5-Year Limited Warranty
High Efficiency: Level V
High Power Density
Lifetime Expectation >5 years
Hold-up Time > 25ms at full load
EISA, CEC Compliant
Floating output
Medical Approval- EN60601-1 Class I
120 Medical Desktop Power Supply
MWA120 Series
Elpac Part
Number
Output
Voltage
Output
Current
Peak
Current
Total
Regulation
Typical
Efficiency
MWA120012A-12A 12.0V 10.0A 12.0A ±5% 89%
MWA120015A-12A 15.0A 8.0A 10.0A ±5% 90%
MWA120018A-12A 18.0A 6.7A 8.0A ±5% 90%
MWA120024A-12A 24.0V 5.0A 6.0A ±5% 91%
MWA120048A-11A 48.0V 2.5A 3.0A ±5% 92%
Input
Input Voltage 85 - 264VAC; 100 - 240VAC Nominal
Input Frequency 47 - 63Hz
Input Current <2A rms
Inrush Current <37A at 230VAC cold start
Power Factor >0.97
Zero Load Power Consumption <0.5W
Output
Output Voltage See Table
Total Regulation +/-5%
Minimum Load No minimum load required
Start-Up Delay <1.5s
Hold-Up Time >25ms at any input voltage
Page 1 of 4MWA120 Series - ICCNexergy
5
/
31
/
201
3
htt
p
://www.iccnexer
gy
.com/el
p
ac/medica
l
-
p
owe
r
-su
pp
lies/external/mwa120-series/?ms=0
Ripple & Noise <1% pk-pk *
Over Voltage Protection 110-135%
Over Temperature Protection Active - Recoverable; plus Passive - Non Recoverable
Over Current Protetion 120 - 180%
Short Circuit Protection Shutdown, auto-restart (hiccup mode)
General
Efficiency Avg Efficiency 90% @ 115VAC; 92% @ 230VAC
MTBF min. 200,000 hours demonstrated
Size 7.56" (192mm) x 2.45" (62.2mm) x 1.52" (38.7mm)
Weight 1.55 lbs (0.70 kg)
Environmental
Operating Temperature 0 – 60°C (Full load to 40°C, derate linearly to 50% load at 60°C)
Storage Temperature -40°C to +85°C
Relative Humidity 5-95%, non-condensing
Cooling Natural Convection
Vibration All units production tested to 19.6m/s2
EMC & Safety
Emissions FCC class B, CISPR11 class B EN61000-3-2, -3
Immunity EN61000-4-2, -3, -4, -5, -6, -8, -11
Certified by TUV to the following: cTUVus
UL 60601-1
CAN/CSA-22.2 No.601.1-M90
CB per IEC60601-1
CE marked to LVD
Input Configuration
Standard Input Cable Not Provided
Connection on Power Supply Body IEC 320 C14 Receptacle
Page 2 of 4MWA120 Series - ICCNexergy
5
/
31
/
201
3
htt
p
://www.iccnexer
gy
.com/el
p
ac/medica
l
-
p
owe
r
-su
pp
lies/external/mwa120-series/?ms=0
Output Configuration (12V, 15V)
Standard Output Cable 4 ft.
Cord Size 2x16awg
Connector (PSU side) Switchcraft DIN-8,
P/N 15BL8M (male pins)
Mating Connector Switchcraft 62GB8FX (8 pin) or equivalent
Output Configuration (18V, 24V)
Standard Output Cable 6 ft.
Cord Size 2x16awg
Connector (PSU side) Switchcraft DIN-8,
P/N 15BL8M (male pins)
Mating Connector Switchcraft 62GB8FX (8 pin) or equivalent
Output Configuration (48V)
Standard Output Cable 6 ft.
Cord Size 2x18awg
Connector (PSU side) Switchcraft DIN-5,
P/N 05GM5M (male pins)
Mating Connector Switchcraft 57GB5FX (5 pin) or equivalent
Output Pin Assignments
Pin 1 Return
Pin 2 Return
Pin 3 +V1
Pin 4 Return
Pin 5 +V1
Output Pin Assignments
Page 3 of 4MWA120 Series - ICCNexergy
5
/
31
/
201
3
htt
p
://www.iccnexer
gy
.com/el
p
ac/medica
l
-
p
owe
r
-su
pp
lies/external/mwa120-series/?ms=0
Pin 1 +V1
Pin 2 +V1
Pin 3 Return
Pin 4 +V1
Pin 5 Return
Pin 6 +V1
Pin 7 Return
Pin 8 Return
MWA120 SERIES | ICCNEXERGY | © 2012 |