1
POWER ENTRY MODULES WITH LINE FILTER
5
51
14
45
5
www.schurter.com
5145
Inlet filter, front side mounting, circuit breaker TA45 2-pole Standard- or Medical-Filter
C14
70° C
D
De
es
sc
cr
ri
ip
pt
ti
io
on
n
- Panel Mount:
Screw-on from front side
- 3 Functions:
Inlet Protection class I, circuit breaker type TA45 2-pole, Line filter in
standard and medical version
- Quick connect terminals 6.3 x 0.8 mm
- Alternative: version without line filter 6145
- We recommend for new applications type DF12
A
Ap
pp
pr
ro
ov
va
al
ls
s
- VDE License Number: 117118
- UL License Number: E72928
C
Ch
ha
ar
ra
ac
ct
te
er
ri
is
st
ti
ic
cs
s
- All single elements are already wired
Unwired versions available on request
- Line switch non-illuminated or illuminated
Thermal overload protection
Optional with undervoltage release or remote trip release
- Qualified for use in equipment according IEC/EN 60950
W
We
eb
bl
li
in
nk
ks
s
Approvals: http://www.schurter.com/approvals
RoHS: http://www.schurter.com/rohs
T
Te
ec
ch
hn
ni
ic
ca
al
l D
Da
at
ta
a
Ratings IEC 1 - 10 A @ Ta 40 °C / 250 VAC; 50 Hz
Ratings UL/CSA 1 - 15 A @ Ta 40 °C / 125 VAC; 60 Hz
Leakage Current standard < 0.5 mA (250 V / 60 Hz)
medical < 5 µA (250 V / 60 Hz)
Dielectric Strength > 1.7 kVDC between L-N
> 2.7 kVDC between L/N-PE
Test voltage (2 sec)
Allowable Operation Temp. -10 °C to 55 °C
Climatic Category 10/055/21acc. to, IEC 60068-1
Degree of Protection from front side IP 40 acc. to IEC 60529
Protection Class Suitable for appliances with protection
class I acc. to IEC 61140
Terminal Quick connect terminals 6.3 x 0.8 mm
Panel Thickness s Screw-on: max 8 mm
Mounting screw torque max 0.5 Nm
Material: Housing Thermoplastic, black, UL 94V-0
Appliance-Inlet /-Outlet C14 acc. to IEC/EN 60320-1,
UL 498, CSA C22.2 no. 42 (for cold con-
dition) pin-temperature 70 °C, 10 A, Pro-
tection class I
Circuit breaker Acc. IEC/EN 60934, UL 1077, CSA 22.2
no. 235
2-pole rocker switch, illuminated or non-il-
luminated. Optional with undervoltage- or
remote trip release
Short circuit capacity Icn:
at In < 3A/240VAC : 10 x In
at In 3A/240VAC : 300A
Line Switch acc. to IEC 61058-1
Technical details
Line Filter Standard and Medical Version, IEC
60939, IEC 60601-1, UL 1283, UL 544,
EN 133 200, CSA C22.2 no. 8
Technical details
MTBF > 100'000 h acc. to MIL-HB-217 F
2
POWER ENTRY MODULES WITH LINE FILTER
5
51
14
45
5
www.schurter.com
D
Di
im
me
en
ns
si
io
on
ns
s
Length 67.5 mm
3.25
+0.1
0
±0.1
43
M3/ø 3.6
2
1
ø 6
Detail A
50.7
67.5* 13.5
6.3x0.8mm
6.3x0.8mm
36
80
91.5
72
80
R 3
29
0
-0.5
0
+0.2
A
* --- Version TA45 with undervoltage release
T
Te
ec
ch
hn
ni
ic
ca
al
l D
Da
at
ta
a o
of
f F
Fi
il
lt
te
er
r-
-C
Co
om
mp
po
on
ne
en
nt
ts
s
RRaatteedd CCuurrrreenntt
[[AA]]
FFiilltteerr--TTyyppeeIInndduuccttaanncceess
LL [[mmHH]]
CCaappaacciittaannccee
CCXX [[nnFF]]
CCaappaacciittaannccee
CCYY [[nnFF]]
RR [[MM]]
1Standard Version 2 x 11 47 2.2 -
2Standard Version 2 x 4 47 2.2 -
3 Standard Version 2 x 2.5 47 2.2 -
4 Standard Version 2 x 1.6 47 2.2 -
6 Standard Version 2 x 0.7 47 2.2 -
8 Standard Version 2 x 0.6 47 2.2 -
10 Standard Version 2 x 0.4 47 2.2 -
15 Standard Version 2 x 0.1 47 2.2 -
1Medical Version (M5) 2 x 11 47 - 1
2Medical Version (M5) 2 x 4 47 - 1
6Medical Version (M5) 2 x 0.7 47 - 1
8 Medical Version (M5) 2 x 0.6 47 - 1
10 Medical Version (M5) 2 x 0.4 47 - 1
15 Medical Version (M5) 2 x 0.1 47 - 1
D
Di
ia
ag
gr
ra
am
ms
s
Standard version
1) Line
2) Load
Medical version
1) Line
2) Load
3
POWER ENTRY MODULES WITH LINE FILTER
5
51
14
45
5
www.schurter.com
A
At
tt
te
en
nu
ua
at
ti
io
on
n l
lo
os
ss
s- - - - differential mode _____ common mode
Standard version
1 A 2 A 3 A 4 A
6 A 8 A 10 A 15A
Medical version (M5)
1 A 2 A 3 A 4 A
6 A 8 A 10 A 15A
P
Pa
ac
ck
ka
ag
gi
in
ng
g u
un
ni
it
t
20 Pcs
A
Ac
cc
ce
es
ss
so
or
ry
y
DDeessccrriippttiioonn
Assorted Covers
4
POWER ENTRY MODULES WITH LINE FILTER
5
51
14
45
5
www.schurter.com
ABT W F 150 C0
Colours
Switch front Rocker
Wblack white
Bblack black
6black – orange transp.
Fembossed
Hprinted white
Kprinted black
Lprinted white
Surface Illustration Colour of print
Rocker legend
l
O
ON
OFF
ON
OFF
l
O
Mprinted black
Pprinted white
Rprinted black
Surface Illustration Colour of print
InCode
10,0 100
11,0 110
12,0 120
InCode
13,0 130
14,0 140
15,0 150
InCode
16,0 160
17,0 170
18,0 180
InCode
19,0 190
20,0 200
Without release: code C0
Undervoltage release Remote trip release
P2 P1
U<
P2 P1
b
U<
P2 P1
ba
U<
P2 P1
c
U E Z A Code
Rated
voltage Un
2
3
4
240 V AC
230 V AC
120 V AC
l
O
O
O
I
I
Position of the rocker legend
e.g F • Without thermal overload protection: code C00
• With thermal overload protection: rated current In(A)
Rated current:
}In= 20 A
Table 1 Selection for type TA45
Order example
Line switch
2-pole, rocker actuated
Quick connect terminal
Other types on request
Without illumination
With illumination 220…240 V
110…120 V
35
P1
a
Diagram
Thermal overload protection without with 1-pole with 2-pole
ABC ABT ABD
A02 A12 A32
A04 A14 A34
P2P1
6
3
4 3
P2P1
P2P1
65
}
5
POWER ENTRY MODULES WITH LINE FILTER
5
51
14
45
5
www.schurter.com
10’000
60
2’000
1’000
500
200
100
50
20
10
5
2
1
0,5
0,3
0,2
0,1
[ sec ][ min ]
10
5
1
30
20
1,05
[ x In ]
10854321,32
Type TA45
Rated current I 3... 15 A
1-pole protected
2-pole protected
Ambient temp. +23 °C
Multiple of rated current
Tripping time
n
10’000
60
2000
1000
500
200
100
50
20
10
5
2
1
0,5
0,3
0,2
0,1
[ sec ][ min ]
10
5
1
30
20
1,05
Multiple of rated current
[ x In ]
10854321,32
Tripping time
Type TA45
Rated current In < 3 A
1-pole protected
2-pole protected
Ambient temp. +23 °C
Technical data (continued)
Circuit breaker
Tripping characteristics
In< 3 A
Tripping characteristics
In*3…)15 A
Effect of ambient temperature 1)
The unit is calibrated for an ambient temperature of +23 °C. To
determine the rated current for a lower or higher ambient tempera-
ture, use a correction factor from the table below.
*Ambient temperature [°C] Correction factor
–10 0,89
5 0,91
0 0,92
+23 1,00
+30 1,03
+40 1,08
+55 1,16
Order code TA45
(2-pole rocker-switch without
accessories)
ABTWF150C0 . 001
see table 1
Order code (Order example)
Wiring
0Without
1With
Type of line filter
1Standard
3Medical
Rated current of line filter
11 (A) 56 (A)
22 (A) 68 (A)
33 (A) 710 (A)
44 (A) 815 (A)
Please note that Schurter will establish an internal part number for logistical use in additional to the order code. The format of this internal part
number is, for example 5145.0031.001
1) Example
Rated current at +23 °C 6,0 A
Ambient temperature +40 °C
Correction factor 1,08
Chosen rated current at
+ 40 °C ambient temperature 6 A x 1,08 = 6,5 A
* Temperature must be measured at the rear of the breaker next to
the terminals after equipment operating temperature has been
reached.
Type
5145.