NEMIC-LAMBDA
JWS 240P
SPECIFICATIONS
A182-01-01
ITEMS MODEL JWS240P-24 JWS240P-48
1 Nominal Output Voltage V24 48
2 Average Output Current A10 5
3 Peak Output Current (*1) A20 10
4 Average Output Power W240 240
5Peak Output Power (*1) W480 480
6 Efficiency (Typ) (*2) %80 80
7 Input Voltage Range (*3) -85 ~ 265VAC (47 ~ 63Hz)
8 Input Current (100/200VAC)(Typ) (*2) A3.2/1.6
9 Inrush Current(Typ) (*4) -20A at 100VAC, 40A at 200VAC
10 PFHC -Built to meet EN61000-3-2
11 Power Factor (100/200VAC)(Typ) (*2) - 0.99/0.95
12 Output Voltage Range V 21.6 ~ 28.8 43.2 ~ 52.8
13 Maximum Ripple & Noise 0 ~ +65°C mV 240 480
(*5) -10 ~ 0°C mV 360 720
14 Maximum Line Regulation (*6) mV 96 192
15 Maximum Load Regulation (*7) mV 192 384
16 Temperature Coefficient Less than 0.02%/°C
17 Over Current Protection (*8) A 20.4 ~ 10.2 ~
18 Over Voltage Protection (*9) V30.0 ~ 34.8 55.2 ~ 64.8
19 Hold-up Time (Typ) (*10) -20ms
20 Leakage Current (*11) -0.75mA MAX, 0.2mA(Typ) at 100VAC / 0.44mA(Typ) at 230VAC
21 Remote Sensing - Possible
22 Remote ON/OFF control - Possible
23 Monitoring Signal -PF (Open Collector Output)
24 Parallel Operation - ---
25 Series Operation -Possible
26 Operating Temperature (*12) --10 ~ +65°C ( -10 ~ +50°C:100%, +60°C:70%,+65°C:55% )
27 Operating Humidity - 30 ~ 90%RH (No dewdrop)
28 Storage Temperature --30 ~ +85°C
29 Storage Humidity - 10 ~ 95%RH (No dewdrop)
30 Cooling -Forced Air By Blower Fan
31 Withstand Voltage -Input - FG:2kVAC(20mA), Input - Output:3kVAC (20mA)
Output - FG:500VAC(100mA), Output-CNT:100VAC(100mA) for 1min.
32 Isolation Resistance -More than 100Mohm Output - FG... 500VDC
More than 10Mohm Output - CNT... 100VDC at 25°C and 70%Rh
33 Vibration -At no operating, 10-55Hz (Sweep for 1min)
2G Constant, X, Y, Z 1hour each.
34 Shock (In package) -Less than 20G
35 Safety (*13) -Built to meet UL1950, CSA950, EN60950,VDE0160.
Built to meet DENTORI.
36 Conducted Emission -Built to meet EN55011/EN55022-A, FCC-ClassA, VCCI-A.
37 Radiated Emission -Built to meet EN55011/EN55022-A, FCC-ClassA, VCCI-A.
38 Weight (Typ.) g 1900
39 Size (WxHxD) mm 120 x 92 x 190 ( Refer to Outline Drawing )
*Read instruction manual carefully, before using the power supply unit.
=NOTES=
*1. Operating time at peak output is less than 10sec.(Duty<=0.5)
*2. At 100/200VAC, Ta=25°C and average output power.
*3. For cases where conformance to various safety specifications (UL, CSA, EN) are required,
input voltage range will be 100-240VAC(50/60Hz).
*4. First in-rush current. Not applicable for the in-rush current to Noise Filter less than 0.2ms.
*5. Measure with EIAJ RC-9131A probe, Bandwidth of scope :100MHz.
*6. 85 - 265VAC , constant load.
*7. No load - Average load, constant input voltage.
*8. Constant current limit with automatic recovery.
Peak current and shorted conditions more than 10 seconds, which could be result of shut down the output voltage.
*9. OVP circuit will shut down output, manual reset (Line recycle).
*10. At 100/200VAC nominal output voltage and average output current.
*11. Measured by the each measuring method of UL, CSA, EN and DENTORI(at 60Hz).
*12. Ratings - Derating at standard mounting.
- Load (%) is percent of average output power or averge output current, whichever is greater.
- As for other mountings, refer to derating curve (A182-01-02_).
*13. As for DENTORI, built to meet at 100VAC.
A1820101_Pdf.xls
NEMIC-LAMBDA
JWS 240P
OUTPUT DERATING
A182-01-02
AVERAGE LOAD(%)
Ta(°C) MOUNTING A MOUNTING B MOUNTING C MOUNTING D
-10 ~+35 100 100 100 100
45 100 100 100 70
50 100 100 100 55
60 70 70 70 -
65 55 55 55 -
OUTPUT DERATING CURVE
0
20
40
60
80
100
-10 010 20 30 40 50 60 70
Ta(°C)
AVERAGE LOAD(%)
MOUNTING A,B,C
MOUNTING D
MOUNTING A
(STANDARD MOUNTING)
MOUNTING B
MOUNTING C
MOUNTING D
A1820102.xls