Users should evaluate the suitability of this product for their application. Specifications are subject to change without notice.
Tyco Electronics also reserves the right to make changes in materials or processing, which do not affect compliance with any specification, without notification to Buyer.
1/ COLORS AND COLOR CODE DESIGNATORS SHALL BE IN ACCORDANCE WITH MIL-STD-681. HOWEVER, DUE TO LENGTH LIMITATIONS OF THE RAYCHEM PART NUMBER,
AN ALTERNATIVE COLOR CODE MAY REPLACE MIL-STD-681 COLOR CODE DESIGNATORS. (EXAMPLE: "901/902..." MAY BE REPLACED BY "Axxx".) OTHER CODES AND
SUFFIXES MAY BE ADDED TO THE PART NUMBER, AS NECESSARY, TO CAPTURE ANY ADDITIONAL REQUIREMENTS IMPOSED BY THE PURCHASE ORDER.
DIMENSIONS ARE IN INCHES AND, UNLESS OTHERWISE DESIGNATED, ARE NOMINAL.
THIS SPECIFICATION SHEET TAKES PRECEDENCE OVER DOCUMENTS REFERENCED HEREIN.
REFERENCED DOCUMENTS SHALL BE OF THE ISSUE IN EFFECT ON DATE OF INVITATION FOR BID.
Wire & Cable
501 Oakside Avenue
Redwood City, CA 94063-3800
Phone: 1-800-227-8816
Fax: 1-650-361-6297
© 2006 Tyco Electronics Corporation. All rights reserved.
SPECIFICATION CONTROL DRAWING
44A083X
Title
THREE CONDUCTOR CABLE, UNSHIELDED, UNJACKETED, 600 VOLT
Date
10-31-06
Revision
F
This specification sheet forms a part of the latest issue of Raychem Specification 44.
COMPONENT WIRES – 44A081X
CABLE CONSTRUCTION DETAILS
OUTSIDE DIAMETER
(inches)
PART NUMBER
1/
CONDUCTOR
SIZE
(AWG) NOMINAL MAXIMUM
MAXIMUM
WEIGHT
(lbs/1000 ft)
44A083X-26-* 26 .104 .108 5.8
44A083X-24-* 24 .117 .121 8.3
44A083X-22-* 22 .134 .140 11.9
44A083X-20-* 20 .151 .158 16.8
44A083X-18-* 18 .173 .179 24.5
44A083X-16-* 16 .192 .201 30.9
44A083X-14-* 14 .233 .242 47.4
44A083X-12-* 12 .272 .281 70.4
44A083X-10-* 10 .335 .346 109.
44A083X- 8-* 8 .462 .475 192.
44A083X- 6-* 6 .570 .585 304.
44A083X- 4-* 4 .691 .708 468.
CABLE RATINGS AND ADDITIONAL REQUIREMENTS
TEMPERATURE RATING: 150°C
Maximum continuous conductor temperature
VOLTAGE RATING: 600 volts (rms) at sea level
INSULATION FLAWS:
Spark Test: 5.7 kV (rms) at 3 kHz
Impulse Dielectric Test, 8.0 kV (peak)
The "X" in the part numbers above shall be replaced with a conductor
material designator as follows:
1 tin-coated copper
2 silver-coated copper
3 nickel-coated copper
4 silver-coated high strength copper alloy (AWG's 26-20 only)
The "*" in the part numbers above shall be replaced by color code
designators with a slash separating component wire colors. Colors
shown do not necessarily reflect the sequence of manufacturing.
1/ Example: AWG 20, tin-coated copper conductors; black, brown and
red component wires: 44A0831-20-0/1/2
NOTE: Nominal values are for information only
Nominal values are not requirements.