es rfac al ntic Ide Us V ! New V, New nte I r e 0 ! 80 40 , V 30 2 V, 1 0 0 10 de o 0Vm 5 and 50V W 15k ls 0 150 d an s del o Vm 5kW W/1 k - 10 C 0VA 0 -2 C/4 A V 08 8 C/4 A V 0 Genesys TM Programmable DC Power Supplies Full-Rack 10kW/15kW in 3U Height Built in RS-232 & RS-485 Interface Parallel Operation (Basic or Advanced) Optional Interfaces: LAN ( compliant w/ Multi-Drop) IEEE (488.2 & SCPI compliant w/ Multi-Drop) USB (2.0 w/ Multi-Drop) Isolated Analog (5V/10V or 4-20mA Pgm/Mon) GenesysTM Family GENH-1U 750W Half-Rack GEN-1U 750W/1.5kW/2.4kW Full-Rack GEN-2U 3.3kW/5.0kW Full-Rack GEN-3U 10kW/15kW Full-Rack www.us.tdk-lambda.com/hp The GenesysTM family of programmable power supplies sets a new standard for flexible, reliable, AC/DC power systems in OEM, Industrial and Laboratory applications. Features include: * * * * * * * * * * * * * High Power Density 10kW/15kW in full-rack 3U package High Output Current (up to 1000ADC) Popular worldwide 3 AC inputs, (208VAC, 400VAC, 480VAC) Power Factor 0.88 (Passive PFC on all 3 AC Inputs) Output Voltage from 7.5V (1000A) to 1500V (10A) Built-in RS-232/RS-485 Serial Interface (standard) Last Setting Memory, Safe/Auto-ReStart, Front Panel Lock/Unlock "Advanced Parallel" configuration reports total system current (up to four identical units) Global Commands for RS-232/RS-485 Serial Interface Continuous Encoders for Voltage and Current Adjustment (Coarse & Fine mode) Independent Remote SHUTOFF and Remote ENABLE/DISABLE 19" Rack Mounted for ATE and OEM Applications, zero-stack capability Optional Interfaces compliant LAN (Class C) w/ Multi-Drop capability: option for all models IEEE (488.2 & SCPI compliant) w/ Multi-Drop capability: option for all models USB (2.0) w/ Multi-Drop capability: option for all models Isolated Analog Programming and Monitoring Interface 0-5V/0-10V: option for models with Vout < 600V, standard for models with Vout > 800V 4-20mA: option for all models * LabViewTM and LabWindowsTM Software Drivers * Worldwide Safety Agency Approvals; UL Recognized and CE Mark for LV, EMC and RoHS2 Directives (208VAC (all models), 400VAC (all models) and 480VAC models (30V < Vout < 1500V)) * Five Year Warranty Applications GenesysTM power supplies are designed for demanding applications. Test & Measurement systems using GPIB control save significant costs by incorporating the optional IEEE MultiDrop Interface (IEMD) in the Master unit. This allows up to 30 Slave units to be used with the standard RS-485 MultiDrop Serial interface. Automated System designers will appreciate new, standard, remote programming features such as Global com- mands. Also, new high-speed status monitoring is available for the standard RS-485 and optional LAN (LXI compliant) Interface. Industrial & Military high power systems can be configured with up to four identical units in parallel (up to 60kW). No space is required above or below each power supply (zero-stack). The Master unit can be configured by the user to report the total Output current of the combined system. Applications include Heaters, Magnets and Laser Diodes. Aerospace & Satellite Testing systems use the complete GenesysTM Family: 1U-750W Half-Rack, 1U-750W/ 1.5kW/2.4kW Full-Rack, 2U-3.3kW/5kW Full-Rack and 3U-10kW/15kW Full-Rack. All are identical in Front Panel, Rear Panel Analog and Digital Interface commands. A wide variety of Outputs (voltage and current) allows testing of many different user configurations. Component Device Testing is simplified because of the many user-friendly control options in the Analog and Digital interfaces. Lamps, capacitors, motors and actuators are typical devices tested. Medical Imaging and Treatment systems require reliable power. Modular construction, SMT and thoroughly proven designs assure continuous performance at full rated power. Semiconductor Processing & Burn-in equipment designers appreciate the wide variety of worldwide AC Inputs and DC Outputs from which to select, depending on application. Selectable Safe-Start and Auto Re-Start protects loads and process integrity. Typical applications include Magnets, Filaments and Heaters. 1 GenesysTM 3U 10/15kW Front Panel Description (7.5V < Vout < 25V) 4 1 6 3 5 7 8 2 1. AC ON/OFF Switch (circuit breaker for Vout < 25V; rocker switch for Vout > 30V models) 2. Air Intake allows zero-stacking for maximum system flexibility and power density. 3. Continuous encoder controls Output Voltage, Address, OVP and UVL settings. 4. Voltage Display shows Output Voltage and directly displays OVP, UVL and Address settings. 5. Continuous encoder controls Output Current, sets Baud rate and Advanced Parallel mode. 6. Current Display shows Output Current and displays Baud rate. Displays total current in Parallel Master/Slave Mode. 7. Function/Status LEDs: * Fine Control * Preview Settings * Alarm * Foldback Mode * Remote Mode * Output On 8. Pushbuttons allow flexible user configuration * Coarse and Fine adjustment of Output Voltage/Output Current and Advanced Parallel Master or Slave select. * Preview Settings and set Voltage/Current with Output OFF, Front Panel Lock/Unlock. * Parallel Master/Slave (Basic and Advanced). * Set Output OVP and UVL Limits. * Set Output Current Foldback Protection. * Go to Local Mode and select unit Address and Baud rate. * Output ON/OFF and Safe-Start/Auto Re-Start mode. Rear Panel Description (7.5V < Vout < 25V) 1 2 4 3 6 1. 2. 3. 4. 5. 6. 7. 8. 9. 5 9 7 8 Remote/Local Output Voltage Sense Connections. DIP Switches select 0-5V or 0-10V Programming and other functions. DB25 (Female) connector allows Analog Program and Monitor (non-isolated) and other functions. RS-485 OUT to other GenesysTM Power Supplies. RS-232/RS-485 IN Remote Serial Programming. Output Connectors: Rugged 2 hole busbars (shown) for models where Vout < 30V, single hole busbars for 30V < Vout < 300V Output, and threaded-stud terminals for models where Vout > 300V. Exit air assures reliable operation when zero-stacked. Input Terminals L1, L2, L3, and Ground (threaded studs). Optional location for LAN (LXI Class C), IEEE (488.2 & SCPI compliant), USB (2.0) or Isolated Analog Interface. 2 GenesysTM 3U 10kW Specifications 1.0 MODEL 1.Rated Output Voltage 2.Rated Output Current 3.Rated Output Power 4.Efficiency (min) at low AC line, 100% Rated Load GEN VDC ADC kW % 7.5-1000 10-1000 12.5-800 20-500 25-400 30-333 40-250 50-200 60-167 7.5 10 12.5 20 25 30 40 50 60 1000 1000 800 500 400 333 250 200 167 7.5 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 77 83 Contact Factory for other models 80-125 80 125 10.0 100-100 100 100 10.0 125-80 125 80 10.0 10kW X X X X X X 1.1 CONSTANT VOLTAGE MODE (CV) 1. Max. Line Reg (0.1% - Vor 30V; 0.05% - 30V < Vor < 600V; 0.05% - 600V < Vor < 1500V) 2. Max. Load Reg (0.1% for Vor 30V; 0.05% for 30V < Vor < 600V; 0.1% for 600V < Vor < 1500V); (*5) 3. Output Ripple, rms (5Hz~1MHz), CV mode; (*1) 4. Output Noise, p-p (20MHz), CV mode; (*1) 5.Remote Sense Compensation / Wire 6. Temperature Stability 7. Temperature Coefficient 8. Up-Prog. Response Time, 0 ~ Vomax, full-load 9. Up-Prog. Response Time, 0~Vomax, no-load 10. Transient Response Time (CV mode); (*2), (*4) mV 7.5 10 12.5 20 25 30 20 25 30 40 50 62.5 X mV 7.5 10 12.5 20 25 30 20 25 30 40 mV mV V --ppm / C ms ms ms 50 62.5 X 20 20 20 20 20 20 20 20 20 25 25 60 60 60 60 60 60 60 75 75 100 100 1 1 1 1 1 1.5 2 3 3 4 5 0.05% of Vo(rated) over 8 hours after 30 minute warm up (constant Line, Load & Temperature) 200 ( 0.02% of Vo(rated)) / C 100 50 Less than 3 25 125 5 X X X X X X X X 1000 1000 800 500 400 333 125 100 83.5 62.5 50 40 X 1000 1000 800 500 400 333 188 150 125 94 75 60 X 5300 4000 2560 1000 640 444 250 160 67 50 40 0.05% of Io(rated) over 8 hours, after 30 minute warm up (constant Line, Load & Temperature) 300 ( 0.03% of Io(rated)) / C 32 X X X 1.2 CONSTANT CURRENT MODE (CC) 1. Max. Line Reg. (0.1% - Ior > 333A; 0.050% - 17A < Ior < 333A; 0.15% - Ior < 17A) 2. Max. Load Reg (0.1% - Ior > 333A; 0.075% - 17A < Ior < 333A; 0.2% - Ior < 17A); (*3), (*5) 3. Output Ripple, rms (5Hz~1MHz), CC mode 4. Temperature Stability 5. Temperature Coefficient mA mA mA --ppm/C 1.3 PROTECTIVE FUNCTIONS 1. OCP 2. OCP type 3. Foldback Protection (FOLD) 4. Foldback Response Time 5. OVP type 6. OVP Programming Accuracy % ----s --% 7. OVP Trip Point V 8. OVP Response Time ms 9. Max. OVP Reset Time 10. Over-Temperature Protection (OTP) 11. Phase-Loss Protection s ----- 1.4 REMOTE ANALOG CONTROLS & SIGNALS 1. Vout Voltage Programming 2. Iout Voltage Programming 3. Vout Resistor Programming 4. Iout Resistor Programming 5. Shut-Off (SO) Control (rear panel) 6. Output Current Monitor 7. Output Voltage Monitor 8. Power Supply OK (PS_OK) Signal 9. CV/CC Signal 10. Enable/Disable 11. Remote/Local Selection 12. Remote/Local Signal 1.5 FRONT PANEL 1.Control Functions 2.Display 3.Indications 1.6 DIGITAL PROGRAMMING & READBACK 1. Vout Programming Accuracy 2. Iout Programming Accuracy 3. Vout Programming Resolution 4. Iout Programming Resolution 5. Vout Readback Accuracy 6. Iout Readback Accuracy 7. Vout Readback Resolution 8. Iout Readback Resolution 9. OV Response Time 10. Other Functions 0 ~ 100 Constant current Output shutdown; Manual reset by front panel OUT button or Digital communication, user-selectable Less than 1 (Min = 0.25 / Max = 25 / Default = 0.25); Settable via "FBD" command Inverter shut-down; Manual reset by AC On/Off recycle, OUT button, Remote Analog or Digital commuincation 5% of Vo(rated) 5% to 105% of Vo(rated) for Vor < 600V; 10% to 105% of Vo(rated) for 600V < Vor < 1500V Shall always be greater than 105% of Vo(setting); Default = 105% of Vo(rated) Less than 10 (for Output to begin to drop) for Vor < 600V Less than 2.0 (for Output to begin to drop) for 600V < Vor < 1500V 7 (from AC On/Off switch turn On) Shut down if internal temperature exceeds safe operating levels (Latched: Safe / Unlatched: Auto) Yes, power supply shutdown (Latched: Safe-Start / Unlatched: Auto-Restart) X X X X X 0~100%, 0 ~ 5V or 0 ~ 10V, user-selectable., Accuracy & Linearity: 1% of Vo(rated) 0~100%, 0 ~ 5V or 0 ~ 10V, user-selectable, Accuracy & Linearity: 1% of Io(rated) 0~100%, 0 ~ 5/10kohm full-scale, user-selectable, Accuracy & Linearity: 1% of Vo(rated) 0~100%, 0 ~ 5/10kohm full-scale, user-selectable, Accuracy & Linearity: 1% of Io(rated) By Voltage: 0.6V = DIS, 2-15V = ENA (default) or by Dry Contact: Open = ENA, Short = DIS (user-selectable logic) 0 ~ 5V or 0 ~ 10V, Accuracy: 1% of Io(rated), user-selectable 0 ~ 5V or 0 ~ 10V, Accuracy: 1% of Vo(rated), user-selectable Yes. TTL High = OK, 0V = Fail (500ohm series impedance) CV: TTL High (4 ~ 5V), Max source current = 10mA; CC: TTL Low (0 ~ 0.4V), Max sink current = 10mA Dry contact; Open = OFF, Short = ON; Maximum voltage across Enable/Disable contacts = 6V Selects Remote or Local operation by voltage: 0 ~ 0.6V = Local / 2 ~ 15V = Remote Signals operating mode; Open collector: Local = Open (Max voltage = 30V), Remote = On (Max sink current = 10mA) X X X X X X X X X X X X Vout/ Iout manual adjust by separate encoders (COARSE and FINE adjustment selectable) OVP/UVL manual adjust by VOLTAGE Adjust encoder, Front Panel Lock/Unlock Address selection by VOLTAGE Adjust encoder. # of Addresses = 31 AC ON/OFF, Output On/Off, Restart Modes (Auto/Safe), Foldback Control (CV to CC), Go-to-Local RS-232/RS-485, LAN, IEEE (IEMD) and USB selection by rear panel DIP-switch Baud rate selection (RS-232/RS-485 only): 1200, 2400, 4800, 9600 and 19,200 (by CURRENT Adjust encoder) Advanced Parallel Master/Slave: Hx = Master unit, where x = # of Slave units (0 to 4), S = Slave unit(s) Voltage: 4 digits, Accuracy: 0.5% of Vo(rated) 1 count Current: 4 digits, Accuracy: 0.5% of Io(rated) 1 count VOLTAGE meter displays voltage at power supply (Local sense) or at load (Remote sense) Green LED's: PREVIEW, FOLD, REM/LOCAL, OUT ON/OFF, CV/CC, FINE Red LED: ALARM (OVP, OTP, FOLD, AC FAIL, ENA, SO) X X X X X X X X X X 0.5% of Vo(rated) 0.5% of Io(rated) for units with Io < 187.5A; 0.7% of Io(rated) for Io 187.5A 0.02% of Vo(rated) 0.04% of Io(rated) (0.1% of Vo(actual) + 0.2% of Vo(rated)) (0.1% of Io(actual) + 0.4% of Io(rated)) 0.02% of Vo(rated) 0.02% of Io(rated) 20ms maximum (between Vout exceeding IEEE Limit and supply Inhibit turning On) Set OVP/UVL limits; Set Local/Remote, Operating parameters and Status, Get Identity *1 Ripple and Noise at Vo(rated) and rated Load, Ta = +25C and nominal AC Input per EIJ R900A. *2. Time for the Output voltage to recover within 2% of rating for a load current change of 50~100% or 100-50% of Io(rated). *3 .From 20% - 100% for models with Ior < 17A. *4 Operating with a load that continuously pulses the current (or voltage) can reduce the operating life of the Power Supply. Please contact TDK-Lambda Sales/Technical Support to discuss the application in detail. *5. CV Mode: from 5% to 100% of Irated (over 5% to 100% of Prated); CC Mode: from 20% to 100% of Vrated (over 20% to 100% of Prated). All specifications subject to change without notice. 3 GenesysTM 3U 10/15kW X X X X X X X X X X X X X X X X X GenesysTM 3U 10kW Specifications 10kW X 1.0 MODEL GEN 150-66 1.Rated Output Voltage VDC 150 200 250 300 400 500 600 800 1000 1250 1500 X 2.Rated Output Current ADC 66 50 40 33 25 20 17 12.5 10 8.0 6.7 X kW % 9.9 10.0 10.0 9.9 10.0 10.0 10.2 83 Contact Factory for other models 10.0 10.0 10.0 10.0 X X X mV 75 100 125 150 200 250 300 400 500 625 750 X 75 100 125 150 200 250 300 800 1000 1250 1500 X 140 1400 5 X X X X X X X X X 3.Rated Output Power 4.Efficiency (min) at low AC line, 100% Rated Load 200-50 250-40 300-33 1.1 CONSTANT VOLTAGE MODE (CV) 1. Max. Line Reg (0.1% - Vor 30V; 0.05% - 30V < Vor < 600V; 0.05% - 600V < Vor < 1500V) 2. Max. Load Reg (0.1% - Vor 30V; 0.05% - 30V < Vor < 600V; 0.1% - 600V < Vor < 1500V); (*5) 3. Output Ripple, rms (5Hz~1MHz), CV mode; (*1) 4. Output Noise, p-p (20MHz), CV mode; (*1) 5.Remote Sense Compensation / Wire 6. Temperature Stability 7. Temperature Coefficient 8. Up-Prog. Response Time, 0~Vomax, full-load 9. Up-Prog. Response Time, 0~Vomax, no load 10. Transient Response Time (CV mode); (*2), (*4) 1.2 CONSTANT CURRENT MODE (CC) 1. Max. Line Reg. (0.1% - Ior > 333A; 0.050% - 17A < Ior < 333A; 0.15% - Ior < 17A) 2. Max. Load Reg (0.1% - Ior > 333A; 0.075% - 17A < Ior < 333A; 0.2% - Ior < 17A); (*3), (*5) 3. Output Ripple, rms (5Hz~1MHz), CC mode 4. Temperature Stability 5. Temperature Coefficient mV mV mV V --ppm / C ms ms ms mA mA mA --ppm / C 1.3 PROTECTIVE FUNCTIONS 1. OCP 2. OCP type 3. Foldback Protection (FOLD) 4. Foldback Response Time 5. OVP type 6. OVP Programming Accuracy % ----s --% 7. OVP Trip Point V 8. OVP response time ms 9. Max. OVP reset time 10. Over-Temperature Protection (OTP) s ----- 11. Phase-Loss Protection 1.4 REMOTE ANALOG CONTROLS & SIGNALS 1. Vout Voltage Programming 2. Iout Voltage Programming 3. Vout resistor programming 4. Iout Resistor Programming 5. Shut-Off (SO) Control (rear panel) 6. Output Current Monitor 7. Output Voltage Monitor 8. Power Supply OK (PS_OK) Signal 9. CV/CC Signal 10. Enable/Disable 11. Remote/Local Selection 12. Remote/Local Signal 1.5 FRONT PANEL 1.Control Functions 2.Display 3.Indications 400-25 500-20 600-17 800-12.5 1000-10 1250-8 1500-6.7 93.5 25 35 35 60 60 60 60 80 100 120 150 175 200 200 300 350 350 700 800 1000 5 5 5 5 5 5 5 5 5 5 0.05% of Vo(rated) over 8 hours after 30 minute warm up (constant Line, Load & Temperature) 200 (0.02% of Vo(rated)) / C 100 17 50 17 Less than 3 Less than 1 33 25 20 17 13 10 9 19 15 12 10 50 38 30 25 19 15 13 25 20 15 14 X 4 X X X 26 20 16 13 10 8 7 15 10 6 0.05% of Io Rated over 8 hours after 30 minute warm up (constant Line, Load & Temperature) 300 (0.03% of Io(rated)) / C 0 ~ 100 Constant current Output shut down; Manual reset by front panel OUT button or Digital communication, user-selectable Less than 1 (Min = 0.25 / Max = 25 / Default = 0.25); Settable via "FBD" command Inverter shut-down; Manual reset by AC On/Off recycle, OUT button, Remote Analog or Digital comm. 5% of Vo(rated) 5% to 105% of Vo(rated) - for Vor < 600V; 10% to 105% of Vo(rated) - 600V < Vor < 1500V Shall always be greater than 105% of Vo(setting); Default = 105% of Vo(rated) Less than 10 (for Output to begin to drop) for Vor < 600V Less than 2.0 (for Output to begin to drop) for 600V < Vor < 1500V 7 (from AC On/Off switch turn On) Shut down if internal temperature exceeds safe operating levels. (Latched: Safe / Unlatched: Auto) Yes, power supply shutdown (Latched: Safe-Start / Unlatched: Auto-Restart) X X X X X X X X X X X 0~100%, 0 ~ 5V or 0 ~ 10V, user-selectable, Accuracy & Linearity: 1% of Vo(rated) 0 ~ 100%, 0~5V or 0 ~ 10V, user-selectable. Accuracy & Linearity 1% of Io(rated) 0~100%, 0~5/10kohm full-scale, user-selectable. Accuracy & Linearity 1% of Vo(rated) 0~100%, 0~5/10kohm full-scale, user-selectable. Accuracy & Linearity 1% of Io(rated) By Voltage: 0.6V = DIS, 2-15V = ENA (default) or Dry Contact : Open = ENA, Short = DIS (user-selectable logic) 0 ~ 5V or 0 ~ 10V, Accuracy: 1% of Io(rated), user-selectable 0 ~ 5V or 0 ~ 10V, Accuracy: 1% of Vo(rated), user-selectable Yes. TTL high = OK, 0V = Fail (500ohm series impedance) CV: TTL High (4 ~ 5V), Max source current = 10mA; CC: TTL Low (0 ~ 0.4V), Max sink current = 10mA Dry contact; Open = OFF, Short = ON; Maximum voltage across Enable/Disable contacts = 6V Selects Remote or Local operation by voltage: 0 ~ 0.6V = Local / 2 ~ 15V = Remote Signals operating mode; Open collector: Local = Open (Max voltage = 30V), Remote = On (Max sink current = 10mA) X X X X X X X X X X X X Vout/ Iout manual adjust by separate encoders (COARSE and FINE adjustment selectable) OVP/UVL manual adjust by VOLTAGE Adjust encoder, Front Panel Lock/Unlock Address selection by Voltage Adjust encoder. # of Addresses = 31 AC ON/OFF, Output On/Off, Restart Modes (Auto/Safe), Foldback Control (CV to CC), Go-to-Local RS-232/RS-485, LAN, IEEE (IEMD) and USB selection by rear-panel DIP-switch Baud rate selection (RS-232/RS-485 only): 1200, 2400, 4800, 9600 and 19,200 (by CURRENT Adjust encoder) Advanced Parallel Master/Slave: Hx = Master unit, where x = # of Slave units (0 to 4), Slave = Slave unit(s) Voltage: 4 digits, Accuracy: 0.5% of Vo(rated) 1 count Current: 4 digits, Accuracy: 0.5% of Io(rated) 1 count VOLTAGE meter displays voltage at power supply (Local sense) or at load (Remote sense) Green LED's: PREVIEW, FOLD, REM/LOCAL, OUT ON/OFF, CV/CC, FINE Red LED: ALARM (OVP, OTP, FOLD, AC FAIL, ENA, SO) X X X X X X X X X X X 1.6 DIGITAL PROGRAMMING & READBACK 1. Vout Programming Accuracy 0.5% of Vo(rated) X 2. Iout Programming Accuracy 0.5% of Io(rated) for units with Io < 187.5A; 0.7% of Io(rated) for Io 187.5A X 3. Vout Programming Resolution 0.02% of Vo(rated) X 4. Iout Programming Resolution 0.04% of Io(rated) X 5. Vout Readback Accuracy (0.1% of Vo(actual) + 0.2% of Vo(rated)) X 6. Iout Readback Accuracy (0.1% of Vo(actual) + 0.4% of Vo(rated)) X 7. Vout Readback Resolution 0.02% of Vo(rated) X 8. Iout Readback Resolution 0.02% of Io(rated) X 9. OV Response Time 20ms maximum (between Vout exceeding IEEE Limit and supply Inhibit turning On) X 10. Other Functions Set OVP/UVL limits; Set Local/Remote, Operating Parameters and Status; Get Identity X *1. Ripple and Noise at Vo(rated) and rated Load, Ta = +25C and nominal AC input, per EIJ R9002A *2. Time for the Output voltage to recover within 2% of rating for a load current change of 50~100% or 100~50% of Io(rated). *3. From 20% - 100% for models with Ior < 17A. *4 Operating with a load that continuously pulses the current (or voltage) can reduce the operating life of the Power Supply. Please contact TDK-Lambda Sales/Technical Support to discuss the application in detail. *5. CV Mode: from 5% to 100% of Irated (over 5% to 100% of Prated); CC Mode: from 20% to 100% of Vrated (over 20% to 100% of Prated). All specifications subject to change without notice. 4 GenesysTM 3U 15kW Specifications 1.0 MODEL 1.Rated Output Voltage 2.Rated Output Current 3.Rated Output Power 4.Efficiency (min) at low AC line, 100% Rated Load 1.1 CONSTANT VOLTAGE MODE (CV) 1. Max. Line Reg (0.1% - Vor 30V; 0.05% - 30V < Vor < 600V; 0.05% - 600V < Vor < 1500V) 2. Max. Load Reg (0.1% - Vor 30V; 0.05% - 30V < Vor < 600V; 0.1% - 600V < Vor < 1500V); (*5) 3. Output Ripple, rms (5Hz~1MHz), CV mode; (*1) 4. Output Noise, p-p (20MHz), CV mode; (*1) 5.Remote Sense Compensation / Wire 6. Temperature Stability 7. Temperature Coefficient 8. Up-Prog. Response Time, 0 ~ Vomax, full-load 9. Up-Prog. Response Time, 0~Vomax, no load 10. Transient Response Time (CV mode); (*2), (*4) 1.2 CONSTANT CURRENT MODE (CC) 1. Max. Line Reg. (0.1% - Ior 333A; 0.050% - Ior < 333A) 2. Max. Load Reg (0.1% - Ior 333A; 0.075% - 25A < Ior < 333A; 0.2% - Ior < 25A); (*3), (*5) 3. Ripple, rms (5Hz~1MHz), CC mode 4. Temperature Stability 5. Temperature Coefficient N/A --------- N/A --------- N/A --------- N/A --------- mV --- --- --- --- --- 30 20 25 30 40 50 62.5 X mV --- --- --- --- --- 30 20 25 30 40 50 62.5 X ----------20 20 20 20 25 25 ----------60 60 75 75 100 100 ----------1.5 2 3 3 4 5 0.05% of Vo(rated) over 8 hours after 30 minute warm up (constant Line, Load & Temperature) 200 ( 0.02% of Vo(rated)) / C 100 50 Less than 3 25 125 5 X X X X X X X X X mV mV V --ppm / C ms ms ms --- --- --- --- --- 500 375 334 125 94 75 60 mA --- --- --- --- --- 500 375 334 188 141 113 90 X ----------350 200 150 100 100 100 0.05% of Io(rated) over 8 hours after 30 minute warm up (constant Line, Load & Temperature) 300 ( 0.03% of Io(rated)) / C 50 X X X mA --ppm/C % ----s --% 7. OVP Trip Point V 8. OVP Response Time ms 9. Max. OVP Reset Time 10. Over-temperature Protection (OTP) s ----- 11. Phase-Loss Protection 1.5 FRONT PANEL 1.Control Functions 2.Display 3.Indications 1.6 DIGITAL PROGRAMMING & READBACK 1. Vout Programming Accuracy 2. Iout Programming Accuracy 3. Vout Programming Resolution 4. Iout Programming Resolution 5. Vout Readback Accuracy 6. Iout Readback Accuracy 7. Vout Readback Resolution 8. Iout Readback Resolution 9. OV Response Time 10. Other Functions 125-120 125 120 15.0 mA 1.3 PROTECTIVE FUNCTIONS 1. OCP 2. OCP type 3. Foldback Protection (FOLD) 4. Foldback Response Time 5. OVP type 6. OVP Programming Accuracy 1.4 REMOTE ANALOG CONTROLS & SIGNALS 1. Vout Voltage Programming 2. Iout Voltage Programming 3. Vout Resistor Programming 4. Iout Resistor Programming 5. Shut-Off (SO) Control (rear panel) 6. Output Current Monitor 7. Output Voltage Monitor 8. Power Supply OK (PS_OK) Signal 9. CV/CC Signal 10. Enable/Disable 11. Remote/Local Selection 12. Remote/Local Signal N/A 30-500 40-375 50-300 60-250 80-187.5 100-150 --30 40 50 60 80 100 --500 375 300 250 187.5 150 --15.0 15.0 15.0 15.0 15.0 15.0 --88 Contact Factory for other models 15kW X X X X X X GEN VDC ADC kW % 0 ~ 100 Constant current Output shutdown; Manual reset by front panel OUT button or DIgital communication, user-selectable Less than 1 (Min = 0.25 / Max = 25 / Default = 0.25); Settable via "FBD" command Inverter shut-down; Manual reset by AC On/Off recycle, OUT button, Remote Analog or Digital communication 5% of Vo(rated) 5% to to 105% of Vo(rated) - for Vor < 600V; 10% to 105% of Vo(rated) - 600V < Vor < 1500V Shall always be greater than 105% of Vo(setting); Default = 105% of Vo(rated) Less than 10 (for Output to begin to drop) for Vor < 600V Less than 2.0 (for Output to begin to drop) for 600V < Vor < 1500V 7 (from AC On/Off switch turn On) Shut down if internal temperature exceeds safe operating levels (Latched: Safe / Unlatched: Auto) Yes, power supply shutdown (Latched: Safe-Start / Unlatched: Auto-Restart) X X X X X X X X X X X 0~100%, 0 ~ 5V or 0 ~ 10V, user-selectable., Accuracy & Linearity: 1% of Vo(rated) 0~100%, 0 ~ 5V or 0 ~ 10V, user-selectable, Accuracy & Linearity: 1% of Io(rated) 0~100%, 0 ~ 5/10kohm full-scale, user-selectable, Accuracy & Linearity: 1% of Vo(rated) 0~100%, 0 ~ 5/10kohm full-scale, user-selectable, Accuracy & Linearity: 1% of Io(rated) By Voltage: 0.6V = DIS, 2-15V = ENA (default) or Dry Contact: Open = ENA, Short = DIS (user-selectable logic) 0 ~ 5V or 0 ~ 10V, Accuracy: 1% of Io(rated), user-selectable 0 ~ 5V or 0 ~ 10V, Accuracy: 1% of Vo(rated), user-selectable Yes. TTL High = OK, 0V = Fail (500ohm series impedance) CV: TTL High (4 ~ 5V), Max source current = 10mA; CC: TTL Low (0 ~ 0.4V), Max sink current = 10mA Dry contact; Open = OFF, Short = ON; Maximum voltage across Enable/Disable contacts = 6V Selects Remote or Local operation by voltage: 0 ~ 0.6V = Local / 2 - 15V = Remote Signals operating mode; Open collector: Local = Open (Max voltage = 30V), Remote = On (Max sink current = 10mA) X X X X X X X X X X X X Vout/ Iout manual adjust by separate encoders (COARSE and FINE adjustment selectable) OVP/UVL manual adjust by VOLTAGE Adjust encoder, Front Panel Lock/Unlock Address selection by VOLTAGE Adjust encoder. # of Addresses = 31 AC ON/OFF, Output On/Off, Restart Modes (Auto/Safe), Foldback Control (CV to CC), Go-to-Local RS-232/RS-485, LAN, IEEE (IEMD) and USB selection by rear panel DIP-switch Baud rate selection (RS-232/RS-485 only): 1200, 2400, 4800, 9600 and 19,200 (by Current Adjust encoder) Advanced Parallel Master/Slave: Hx = Master unit, where x = # of Slave units (0 to 4); S = Slave unit(s) Voltage: 4 digits, Accuracy: 0.5% of Vo(rated) 1 count Current: 4 digits, Accuracy: 0.5% of Vo(rated) 1 count VOLTAGE meter displays voltage at power supply (Local sense) or at load (Remote sense) Green LED's: PREVIEW, FOLD, REM./LOCAL, OUT ON/OFF, CV/CC, FINE Red LED:.ALARM (OVP, OTP, FOLD, AC FAIL, ENA, SO) X X X X X X X X X X 0.5% of Vo(rated) 0.5% of Io(rated) for units with Io < 187.5A; 0.7% of Io(rated) for Io 187.5A 0.02% of Vo(rated) 0.04% of Io(rated) (0.1% of Vo(actual) + 0.2% of Vo(rated)) (0.1% of Io(actual) + 0.4% of Io(rated)) 0.02% of Vo(rated) 0.02% of Io(rated) 20ms maximum (between Vout exceeding IEEE Limit and supply Inhibit turning On) Set OVP/UVL limits, Set Local/Remote, Operating parameters and Status, Get Identity X X X X X X X X X X *1. Ripple and Noise at Vo(rated) and rated Load, Ta = 25C and nominal AC input, per EIJ R9002A. *2. Time for the Output voltage to recover within 2% of rating for a load current change of 50~100% or 100-50% of rated Output. *3. From 20% - 100% for models with Ior < 25A. *4. Operating with a load that continuously pulses the current (or voltage) can reduce the operating life of the Power Supply. Please contact TDK-Lambda Sales/Technical Support to discuss the application in detail. *5. CV Mode: from 5% to 100% of Irated (over 5% to 100% of Prated); CC Mode: from 20% to 100% of Vrated (over 20% to 100% of Prated). All specifications subject to change without notice. 5 GenesysTM 3U 10/15kW GenesysTM 3U 15kW Specifications 1.0 MODEL GEN 150-100 200-75 250-60 300-50 400-37.5 500-30 600-25 800-18.8 1000-15 1250-12 1500-10 15kW X 1.Rated Output Voltage VDC 150 200 250 300 400 500 600 800 1000 1250 1500 X 2.Rated Output Current ADC 100 75 60 50 37.5 30 25 18.8 15 12 10 X kW % 15.0 15.0 15.0 15.04 15.0 15.0 15.0 X X X mV 75 100 125 150 200 250 300 400 500 625 750 X 75 100 125 150 200 250 300 800 1000 1250 1500 X 140 1400 5 X X X X X X X X X 3.Rated Output Power 4.Efficiency (min) at low AC line, 100% Rated Load 1.1 CONSTANT VOLTAGE MODE (CV) 1. Max. Line Reg (0.1% - Vor 30V; 0.05% - 30V < Vor < 600V; 0.05% - 600V < Vor < 1500V) 2. Max. Load Reg (0.1% - Vor 30V; 0.05% - 30V < Vor < 600V; 0.1% - 600V < Vor < 1500V); (*5) 3. Output Ripple, rms (5Hz~1MHz), CV mode; (*1) 4. Output Noise, p-p (20MHz), CV mode; (*1) 5.Remote Sense Compensation / Wire 6. Temperature Stability 7. Temperature Coefficient 8. Up-Prog. Response Time, 0~Vomax, full-load 9. Up-Prog. Response Time, 0~Vomax, no load 10. Transient Response Time (CV mode); (*2), (*4) 1.2 CONSTANT CURRENT MODE (CC) 1. Max. Line Reg (0.1% - Ior 333A; 0.050% - Ior < 333A) 2. Max. Load Reg (0.1% - Ior 333A; 0.075% - 25A < Ior < 333A; 0.2% - Ior < 25A); (*3), (*5) 3. Output Ripple, rms (5Hz~1MHz), CC mode 4. Temperature Stability 5. Temperature Coefficient mV mV mV V --ppm / C ms ms ms 15.0 15.0 15.0 15.0 88 Contact Factory for other models 93.5 25 35 35 60 60 60 60 80 100 120 150 175 200 200 300 350 350 700 800 1000 5 5 5 5 5 5 5 5 5 5 0.05% of Vo(rated) over 8 hours, after 30 minute warm up, constant Line, Load & Temperature 200 (0.02% of Vo(rated)) / C 100 17 50 17 Less than 3 Less than 1 mA 50 38 30 25 19 15 13 28 23 18 15 mA 75 57 45 38 28 23 19 38 30 24 20 X 4 X X X mA --ppm / C 1.3 PROTECTIVE FUNCTIONS 1. OCP 2. OCP type 3. Foldback Protection 4. Foldback Response Time 5. OVP type 6. OVP Programming Accuracy % ----s --% 7. OVP Trip Point V 50 20 20 20 10 10 10 15 10 6 0.05% of Io(rated) over 8 hours after 30 minute warm up (constant Line, Load & Temperature) 300 ( 0.03% of Io(rated)) / C 0 ~ 100 Constant current Output shut down; Manual reset by front panel OUT button or DIgital communication, user-selectable Less than 1 (Min = 0.25 / Max = 25 / Default = 0.25); Settable via "FBD" command Inverter shut-down; Manual reset by On/Off recycle, OUT button, Remote Analog or Digital communication 5% of Vo(rated) 5% to to 105% of Vo(rated) - for Vor < 600V; 10% to 105% of Vo(rated) - 600V < Vor < 1500V Shall always be greater than 105% of Vo(setting); Default = 105% of Vo(rated) 8. OVP response time ms Less than 10 (for Output to begin to drop) for Vor < 600V Less than 2.0 (for Output to begin to drop) for 600V < Vor < 1500V 9. Max. OVP reset time 10. Over temperature Protection s ----- 7 (from AC On/Off switch turn On) Shut down if internal temperature exceeds safe operating levels (Latched: Safe / Unlatched: Auto) Yes, power supply shutdown (Latched: Safe-Start / Unlatched: Auto-Restart) 11. Phase Loss Protection 1.4 REMOTE ANALOG CONTROLS & SIGNALS 1. Vout Voltage Programming 2. Iout Voltage Programming 3. Vout resistor programming 4. Iout Resistor Programming 5. Shut-Off (SO) Control (rear panel) 6. Output Current Monitor 7. Output Voltage Monitor 8. Power Supply OK (PS_OK) Signal 9. CV/CC Signal 10. Enable/Disable 11. Remote/Local Selection 12. Remote/Local Signal 1.5 FRONT PANEL 1.Control Functions 2.Display 3.Indications 1.6 DIGITAL PROGRAMMING & READBACK 1. Vout Programming Accuracy 2. Iout Programming Accuracy 3. Vout Programming Resolution 4. Iout Programming Resolution 5. Vout Readback Accuracy 6. Iout Readback Accuracy 7. Vout Readback Resolution 8. Iout Readback Resolution 9. OV Response Time 10. Other Functions X X X X X X X X X X X 0~100%, 0 ~ 5V or 0 ~ 10V, user-selectable, Accuracy & Linearity: 1% of Vo(rated) 0 ~ 100%, 0~5V or 0 ~ 10V, user-selectable. Accuracy & Linearity 1% of Io(rated) 0~100%, 0~5/10kohm full-scale, user-selectable. Accuracy & Linearity 1% of Vo(rated) 0~100%, 0~5/10kohm full-scale, user-selectable. Accuracy & Linearity 1% of Io(rated) By Voltage: 0.6V = DIS, 2-15V = ENA (default) or Dry Contact: Open = ENA, Short-DIS (user-selectable logic) 0 ~ 5V or 0 ~ 10V, Accuracy: 1% of Io(rated), user-selectable 0 ~ 5V or 0 ~ 10V, Accuracy: 1% of Vo(rated), user-selectable Yes. TTL High = OK, 0V = Fail (500ohm series impedance) CV: TTL High (4 ~ 5V), Max source current = 10mA; CC: TTL Low (0 ~ 0.4V), Max sink current = 10mA Dry contact; Open = OFF, Short = ON; Max. voltage across Enable/Disable contacts = 6V Selects Remote or Local operation by voltage: 0 ~ 0.6V = Local / 2 - 15V = Remote Signals operating mode; Open collector: Local = Open (Max voltage = 30V), Remote = On (Max sink current = 10mA) X X X X X X X X X X X X Vout/ Iout manual adjust by separate encoders (COARSE and FINE adjustment selectable) OVP/UVL manual adjust by VOLTAGE Adjust encoder, Front Panel Lock/Unlock Address selection by VOLTAGE Adjust encoder. # of Addresses = 31 AC ON/OFF, Output On/Onn, Restart Modes (Auto/Safe), Foldback Control (CV to CC), Go-to-Local RS232/RS-485, LAN, IEEE (IEMD) and USB selection by rear panel DIP-switch Baud rate selection (RS-232/RS-485 only): 1200, 2400, 4800, 9600 and 19,200 (by CURRENT Adjust encoder) Advanced Parallel Master/Slave: Hx = Master unit, where x = # of Slave units (0 to 4); S = Slave unit(s) Voltage: 4 digits, Accuracy: 0.5% of Vo(rated) 1 count Current: 4 digits, Accuracy: 0.5% of Io(rated) 1 count VOLTAGE meter displays Voltage at power supply (Local sense) or at load (Remote sense) Green LED's: PREVIEW, FOLD, REM./LOCAL, OUT ON/OFF, CV/CC, FINE Red LED:.ALARM (OVP, OTP, FOLD, AC FAIL, ENA, SO) X X X X X X X X X X 0.5% of Vo(rated) 0.5% of Io(rated) for units with Io < 187.5A; +/-0.7% of Io(rated) for Io 187.5A 0.02% of Vo(rated) 0.04% of Io(rated) (0.1% of Vo(actual) + 0.2% of Vo(rated)) (0.1% of Io(actual) + 0.4% of Io(rated)) 0.02% of Vo(rated) 0.02% of Io(rated) 20ms maximum (between Vout exceeding OVP Limit and supply inhibit turning On) Set OVP/UVL limits, Set Local/Remote, Operating parameters and Status, Get Identity X X X X X X X X X X X *1. Ripple and Noise at Vo(rated) and rated Load, Ta = 25C and nominal AC input, per EIJ R9002A. *2. Time for the Output voltage to recover within 2% of rating for a load current change of 50~100% or 100-50% of rated Output. *3. From 20% - 100% for models with Ior < 25A. *4. Operating with a load that continuously pulses the current (or voltage) can reduce the operating life of the Power Supply. Please contact TDK-Lambda Sales/Technical Support to discuss the application in detail. *5. CV Mode: from 5% to 100% of Irated (over 5% to 100% of Prated); CC Mode: from 20% to 100% of Vrated (over 20% to 100% of Prated). All specifications subject to change without notice. 6 General Specifications, GenesysTM 3U 10kW/15kW 2.1 INPUT CHARACTERISTICS 1. Input Voltage / Frequency (range) 2. No. of phases 3. Dropout Voltage 4. Input Current (180VAC/342VAC or 360VAC/432VAC) ----V Arms 5. Inrush Current A 6. Power Factor, passive (typical) --- 7. Leakage Current 8. Input Protection 10. Phase Imbalance mA --% 2.2 POWER SUPPLY CONFIGURATION 1. Parallel Operation; (*6) 2. Series Operation (*6) 208VAC (180-253), 400VAC (342-440 for Vout > 30V; 360-440 for Vout < 30V), 480VAC (432-528); 47-63Hz (all) 3-Phase (Wye or Delta) 4 wire total (3 phases and 1 Protective Earth (PE) ground) 180 / (342/360) / 432 10kW - 45/23/20 (Vout < 600V); 40/23/20 (800V < Vout < 1500V) - at full rated Output power 15kW - 64/32/27 (Vout < 600V); 55/32/27 (800V < Vout < 1500V) - at full rated Output power Not to exceed full rated Input current (see 2.1.4 (Input Current)) Vout < 600V: 0.88 (passive), 10kW/15kW (208VAC, 400VAC, 480VAC) Vout > 600V: 0.90/0.93 - 10kW/15kW (208VAC), 0.89/0.92 - 10kW/15kW (400VAC), 0.84/0.88 - 10kW/15kW (480VAC) 3.5 maximum (EN60950) Circuit breaker: 208VAC, (Vout < 30V); Line fuse: 208VAC (Vout > 30V) and 400VAC/480VAC (all models) 5% on three-phase Input Up to four (4) identical units may be connected in Master/Slave Mode with Single-Wire/Two-Wire connection. In "Advanced-Parallel", the current of Master unit multiplied by number of units connected in parallel is available via digital interface and displayed on the front panel display of the Master unit. Remote Analog current monitor of Master unit is scaled to the Output current of the Master unit (only) Possible (with external diodes); Up to two identical units with total Output voltage not to exceed 600V from Chassis ground (for Vor < 600V) or not to exceed 1500V from Chassis ground (for 600V < Vor < 1500V) 2.3 ENVIRONMENTAL CONDITIONS 1. Operating Temperature 2. Storage Temperature 3. Operating Humidity 4. Storage Humidity 5. Vibration & Shock 0 to +50C, 100% load -20 to +70C 20 to 80% RH (non-condensing) 10 to 90% RH (non-condensing) 6. Altitude 7. Audible Noise Operating: +50C up to 7500ft. (2500m), +45C from 7501 to 10,000ft (2501m - 3000m), Non-Operating 40,000ft (12,000m) 70dBA at Io(rated) (measured 1m from front panel) for Vout < 30V; 65dBA at Io(rated) (measured 1m from front panel) for Vout > 30V 2.4 EMC 1. 208VAC Input (all models) 1. ESD 2. Fast Transients 3. Surge Immunity 4. Conducted Immunity 5. Radiated Immunity 6. Power Frequency Magnetic Field 7. Conducted Emissions 8. Radiated Emissions 2. 400VAC (all models) /480VAC Input (Vout > 30V) 1. ESD 2. Fast Transients 3. Surge Immunity 4. Conducted Immunity 5. Radiated Immunity 6. Power Frequency Magnetic Field 7. Voltage Dips, Short Interruptions and Voltage Variations Immunity Test (400VAC Only) 8. Conducted Emissions 9. Radiated Emissions 2.5 SAFETY 1.Applicable Standards 2. Withstand Voltage: (208VAC/400VAC/480VAC; for 60 seconds); (*7) ASTM D4169, Standard Practice for Performance Testing of Shipping Containers and Systems, Shipping Unit: Single Package Assurance Level: Level II; Acceptance Criteria: Criterion 1 - No product damage Criterion 2 - Packaging is intact, Distribution Cycle: 12 Air (intercity) and motor freight (local), unitized is used. CE Mark EN61000-4-2 (IEC 801-2): Air-discharge 8kV , Contact-discharge 4kV EN61000-4-4 (IEC 1000-4-3) EN61000-4-5 (IEC 1000-4-5) EN61000-4-6 (IEC 1000-4-6) EN61000-4-3 (IEC 1000-4-3) EN61000-4-8 EN55011A, FCC part 15J-A EN55011A, FCC part 15J-A CE Mark EN61000-4-2 (IEC 801-2): Air-discharge 8kV , Contact-discharge 4kV EN61000-4-4 (IEC 1000-4-3) EN61000-4-5 (IEC 1000-4-5) EN61000-4-6 (IEC 1000-4-6) EN61000-4-3 (IEC 1000-4-3) EN61000-4-8 IEC 61000-4-11 EN55011A, FCC part 15J-A EN55011A, FCC part 15J-A UL/cUL 60950-1, EN60950-1 recognized, CB Scheme, CE Mark (208VAC, 400VAC and 480VAC) 7.5V < Vout < 400V: Output is Hazardous; LAN/IEEE/USB/Isolated Analog are SELV 400V < Vout < 600V: Output is Hazardous; LAN/IEEE/USB/Isolated Analog are not SELV 600V < Vout < 1500V: Output is Hazardous; LAN/IEEE/USB/Isolated Analog are SELV Vout < 80V: Input - Ground: 2200VDC/2900VDC/2900VDC, Input-Hazardous Output: 2200VDC/3100VDC/3100VDC, Input - SELV: 2200VDC/2900VDC/2900VDC; Hazardous Output - SELV: 900VDC/900VDC/900VDC, Hazardous Output - Ground: 900VDC/900VDC/900VDC. 80V < Vout < 300V: Input - Ground: 2200VDC/2900VDC/2900VDC, Input-Hazardous Output: 2200VDC/3500VDC/3500VDC, Input - SELV: 2200VDC/2900VDC/2900VDC; Hazardous Output - SELV: 900VDC/900VDC/900VDC, Hazardous Output - Ground: 900VDC/900VDC/900VDC. 300 < Vout < 600V models: Input-Ground: 2200VDC/2900VDC/2900VDC, Input-Hazardous Output: 3300VDC/3900VDC/3900VDC, Input-SELV: 2200VDC/2900VDC/2900VDC, Hazardous Output - SELV: 900VDC/900VDC/900VDC, Hazardous Output - Ground: 900VDC/900VDC/900VDC 600 < Vout < 1500V models: Input-Ground: 2200VDC/2900VDC/2900VDC, Input-Hazardous Output: 4500VDC/5040VDC/5040VDC, Input-SELV: 2900VDC/2900VDC/2900VDC, Hazardous Output - SELV: 2500VDC/2500VDC/2500VDC, Hazardous Output - Ground: 2500VDC/2500VDC/2500VDC 3.Insulation Resistance 2.6 MECHANICAL CONSTRUCTION 1. Cooling 20Megohms (typical) at 500VDC, Ta = +25C 6.Control Connectors 7. Mounting Method 8. Output Ground Connection Fan-driven with airflow from front to rear. Fan-speed control on models with Vout > 30V "Zero Stackable" top and bottom. Vents on side shall not be blocked. Chassis slides or suitable rear support required. EIA rack mounting Width: 429mm / 16.9"; Height: 3U - 133mm / 5.22" Depth: 564mm / 22.2" for Vout < 600V, 581mm / 22.9" for 800V < Vout < 1500V; excluding connectors, encoders, handles, etc. 43kg / 97 lbs (Vout < 600V); 32kg / 70lbs (Vout > 600V) M6 x 1" (25.4mm) threaded studs (L1, L2, L3 and Chassis GND) and terminal cover. Busbars: Vout < 25V: (two-hole busbars); 30V < Vout < 300V: busbars (one hole busbars) Threaded-stud terminals: 400V < Vout < 600V: M6 x 0.5" (12.7mm) threaded-stud; 800V < Vout < 1500V: M6 x 1.0" (25.4mm) threaded-stud Analog Programming: DB25, plastic connector, AMP747461-5, Female on Supply; Male on Mating connector, 747321, 25 pin Sub-D connector. Standard 19" Rack-Mount, provision for standard chassis slides. Side/Rear Support is required; Do not mount by front panel only M5 x 0.91" (23mm) threaded-stud 2.7 WARRANTY 1. Warranty 5 years 2. Dimensions (W x H x D) 3. Weight 4. AC Input connector (with Protective Cover) 5.Output Connectors (busbar) *6. Please contact TDK-Lambda Sales/Technical Support to discuss your Parallel or Series application in more detail. *7 Please contact TDK-Lambda Sales/Technical Support to discuss your System-Level Withstand Voltage requirements in more detail. All specifications subject to change without notice. 7 GenesysTM 3U 10/15kW GenesysTM Power Parallel and Series Configurations Parallel Operation - Master/Slave (*6) Active current sharing allows up to four identical units to be connected in an Auto-parallel configuration for the Output power. In Advanced Parallel Master/Slave Mode, total current is programmed and reported by the Master, Up to four 10kW/15kW Power Supplies in parallel act as one 40kW/60kW Power Supply. Series Operation (*6) Up to two units may be connected in series to increase the Output voltage or to provide bipolar output. (Max 600V to Chassis GND for Vor < 600V; Max 1500V to Chassis GND for 600V < Vor < 1500V). Remote Programming via RS-232 & RS-485 Interface Standard Serial Interface allows daisy-chain control of up to 31 power supplies on the same communication bus with built-in RS-232 & RS-485 Interface or optional LAN, USB or IEEE Interface. RS-232, RS-485 LAN, IEEE or USB RS-485 Link Programming Options (Factory installed) Standard RS-232/RS-485 (Multi-Drop) Interface P/N: "-----" LAN Interface ( P/N: LAN (for all models) * * * * * * Standard Units are equipped with the RS-485 Multi-Drop function Allows RS-232 or RS-485 Master unit to control up to 30 (standard) Slave units using RS-485 daisy-chain Compliant w/ Multi-Drop) Meets all LXI Class C Requirements Address Viewable on Front Panel Fixed and Dynamic Addressing Fast Startup * * * * VISA & SCPI Compatible LAN Fault Indicators Auto-detects LAN Cross-over Cable Compatible with most standard Networks IEEE (Multi-Drop) Interface P/N: IEMD (for all models) * * * * * IEEE 488.2 & SCPI compliant Allows IEEE Master to control up to 30 (standard) Slave units using RS-485 daisy-chain Program/Measure Voltage* Program/Measure Current Over-Voltage setting and shutdown * Current Foldback shutdown Error and Status Messages USB (Multi-Drop) Interface P/N: USB (for all models) * * * * USB 2.0 compliant Allows serial connection to computer USB port Allows USB Master to control up to 30 (standard) Slaves using RS-485 daisy-chain Uses same command set as standard RS-232/RS-485 interface Isolated Analog Programming * * * * * * Option for models with Vout < 600V (IS510 & IS420); IS510 built-in for models where 800V < Vout < 1500V Four Channels total (Two channels to Program Voltage and Current; Two channels to Monitor Voltage and Current) Isolation allows operation with floating references in harsh electrical environments Choose between programming with Voltage or Current Connection via removable terminal block: Phoenix MC1,5/8-ST-3.81 Voltage Programming, User-selectable 0-5V or 0-10V signal Power supply Voltage and Current Programming Accuracy: 1.0% * Power supply Voltage and Current Monitoring Accuracy: 1.5% Current Programming with 4-20mA signal Power supply Voltage and Current Programming Accuracy: 1.0% P/N: IS510 (for Vout < 600V) P/N: IS420 (for all models) Power supply Voltage and Current Monitoring Accuracy: 1.5% 8 Outline Drawing: GenesysTM 10kW/15kW (7.5V to 25V - 208VAC/400VAC/480VAC) 12 J2 SW1 J3 J1 J2 RS 485/232 OUT J1 SW1 IN CAUTION: TORQUE TERMINAL TO 32 IN-LBS. (3.5NM) J3 RS 485/232 OUT IN CAUTION: TORQUE TERMINAL TO 32 IN-LBS. (3.5NM) NOTES: 1. Busbars for models where Vout < 30V Output: two holes 0.42" (10.72mm) diameter. 2.N/A 3.N/A 4. Input Terminals: M6 x 1" (Qty = 3); Ground Terminal: M5 x 1" (Qty = 2) 5. Mounting for Slide Mounts (not included). Recommend: General Devices, Chassis Trak P/N C230-S-122; Verify requirements with slide manufacturer. Secure with pan head screw: M5 x 0.8-8mm long (max). 9 GenesysTM 3U 10/15kW Outline Drawing: GenesysTM 10kW/15kW (30V to 300V - 208VAC/400VAC/480VAC) 22.85 580.39 2.50 63.45 0.422 THRU 10.72 88.46 2.70 68.49 4.75 120.65 1.10 28.05 8.63 219.08 12.50 317.50 16.38 415.93 L1 L2 L3 NOTES: 1.N/A 2. Bus bars for models 30-300V Output (10kW/15kW): one hole 0.42" (10.72mm) diameter. 3.N/A 4. Input Terminals: M6 x 1" (Qty = 3) + Ground M5 x 1" (Qty = 2) 5. Mounting for Slide Mounts (not included). Recommend General Devices, Chassis Trak P/N C230-S-122; Verify requirements with slide manufacturer. Secure with pan head screw: M5 x 0.8-8mm long (max). 10 Outline Drawing: GenesysTM 10kW/15kW (400V to 600V - 208VAC/400VAC/480VAC) 2.30 58.37 22.85 580.39 3.48 88.46 4.75 120.65 8.63 219.08 12.50 317.50 16.38 415.93 3 L1 L2 L3 NOTES: 1.N/A 2.N/A 3. Threaded-stud terminals for models with 300V < Vout < 600V (M5 x 1"). 4. Input Terminals M6 x 1" (Qty = 3) + Ground M5 x 1" (Qty = 2) 5. Mounting for Slide Mounts (not included). Recommend General Devices, Chassis Trak P/N C230-S-122; Verify requirements with slide manufacturer. Secure with pan head screw: M5 x 0.8-8mm long (max). 11 GenesysTM 3U 10/15kW Outline Drawing: GenesysTM 10kW/15kW (800V to 1500V - 208VAC/400VAC/480VAC) 2.00 50.80 22.85 580.39 88.46 4.75 120.65 8.63 219.08 12.50 317.50 16.38 415.93 3 L1 L2 L3 NOTES: 1.N/A 2. N/A 3. Threaded stud terminals for models with 800V < Vout < 1500V Output (M5 x 1"). 4. Input Terminals M6 x 1" (Qty = 3) + Ground M5 x 1" (Qty = 2) 5. Mounting for Slide Mounts (not included). Recommend General Devices, Chassis Trak P/N C230-S-122; Verify requirements with slide manufacturer. Secure with pan head screw M5 x 0.8-8mm long (max). 12 Power Supply Identification / Accessories (GenesysTM 3U 10kW/15kW) How to Order: GEN Series Name 10 Output Voltage (0~10V) Output Voltage (Vdc) Model - 1000 - Output Current (0~1000A) Output Current (Adc) Output Power (kW) LAN - 3P208 Factory Options AC Input Options Option: "-----" LAN IEMD USB IS510 IS420 3P208 (Three-Phase 208VAC) 3P400 (Three-Phase 400VAC) 3P480 (Three-Phase 480VAC) Model GEN 7.5-1000 0~7.5 0~1000 7.5 GEN 200-50 GEN 10-1000 0~10 0~1000 10 GEN 200-75 GEN 12.5-800 0~12.5 0~800 10 GEN 250-40 GEN 20-500 0~20 0~500 10 GEN 250-60 GEN 25-400 0~25 GEN 30-333 0~30 GEN 30-500 GEN 40-250 0~40 GEN 40-375 GEN 50-200 0~50 GEN 50-300 GEN 60-167 0~60 GEN 60-250 GEN 80-125 0~80 GEN 80-187.5 GEN 100-100 0~100 GEN 100-150 GEN 125-80 0~125 GEN 125-120 GEN 150-66 0~150 GEN 150-100 0~400 10 GEN 300-33 0~333 10 GEN 300-50 0~500 15 GEN 400-25 0~250 10 GEN 400-37.5 0~375 15 GEN 500-20 0~200 10 GEN 500-30 0~300 15 GEN 600-17 0~167 10 GEN 600-25 0~250 15 *GEN 800-12.5 0~125 10 *GEN 800-18.8 0~187.5 15 *GEN 1000-10 0~100 10 *GEN 1000-15 0~150 15 *GEN 1250-8 0~80 10 *GEN 1250-12 0~120 15 *GEN 1500-6.7 0~66 10 *GEN 1500-10 0~100 15 Output Voltage (Vdc) Output Current (Adc) 0~200 0~250 0~300 0~400 0~500 0~600 0~800 0~1000 0~1250 0~1500 0~50 10 0~75 15 0~40 10 0~60 15 0~33 10 0~50 15 0~25 10 0~37.5 15 0~20 10 0~30 15 0~17 10 0~25 15 0~12.5 10 0~18.8 15 0~10 10 0~15 15 0~8 10 0~12 15 0~6.7 10 0~10 15 Factory optionsP/N RS-232/RS-485 Multi-Drop Interface (built-in standard) LAN Interface ( Class C compliant w/ Multi-Drop) GPIB (488.2 w/ Multi-Drop) Interface USB (2.0 w/ Multi-Drop) Interface Isolated Analog Interface (Voltage Program/Monitor) Isolated Analog Interface (Current Program/Monitor) "------" LAN IEMD USB IS510 *(built-in standard on 800-1500V models) IS420 Accessories 1. Serial Communication cable (optional) RS-232/RS-485 cable is used to connect the power supply to the Host PC. Mode RS-485 RS-232 RS-232 PC Connector DB-9F DB-9F DB-25F Communication Cable Shield Ground, L=2m Shield Ground, L=2m Shield Ground, L=2m Power Supply Connector EIA/TIA-568A (RJ-45) EIA/TIA-568A (RJ-45) EIA/TIA-568A (RJ-45) P/N GEN/485-9 GEN/232-9 GEN/232-25 2. Serial Link cable (optional) Daisy-chain up to 31 GenesysTM power supplies. Mode Power Supply Connector Communication Cable P/N RS-485 EIA/TIA-568A (RJ-45) Shield Ground, L=50cm GEN/RJ45 13 GenesysTM 3U 10/15kW Output Power (kW) GenesysTM Family - Output Voltage / Output Current Model GENH Rated Power 750W GEN-1U 750W 1.5kW GEN-2U 2.4kW Voltage Range 0~6V 3.3kW 5.0kW 0~100A 0~200A 0~90A 0~90A 0~180A 0~60A 0~60A 0~300A 0~400A 0~600A 0~240A 0~330A 0~500A 0~120A 0~1000A 0~800A 0~15V 0~220A 0~16V 0~20V 15kW 0~1000A 0~10V 0~12.5V 10kW Output Current Range 0~100A 0~7.5V 0~8V GEN 3U 0~150A 0~38A 0~38A 0~76A 0~310A 0~120A 0~165A 0~250A 0~25V 0~500A 0~400A 0~30V (15kW) - NEW ! 0~25A 0~25A 0~50A 0~80A 0~110A 0~170A 0~333A 0~40V (15kW) - NEW ! 0~19A 0~19A 0~38A 0~60A 0~85A 0~125A 0~250A 0~375A 0~200A 0~300A 0~250A 0~50V (15kW) - NEW ! 0~30A 0~500A 0~60V 0~12.5 0~12.5A 0~25A 0~40A 0~55A 0~85A 0~167A 0~80V 0~9.5A 0~9.5A 0~19A 0~30A 0~42A 0~65A 0~125A 0~187.5A 0~100V 0~7.5A 0~7.5A 0~15A 0~24A 0~33A 0~50A 0~100A 0~150A 0~80A 0~120A 0~5A 0~5A 0~10A 0~16A 0~22A 0~34A 0~66A 0~100A 0~16.5A 0~25A 0~50A 0~75A 0~125V 0~150V 0~200V - NEW ! 0~250V 0~300V 0~40A 0~2.5A 0~33A 0~50A 0~400V (5.0kW) - NEW ! 0~12.5A 0~25A 0~37.5A 0~500V (5.0kW) - NEW ! 0~10A 0~20A 0~30A 0~8.5A 0~17A 0~25A 0~800V - NEW ! 0~12.5A (5) 0~18.8A (5) 0~1000V - NEW ! 0~10A (5) 0~15A (5) 0~1.3A 0~1.3A 0~5A 0~8A 0~2.6A 0~11A 0~60A 0~17A 0~600V 0~2.5A 0~4A 0~5.5A 0~1250V - NEW ! 0~8A 0~1500V - NEW ! Weight (kg/lb) (5) 0~6.7A 4.5 / 9.9 7.0 / 15.0 8.5 / 18.0 10 .0 / 22.0 13.0 / 29.0 (5) 0~12A (5) 0~10A (5) 16.0 / 35.0 43.0 / 97.0 43.0 / 97.0 32.0 / 70.0 (6) (6) 800V - 1500V models only (10kW/15kW) AC Inputs 85-265Vac, 1O * (1) * (1) * (1) 230Vac, 1O * (1 * (1) 208Vac, 3O * (1 * (1) * (1) * (3) * (3) 400Vac, 3O * (1) * (1) * (3) * (3) 480Vac, 3O * (2) - NEW ! * (2) - NEW ! * (3), (4) * (3), (4) (1) UL Listed; CE Mark (RoHS2); (2) UL Listed (RoHS2); (3) UL Recognized, CE Mark (RoHS2) - (Vout > 25V); 4) UL Recognized, RoHS2 (Vout < 25V) Options (All Models) "-----" Standard RS-232/RS-485 Master with RS-485 Multi-Drop capability installed LAN LXI Compliant LAN Interface (Class C) with RS-485 Multi-Drop capability installed IEMD IEEE Master (IEEE 488.2 & SCPI compliant) with RS-485 Multi-Drop capability installed USB USB (2.0) Master with RS-485 Multi-Drop capability installed IS510 Isolated Analog Program/Monitor (0-5V or 0-10V, user-selectable) for 6V-600V models; *(5) IS420 Isolated Analog Program/Monitor (4-20mA) All "Options" are factory installed and limited to one "option" per power supply *(5) Isolated 5V/10V (IS510) Interface is bulit-in standard for 800V-1500V models All specifications are subject to change without notice 14 GLOBAL NETWORK USA TDK-Lambda Americas Inc. 405 Essex Rd. Neptune, NJ 07753 Tel: +1-732-795-4100 Fax: +1-732-922-9334 E-Mail: sales@us.tdk-lambda.com Web: www.us.tdk-lambda.com/hp JAPAN TDK-Lambda Corporation International Sales Division, 3-9-1, Shibaura, Minato-ku, Tokyo 108-0023, Japan Tel: +81-3-6852-7125 Fax: +81-3-6852-7140 Web: www.jp.tdk-lambda.com CANADA ACA TMetrix 3835 Laird Road, Mississauga, Ontario, L5L 5Y4 Tel: +1-800-665-7301 Fax: +1-905-890-1959 E-Mail: lambda@aca.ca Web: tmetrix.com MEXICO AcMax de Mexico 39 Poniente 3515 Piso 5 Col. Las Animas Puebla, Pue. C.P. 72400 Tel: 01-800-211-0060 / (222) 891-8484 Fax: 222-264-1445 E-Mail: info@acmax.mx, Web: www.acmax.mx BRAZIL Supplitec Rua Sena Madureira 465 31340-000 Belo Hte - MG-Brazil Tel: +55-31-3498-1177 E-Mail: vendas@suplitec.com.br, Web: www.suplitec.com.br SCANDINAVIA BALTICS TDK-Lambda Germany GmbH Karl-Bold-Strasse 40 D-77855 Achern, Germany Tel: +49-7841-666-0 Fax: +49-7841-500-0 E-Mail: info.germany@de.tdk-lambda.com Web: www.de.tdk-lambda.com Shenzen Branch of Wuxi TDK-Lambda Electronics Co. Ltd. 69/F, Ping An Finance Center, 5033 Yitian Road Futian District, Shenzen, P. R. CHINA Tel: +86-755-83588261 Fax: +86-755-83588260 Web: www.cn.tdk-lambda.com SWITZERLAND MALAYSIA TDK-Lambda Malaysia Sdn. Bhd. c/o TDK (Malaysia) Sdn Bhd., Lot 709, Nilai Industrial Estate 71800 Nilai Negeri Sembilan, Malaysia Tel: +60-6-799-1130 Fax: +60-6-799-3277 Web: www.my.tdk-lambda.com SINGAPORE PHILIPPINES TDK-Lambda Singapore Pte. Ltd. 1008 Toa Payoh North # 06-01/08, #07-01/03 Singapore 318996 Tel: +65-6251-7211 Fax: +65-6250-9171 Web: www.sg.tdk-lambda.com INDIA TDK-Lambda Singapore Pte. Ltd. (India Branch) No.989, 1st Cross, 2nd Floor, 13th Main, HAL 2nd Stage, Bangalore, Karnataka, India-560 008 Tel : +91-80-43550 500 Fax :+91-80-43550 501 E-Mail: mathew.philip@in.tdk-lambda.com Web: www.in.tdk-lambda.com ISRAEL RUSSIA TDK-Lambda Ltd. Israel Kibbutz Givat Hashlosha Tel-Aviv 48800, Israel Tel: +972-3-9024-333 Fax: +972-3-9024-777 E-Mail: info@tdk-lambda.co.il Web: www.tdk-lambda.co.il TDK-Lambda Americas Inc. 405 Essex Road, Neptune, NJ 07753 USA Tel: +1.732.795.4100 Fax: +1.732.922.9334 www.us.tdk-lambda.com/hp TDK Logo is a trademark or registered trademark of TDK Corporation (c) Copyright 2019, TDK-Lambda Americas Inc. THAILAND 93-530-001, Rev. L2 FRANCE NETHERLANDS SPAIN TDK-Lambda France SAS 3 Avenue du Canada, Parc Technopolis - Batiment Sigma 91940 Les Ulis - France CS 41077 Tel: +33 1 60 12 71 65 Fax: +33 1 60 12 71 66 E-Mail: france@fr.tdk-lambda.com, Web: www.fr.tdk-lambda.com ITALY TDK-Lambda Italy France Sas Succursale Italiana Via dei Lavoratori 128/130 IT 20092 Cinisello Balsamo, Milano, Italy Tel: +39-02-6129-3863 Fax: +39-02-6129-0900 E-Mail: info.italia@it.tdk-lambda.com Web: www.it.tdk-lambda.com Beijing Branch of Wuxi TDK-Lambda Electronics Co. Ltd. Room 12B11-12B12, Unit 7 Dacheng Square, No. 28 Xuanwumenxi Street, Xuanwu District Beijing, 100053, P.R. CHINA Tel: +86-10-6310-4872 Fax: +86-10-6310-4874 Web: www.cn.tdk-lambda.com KOREA TDK-Lambda Corporation Korea Branch (Seocho-Dong, 8F, Songnam Bldg.) 273, Gangnam-Daero, Seochu-Gu. Seoul 137-862, Republic of Korea 137-862 Tel: +82-2-3473-7051 Fax: +82-2-3472-9137 www.tdk-lambda.co.kr UK IRELAND TDK-Lambda UK Ltd. Kingsley Avenue Ilfracombe, Devon 34 8ES, United Kingdom Tel: +44-1271-856666 Fax: +44-1271-864894 E-Mail: powersolutions@uk.tdk-lambda.com Web: www.uk.tdk-lambda.com GERMANY AUSTRIA TDK-Lambda Germany GmbH Karl-Bold-Strasse 40 D-77855 Achern, Germany Tel: +49-7841-666-0 Fax: +49-7841-500-0 E-Mail: info.germany@de.tdk-lambda.com Web: www.de.tdk-lambda.com CHINA Wuxi TDK-Lambda Electronics Co. Ltd, Shanghai Office 5th Floor Kehui Tower, 1188 Qinzhou Road (North) Xuhui District Shanghai, 200233 P.R. CHINA Tel: +86-21-6485-0777 Fax: +86-21-6485-0666 Web: www.cn.tdk-lambda.com