned corresponding to the maximum rms output current, or protected using additional components (for example, miniature circuit breaker, fuses). However, a load circuit that fails as a result of overload, for instance, should frequently be reliably and quickly identified and specifically switched off before the power supply goes into current-limiting mode (in current-limiting mode, the supply voltage would also be reduced for all of the remaining 24 V loads). The SITOP PSE200U selectivity module with 4 outputs (versions with adjustable output current range for each output from 0.5 - 3 A and 3 - 10 A) is available for this purpose; this monitors the 24 V branches for overload and short circuit (Figure 9-4 Electronic protection of 24 V consumers with the SITOP PSE200U selectivity module (Page 69)). Brief current peaks, e.g. as a result of a high inrush current, are permitted, and branches with a longer overload are switched into a no-current condition. This is also ensured for cables in a highohmic condition and for short-circuits that slowly develop over time. When an output fails, the fault is signaled using a group signal contact or as a single channel signal, and the branch of the module involved is displayed using an LED. For versions with single-channel signaling, function blocks for evaluation purposes are available at no charge for SIMATIC S7-1200/1500/300/400, for STEP 7 and TIA Portal as well as for SIMOTION CPUs and SIMOTION SCOUT. You can find additional information at: Manual SITOP selectivity modules (https://support.industry.siemens.com/cs/ww/en/view/108989004) Figure 9-4 Electronic protection of 24 V consumers with the SITOP PSE200U selectivity module SITOP PSU8200 1ph Manual, 08.2016, C98130-A7633-A1-5-7629 69 Applications 9.5 Protection against short-time voltage dips 9.5 Protection against short-time voltage dips In the case of a drop in the line-side supply voltage, the SITOP PSU8200 power supply can still maintain the output voltage for a short time in the millisecond range (see section Technical data (Page 43)). For line supplies that manifest frequent brief voltage dips, in order to increase the power supply reliability, it may make sense to increase the line buffering time in the device using an additional SITOP PSE201U buffer module. The SITOP PSE201U buffer module, based on electrolytic capacitors, is connected in parallel to the 24 V power supply output (Figure 9-5 Buffering brief power failures using the SITOP PSE201U buffer module (Page 70)). The buffer time is 200 ms at 40 A up to 1.6 s for a load current of 5 A. This time can be increased a multiple number of times by connecting buffer modules in parallel; the maximum buffer time is 10 s. You can find additional information at: SITOP PSE201U manual (https://support.industry.siemens.com/cs/ww/en/view/41129219) Figure 9-5 Buffering brief power failures using the SITOP PSE201U buffer module SITOP PSU8200 1ph 70 Manual, 08.2016, C98130-A7633-A1-5-7629 Applications 9.6 Protecting against longer power failures 9.6 Protecting against longer power failures Sudden and longer failures of the line supply voltage can result in undefined states and significant danger as a result of the associated failure of the plant or system control. The SITOP power supply product portfolio includes various DC-UPS solutions to prevent the failure of the 24 V power supply voltage. Power supply failures up into the minutes range can be buffered using the maintenance-free SITOP UPS500 DC-UPS modules based on capacitors (Figure 9-6 24 V buffering to allow the saving of process data and controlled shutdown of PCs (Page 71)). Figure 9-6 24 V buffering to allow the saving of process data and controlled shutdown of PCs Using the free-of-charge SITOP DC-UPS software tool, DC-UPS systems can be simply integrated into PC-based automation solutions. This supports further processing of the status signals and safely running down the PC. You can find additional information at: Manual, DC UPS with capacitors (https://support.industry.siemens.com/cs/ww/en/ps/18042/man) SITOP PSU8200 1ph Manual, 08.2016, C98130-A7633-A1-5-7629 71 Applications 9.6 Protecting against longer power failures Using DC UPS SITOP UPS1600 and SITOP UPS1100 battery modules, buffer times in the range of hours can be implemented. Intelligent battery management using Energy Storage Link automatically detects the UPS1100 energy storage device, and ensures optimum temperature-controlled charging and continuous monitoring. The UPS1600 can be flexibly integrated into the widest range of automation applications with its digital inputs/outputs as well as optional USB interface or Ethernet/PROFINET port. Figure 9-7 24 V buffering with SITOP UPS1600 to maintain communication, signaling functions, sensor measured values and position values For open, PC-based automation systems, configuration and monitoring is realized using the SITOP UPS Manager PC software, which is available at no charge. This allows PC responses to the operating states of the DC UPS to be freely selected - and offers comprehensive diagnostic functions. For TIA-based automation systems, the UPS1600 is engineered using the TIA Portal. Special function blocks for SIMATIC S7-300/400/1200 and S7-1500 - available at no charge - make it easy to integrate operating and diagnostics information into STEP 7 user programs. Preconfigured UPS faceplates for WinCC visualization can be downloaded at no charge. You can find additional information at: DC UPS SITOP UPS1600/UPS1100 Manual (https://support.industry.siemens.com/cs/ww/en/view/84977415) SITOP PSU8200 1ph 72 Manual, 08.2016, C98130-A7633-A1-5-7629 Environment 10 The devices are in conformance with RoHS. As a rule, only non-silicon precipitating materials are used. Disposal guidelines Packaging and packaging aids can and should always be recycled. The product itself may not be disposed of as domestic refuse. SITOP PSU8200 1ph Manual, 08.2016, C98130-A7633-A1-5-7629 73 Environment SITOP PSU8200 1ph 74 Manual, 08.2016, C98130-A7633-A1-5-7629 Service & Support 11 Technical support Technical support for all IA/DT products can be accessed through the following communication channels: Phone: + 49 (0) 911 895 7222 E-Mail (mailto:support.automation@siemens.com) Internet: Online support request form (http://www.siemens.de/automation/support-request) Technical documentation on the Internet Operating instructions and manuals for SITOP are available in the Internet: Operating instructions/manuals (http://www.siemens.de/sitop/manuals) SITOP power supply homepage General news about our power supplies is available in the Internet at the SITOP homepage: SITOP (http://www.siemens.de/sitop) Information material SITOP information can be downloaded from the Internet: Information and download center (http://www.siemens.de/sitop-infomaterial) CAx data 2D/3D data and circuit diagram macros can be downloaded from the Internet: Siemens image database (http://www.siemens.de/sitop-cax) Request all CAx data via the CAx download manager: CAx shopping cart (http://www.siemens.de/cax) SITOP Selection Tool Simply and quickly select the optimum the power supply or DC-UPS: SITOP Selection Tool (http://www.siemens.de/sitop-selection-tool) Online catalog and ordering system The online catalog and the online ordering system are available through the Industry Mall homepage: Industry Mall (http://www.siemens.com/industrymall/de) SITOP PSU8200 1ph Manual, 08.2016, C98130-A7633-A1-5-7629 75 Service & Support Contact persons If you have any questions regarding the use of our products, then contact the Siemens contact person in your regional Siemens sales office. You can find these addresses as follows: On the Internet (http://www.siemens.de/automation/partner) In Catalog CA 01 SITOP PSU8200 1ph 76 Manual, 08.2016, C98130-A7633-A1-5-7629