cui.com
date 08/04/2020
page 1 of 6
SERIES: PDRC-10 DESCRIPTION: AC-DC DIN RAIL POWER SUPPLY
MODEL output
voltage
output
current
output
power
ripple
and noise1
eciency2
(Vdc)
max
(A)
max
(W)
max
(mVp-p)
typ
(%)
PDRC-10-5 5 1.5 7.5 50 75
PDRC-10-12 12 0.83 10 50 79
PDRC-10-15 15 0.67 10 50 80
PDRC-10-24 24 0.42 10 50 80
Notes: 1. At full load, nominal input, 20 MHz bandwidth oscilloscope.
2. At nominal input.
3. All specications are measured at Ta=25°C, nominal input voltage, and rated output load unless otherwise specied.
FEATURES
• low profile for building automation
• universal input (90~264 Vac)
• integrated fuse and surge protection
• 3,000 Vac input/output isolation voltage
• DC On/Low LED indicators
• over-voltage/current protection
• UL/cUL, TUV, CE certified
PART NUMBER KEY
Base Number
PDRC-10 - XX
Output Voltage
Additional Resources: Product Page | 3D Model
cui.com
date 08/04/2020 page 2 of 6CUI Inc SERIES: PDRC-10 DESCRIPTION: AC-DC DIN RAIL POWER SUPPLY
INPUT
parameter conditions/description min typ max units
voltage 90
120
264
375
Vac
Vdc
frequency 47 63 Hz
current at 90 Vac, full load 300 mA
inrush current at 115 Vac, full load
at 230 Vac, full load
16
32
A
A
leakage current input to output 0.25 mA
OUTPUT
parameter conditions/description min typ max units
capacitive load
5 Vdc output model
12 Vdc output model
15 Vdc output model
24 Vdc output model
3,500
1,800
1,500
560
µF
µF
µF
µF
initial set point accuracy ±1 %
line regulation at full load, V in min to V in max ±1 %
load regulation at Vi nom, 0~100% load ±1 %
start-up time at Vi nom, full load
at Vi nom, full load with max capacitive load
1.0
1.5
s
s
rise time at Vi nom, full load
at Vi nom, full load with max capacitive load
150
500
ms
ms
hold-up time at 115 Vac, full load
at 230 Vac, full load
10
30
ms
ms
fall time at Vi nom, full load 150 ms
transient recovery time at Vi nom, 100~50% load 2 ms
switching frequency at Vi nom, full load 132 kHz
temperature coecient ±0.03 %/°C
power back immunity
at Vi nom, full load, for 1 second
5 Vdc output model
12 Vdc output model
15 Vdc output model
24 Vdc output model
7.5
18
22
35
Vdc
Vdc
Vdc
Vdc
DC ON indicator threshold at
start-up (GREEN)
5 Vdc output model
12 Vdc output model
15 Vdc output model
24 Vdc output model
3.5
9.0
11.0
19.2
4.5
10.8
13.5
21.6
Vdc
Vdc
Vdc
Vdc
DC LOW indicator threshold
after start-up (RED)
5 Vdc output model
12 Vdc output model
15 Vdc output model
24 Vdc output model
3.5
9.0
11.0
19.2
4.5
10.8
13.5
21.6
Vdc
Vdc
Vdc
Vdc
PROTECTIONS
parameter conditions/description min typ max units
over voltage protection
at Vi nom, full load, auto recovery
5 Vdc output model
12 Vdc output model
15 Vdc output model
24 Vdc output model
5.75
15
18
30
6.5
16.5
20
33
Vdc
Vdc
Vdc
Vdc
over current protection hiccup, auto recovery (see curve) 125 185 %
short circuit protection hiccup, auto recovery
Additional Resources: Product Page | 3D Model
cui.com
date 08/04/2020 page 3 of 6CUI Inc SERIES: PDRC-10 DESCRIPTION: AC-DC DIN RAIL POWER SUPPLY
SAFETY & COMPLIANCE
parameter conditions/description min typ max units
isolation voltage input to output for 1 minute 3,000
4,242
Vac
Vdc
isolation resistance input to output at 500 Vdc 100
safety approvals UL 508, UL 1310, UL/EN 62368-1
ISA 12.12.01 (Class I, Div 2, Groups A~D)
safety class class I
EMI/EMC
EN 55022 Class B, EN 55032 Class B, EN 55024,
ENV 50204, EN 61204-3, EN 61000-3-2,
EN 61000-3-3, EN 61000-6-2, EN 61000-6-3,
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4,
EN 61000-4-5,EN 61000-4-6, EN 61000-4-8,
EN 61000-4-11
pollution degree 2
degree of protection IP20
MTBF
as per Bellcore Issue 6 at 40 °C, GB
5 Vdc output model
12 Vdc output model
15 Vdc output model
24 Vdc output model
901,000
888,000
893,000
910,000
hours
hours
hours
hours
RoHS yes
Notes: 4. The power supply is considered a component which will be installed into nal equipment. The nal equipment still must be tested to meet the necessary EMC directives.
ENVIRONMENTAL
parameter conditions/description min typ max units
operating temperature see derating curves -40 71 °C
storage temperature -40 85 °C
humidity non-condensing 20 95 %
altitude IEC 60068-2-13 4,850 m
vibration
meets IEC 60068-2-6 (Mounting on rail: 10~500
Hz, 2 G, along X,Y,Z axis, for 60 minutes on each
axis)
shock meets IEC 60068-2-27 (15 G, 11 ms, 3 axis, 6
faces, 3 times for each face)
Additional Resources: Product Page | 3D Model
cui.com
date 08/04/2020 page 4 of 6CUI Inc SERIES: PDRC-10 DESCRIPTION: AC-DC DIN RAIL POWER SUPPLY
units: mm [inch]
tolerance:
X≤30.00: ±0.30 [±0.01]
30.00<X≤120.00: ±0.50 [±0.02]
unless otherwise noted
TERMINAL
CONNECTIONS
TERMINAL Function
1V-
2 V+
3 L
4 N
MECHANICAL
parameter conditions/description min typ max units
dimensions 91.00 x 18.00 x 56.50 (3.58 x 0.71 x 2.22 inches) mm
material plastic
weight 65 g
cooling natural convection
input/output connector accepts 26~12 AWG wire
MECHANICAL DRAWING
INSTALLATION
DIN RAIL TS35/7.5 or TS35/15
Cable exible/solid, copper conductors
only, 60/75°C
Wire Range 26~12 AWG
(0.2~2.5 mm2)
Strip Length 4~5 mm
Screw Torque 5 lb·in
Position Vertical
Cooling Natural convection, 25 mm
clearance on all sides
Additional Resources: Product Page | 3D Model
cui.com
date 08/04/2020 page 5 of 6CUI Inc SERIES: PDRC-10 DESCRIPTION: AC-DC DIN RAIL POWER SUPPLY
100
80
60
40
20
Ambient Temperature (°C)
Load (%)
40 50 61
75
-40 010203071 80
EFFICIENCY CURVES
DERATING CURVES
Temperature Derating Curve
(Output Load vs. Ambient Tempearature)
Load Current (%)
Eciency (%)
PDRC-10-24 Eciency Curve
(Efciency vs. Load Current)
(%)
PDRC-10-24 Typical Over Current Protection Curve
(Output Voltage vs. Time)
CURRENT LIMITED CURVE
Additional Resources: Product Page | 3D Model
date 08/04/2020 page 6 of 6CUI Inc SERIES: PDRC-10 DESCRIPTION: AC-DC DIN RAIL POWER SUPPLY
CUI oers a two (2) year limited warranty. Complete warranty information is listed on our website.
CUI reserves the right to make changes to the product at any time without notice. Information provided by CUI is believed to be accurate and reliable. However, no responsibility is
assumed by CUI for its use, nor for any infringements of patents or other rights of third parties which may result from its use.
CUI products are not authorized or warranted for use as critical components in equipment that requires an extremely high level of reliability. A critical component is any component of a
life support device or system whose failure to perform can be reasonably expected to cause the failure of the life support device or system, or to aect its safety or eectiveness.
Headquarters
20050 SW 112th Ave.
Tualatin, OR 97062
800.275.4899
Fax 503.612.2383
cui.com
techsupport@cui.com
rev. description date
1.0 initial release 06/13/2019
1.01 updated safety certications 08/04/2020
The revision history provided is for informational purposes only and is believed to be accurate.
REVISION HISTORY
Additional Resources: Product Page | 3D Model