Voltage Regulation Description Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 83 to 145
Overvoltage Correction Input voltages between 127 and 145 are reduced by 12%
Undervoltage Correction Input voltages between 95 and 108 are boosted by 12%
Severe Undervoltage Correction Input voltages between 83 and 94 are boosted by 24%
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display Front panel LCD information and configuration screen offers detailed UPS and site power status and operating
data, plus configuration of voltage, operating mode, alarm function and a variety of additional options (see manual
for detailed LCD configuration and monitoring options)
Switches 3 pushbutton switches control OFF / ON power status, MODE selection and MUTE / ENTER control functions
Alarm Cancel Operation Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option
available
Audible Alarm Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions
SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating 570
UPS AC Suppression Response
Time Instantaneous
EMI / RFI AC Noise Suppression Yes
PHYSICAL
Included Mounting Accessory
Description 4 post rackmount installation accessories included
Installation Form Factors Supported
with Optional Accessories 2 post rackmount(2POSTRMKITWM); Wallmount(2POSTRMKITWM); Tower(2-9USTAND)
Primary Form Factor Rackmount
UPS Power Module Dimensions
(hwd, in.) 3.45 x 17.3 x 13.45
UPS Power Module Dimensions
(hwd, cm) 8.76 x 43.94 x 34.16
Rack Height (U Spaces) 2
Minimum Required Rack Depth
(inches) 20
Minimum Required Rack Depth (cm) 50.80
UPS Power Module Weight (lbs.) 46.5
UPS Power Module Weight (kg) 21.09
UPS Shipping Dimensions (hwd / in.) 8.5 x 23.4 x 19.9
UPS Shipping Dimensions (hwd /
cm) 21.59 x 59.44 x 50.55
Shipping Weight (lbs.) 51.3
Shipping Weight (kg) 23.3