Molded
Case
Circuit
Breakers
70
-
250
Amperes
J-Frame
12-33
Product
Selection
Table
12-56.
Types
JD, HJD and JDC
Thermal-Magnetic
Circuit Breakers
with
Interchangeable Trip
Units
Max.
Cont.
Amp
Rating
@40°C
Standard
Interrupting
Capacity
600V
AC
Rated
35
kAIC
@
480V
AC
Factory
Assembled
Circuit
Consisting
of
Frame,
Trip
Unit
and
Terminals
@
Catalog
Number
Price
U.S.S
High
Interrupting
Capacity
600V
AC
Rated
65
kAIC
@
480V
AC
Factory
Assembled
Circuit
Consisting
of
Frame,
Trip
Unit
and
Terminals
'*'
Catalog
Number
Price
U.S.S
Ultra
High
Interrupting
Capacity
Current
Limiting
600V
AC
Rated
1
00
kAIC
@
480V
AC
Factory
Assembled
Circuit
Consisting
of
Frame,
Trip
Unit
and
Terminals
<i'
Catalog
Number
Price
U.S.S
Thermal
Magnetic
Trip
Unit
Only
<i!
For
Use
with
Stan
High
or
Ultra
High
Interrupting
Frame
Catalog
Number
dard
or
is
Price
U.S.S
Standard
Terminals
Only
See
Page 12-35
for
Optional
Terminals
Catalog
Number
Price
U.S.S
2-Pole
70
90
100
125
150
175
200
225
250
JD2070
JD2090
JD2100
JD2125
JD2150
JD2175
JD2200
JD2225
JD2250
2,160.00
2,160.00
2,160.00
2,160.00
2,160.00
2,160.00
2,160.00
2,160.00
2,325.00
HJD2070
HJD2090
HJD2100
HJD2125
HJD2150
HJD2175
HJD2200
HJD2225
HJD2250
3,200.00
3,200.00
3,200.00
3,200.00
3,200.00
3,200.00
3,200.00
3,200.00
4,460.00
JDC2070
JDC2090
JDC2100
JDC2125
JDC2150
JDC2175
JDC2200
JDC2225
JDC2250
3,975.00
3,975.00
3,975.00
3,975.00
3,975.00
3,975.00
3,975.00
3,975.00
5,210.00
JT2070T
JT2090T
JT2100T
JT2125T
JT2150T
JT2175T
JT2200T
JT2225T
JT2250T
449.00
449.00
449.00
449.00
449.00
449.00
449.00
449.00
1,435.00
TA250KB
V
22.40
3-Pole
70
90
100
125
150
175
200
225
250
JD3070
JD3090
JD3100
JD3125
JD3150
JD3175
JD3200
JD3225
JD3250
2,605.00
2,605.00
2,605.00
2,605.00
2,605.00
2,605.00
2,605.00
2,605.00
2,805.00
HJD3070
HJD3090
HJD3100
HJD3125
HJD3150
HJD3175
HJD3200
HJD3225
HJD3250
3,770.00
3,770.00
3,770.00
3,770.00
3,770.00
3,770.00
3,770.00
3,770.00
4,915.00
JDC3070
JDC3090
JDC3100
JDC3125
JDC3150
JDC3175
JDC3200
JDC3225
JDC3250
4,915.00
4,915.00
4,915.00
4,915.00
4,915.00
4,915.00
4,915.00
4,915.00
6,040.00
JT3070T
JT3090T
JT3100T
JT3125T
JT3150T
JT3175T
JT3200T
JT3225T
JT3250T
595.00
595.00
595.00
595.00
595.00
595.00
595.00
595.00
1,710.00
TA250KB
ft
,
22.40
4-Pole1>
125
150
175
200
225
250
JD4125
JD4150
JD4175
JD4200
JD4225
JD4250
3,310.00
3,310.00
3,310.00
3,310.00
3,310.00
4,420.00
HJD4125
HJD4150
HJD4175
HJD4200
HJD4225
HJD4250
5,550.00
5,550.00
5,550.00
5,550.00
5,550.00
6,830.00
JDC4125
JDC4150
JDC4175
JDC4200
JDC4225
JDC4250
7,280.00
7,280.00
7,280.00
7,280.00
7,280.00
8,560.00
JT3125T
JT3150T
JT3175T
JT3200T
JT3225T
JT3250T
595.00
595.00
595.00
595.00
595.00
1,710.00
TA250KB
i
22.40
©
Individually
packed.
®
Fully rated neutral pole
with
no
protection.
®
Neutral
is in
right
pole.
®
Magnetic
trip
adjustable 5-10 times continuous ampere rating.
Table
12-57.
Types
JD, HJD and JDC
Thermal-Magnetic
Circuit Breakers
Frame Only
Standard
Interrupting
Capacity
600V
AC
Rated
35
kAIC
@
480V
AC
Catalog
Number
Price
U.S.S
High
Interrupting
Capacity
600V
AC
Rated
65
kAIC
@
480V
AC
Catalog
Number
Price
U.S.S
Ultra
High
Interrupting
Capacity
Current
Limiting
600V
AC
Rated
1
00
kAIC
@
480V
AC
Catalog
Number
Price
U.S.S
2-Pole
JD2250F
805.00
HJD2250F
2,655.00
JDC2250F
3,395.00
3-Pole
JD3250F
950.00
HJD3250F
3,040.00
JDC3250F
4,170.00
4-Pole
JD4250F
2,530.00
HJD4250F
4,940.00
JDC4250F
6,672.00
Note:
Instruction
Leaflet/FRED
Number
29C104
for
Breaker; 29C603
for
Thermal
Magnetic
Trip
Unit
Discount
Symbol.
CB-2
CAT.200.01.T.E
For
more information contact
Cutler-Hammer
at:
www.ch.cutler-hammer.com/catalog
F.T'N
12
-
2
For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog CAT.200.01.T.E
January 2001
12
Product Line Overview
Vol. 1, Ref. No. [0468]
Product Line Description
Cutler-Hammer Molded Case Circuit
Breakers are designed to provide circuit
protection for low voltage distribution
systems. They are described by NEMA
as, “. . . a device for closing and inter-
rupting a circuit between separable
contacts under both normal and
abnormal conditions,” and furthermore
as, “. . . a breaker assembled as an
integral unit in a supporting and
enclosing housing of insulating
material.” The NEC describes them as,
“A device designed to open and close
a circuit by non-automatic means, and
to open the circuit automatically on a
predetermined overload of current,
without injury to itself when properly
applied within its rating.”
So designed, Cutler-Hammer circuit
breakers protect conductors against
overloads and conductors and con-
nected apparatus, such as motors and
motor starters, against short circuits.
In low voltage distribution systems,
there are many varied applications
of molded case circuit breakers.
Cutler-Hammer offers the most
comprehensive family of molded
case circuit breakers in the industry.
This family of circuit breakers includes:
Thermal Magnetic Trip Breakers
Electronic rms Trip Breakers
Molded Case Switches
Motor Circuit Protectors
Current Limiting Breakers
Special Application Breakers
World Breakers
Special Calibration
Special non-UL-listed calibrations
are available for certain ambient
temperatures other than 40°C and for
frequencies other than 50/60 Hz or DC.
Reduced interrupting ratings will apply
for 400 Hz applications. Maximum
thermal calibration is limited to 135A
at 400 Hz.
50°C Calibration
Add suffix V to Catalog Number for
complete breaker, listed above, when
ordering listed ampere ratings for
breakers to be used in 50°C ambients.
Moisture-Fungus Treatment
All circuit breaker cases are molded
from glass-polyester which does not
support the growth of fungus. Any
parts which are susceptible to the
growth of fungus will require special
treatment.
Freeze-Tested Circuit Breakers
The circuit breakers may be ordered
with freeze testing. This option uses
special lubrication and mechanical
operation is verified at -40°C.
Marine Applications
F-Frame circuit breakers can be sup-
plied to meet the following marine
specifications:
U.S. Coast Guard CFR 46 ABS —
American Bureau of Shipping
IEEE 45
These specifications generally require
molded case circuit breakers to be
supplied with 50°C ambient calibration,
special nameplating, and plug-in
adapter kits. When plug-in adapter kits
are used, no terminals need be supplied.
Circuit breakers can also be supplied
to meet UL489 Supplement SA
(Marine Use) and UL489 Supplement
SB (Naval Use).
UL489 Supplement SA applies to vessels
over 65 feet in length. Requirements
include 40°C ambient calibration, spe-
cial labeling, and no use of aluminum
conductors or terminals.
UL 489 Supplement SB requires 50°C
ambient calibration, vibration testings,
special nameplating and no use of
aluminum conductors or terminals.
Standards and Certifications
Molded case circuit breakers are
designed to conform with the follow-
ing standards:
Underwriters Laboratories, Inc.,
Standard UL489, Molded Case
Circuit Breakers and Circuit Breaker
Enclosures
National Electrical Manufacturers
Association Standards Publication
No. AB1-1993, Molded Case Circuit
Breakers
Australian Standard AS 2184,
Molded Case Circuit Breakers
British Standards Institution Standard
BS 4752: Part 1, Switchgear and
Control Gear Part 1: Circuit Breakers
Canadian Standards Association
Standard C22.2 No. 5, Service
Entrance and Branch Circuit Breakers
International Electrotechnical
Commission Recommendations
IEC 157-1, Circuit Breakers
Japanese T-Mark Standard Molded
Case Circuit Breakers
South African Bureau of Standards,
Standard SABS 156, Standard
Specification for Molded Case Circuit
Breakers
Swiss Electro-Technical Association
Standard SEV 157-1, Safety Regula-
tions for Circuit Breakers
Union Technique de l’Electricite
Standard NF C 63-120, Low Voltage
Switchgear and Control Gear Circuit
Breaker Requirements
Verband Deutscher Elektrotechniker
(Association of German Electrical
Engineers) Standard VDE 0660, Low
Voltage Switchgear and Control
Gear, Circuit Breakers
Conformance with these standards
satisfies most local and international
codes, assuming user acceptability
and simplified application.
Molded case circuit breakers equal or
exceed Federal Specification Classifi-
cation W-C-375b requirements for the
particular class associated with the cir-
cuit breaker frame being considered.
Note: For further information, see Circuit
Breaker, CD-ROM SA.74A.01.T.E.
Suffix H01 400 Hz 20% Adder
Suffix J01 Fungus Treated $325. + 20% Adder
Suffix F01 Freeze Tested 20% Adder
Suffix H08 “Marine” 10% Adder
Suffix H09 “Naval” 10% Adder
Cutler-Hammer
January
2001
Vol.
1,
Ref.
No.
[0497]
Molded
Case Circuit Breakers
70
-
250
Amperes
J-Frame
12-31
Contents
Description
Page
Product
Description
........
12-31
Technical
Data
and
Specifications
........
12-31
Dimensions/Weights ....... 12-32
Product
Selection .......... 12-32
, I,
x'
'
J-Frame
Product
Description
All
J-Frame Circuit
Breakers
are
HACR
rated.
J-Frame circuit breakers
are
available
as
individual components (Frame,
Trip
Unit,
Terminals),
or
factory
assembled
complete
breakers.
J-Frame
circuit breakers
with
non-
interchangeable
trip
units
are
suitable
for
reverse feed use.
Typical
J-Frame Circuit Breaker
Technical Data
and
Specifications
Table
12-50.
UL489
Interrupting
Capacity Ratings
Circuit
Breaker
Type
JOB
JD
HJD
JDC
Number
of
Poles
2,3
2,3,4
2,3,4
2,3,4
Interrupting
Capacity
(Symmetrical
Amperes) (kA)
Volts
AC
(50/60
Hz)
240
65
65
100
200
480
35
35
65
100
600
125
18
18
25
35
Volts
DC
250 '>?
10
10
22
22
500®
©
2-pole circuit breaker
or two
outside poles
of
3-pole circuit breaker.
@
Time constant
is 3
milliseconds minimum
at 10 kA and 8
milliseconds
minimum
at 22 kA.
®
8
milliseconds time constant.
Table
12-51.
IEC157-1
(PI)
Interrupting Capacity Ratings
Circuit
Breaker
Type
JD
HJD
JDC
Number
of
Poles
2,3,4
2,3,4
2,3,4
Interrupting
Capacity
(Symmetrical
Amperes) (kA)
Volts
AC
(50/60
Hz)
240
65
100
200
380
415
35
65
100
35
65
100
600
125
Volts
DC
250
®t
10
22
22
®
2-pole circuit
breaker
or two
outside poles
of
3-pole circuit breaker.
®
Time constant
is 3
milliseconds
minimum
at 10 kA and 8
milliseconds
minimum
at 22 kA.
y
-•M<S»-
.
<?k.
~t
CAT.200.01.T.E
For
more information contact
Cutler-Hammer
at:
www.ch.cutler-hammer.com/catalog
E:T*M
12-32Molded Case Circuit Breakers
70
-
250
Amperes
J-Frame
Cutler-Hammer
January
2001
Vol.
1,
Ref.
No.
[0498]
Dimensions/Weights
Table
12-52.
Dimensions
in
Inches (mm)
Number
of
Poles
2,3
4
Width
4.125(105)
5.5(140)
Height
|
Depth
10
(255)
10
(254)
4.063
(103)
4.063(103)
Table
12-53.
Approximate Shipping
Weight
in
Lbs. (Kg)
Breaker
Type
JOB
JD
HJD
JDC
Complete
Breaker
Frame
Only
Trip
Unit
Number
of
Poles
2
11.25(5.103)
11.25(5.103)
11.25(5.103)
12.25(5.557)
3
4
12.5
(5.670)
12.5(5.670)
12.5
(5.670)
13.5(6.124)
13.25(6.010)
13.25(6.010)
14.25
(6.470)
2
9
(4.082)
9
(4.082)
10
(4.536)
3
10(4.536)
10
(4.536)
11
(4.990)
4
2
10.5
(4.763)
10.5(4.763)
11.5(5.217)
2
(.907)
2
(.907)
2
(.907)
3
2
(.907)
2
(.907)
2
(.907)
4
2.25(1.021)
2.25(1.021)
2.25(1.021)
Product
Selection
This
information
is
presented only
as an aid to
understanding Catalog Numbers.
It is not to be
used
to
build
Catalog Numbers
for
circuit
breakers
or
trip
units.
Table
12-54.
Circuit Breaker/Frame Catalog Numbering System
Circuit
Breaker/
Frame Ampere Rating
Suffix
C
=
Non-aluminum
Terminals
F
=
Frame
Only
K
=
High
Magnetic
Molded
Case
Switch
V
=
50°C
Calibration
W
=
Without
Terminals
X
=
Load
Side
Terminals Only
Y
=
Line
Side
Terminals
Only
Table 12-55.
Trip
Unit
Catalog
Numbering
System
JT
3
250 T
T
Trip
Unit
Type
Number
._
_, ... . of
Poles
2 = 2
Poles
3 = 3
Poles
4 = 4
Poles
Trip
Unit
Rating/
Plug
Ampere
Rating
070
090
100
125
150
175
200
225
250
Suffix
T
=
Trip
Unit
Thermal-Magnetic
Fixed
Thermal
Adj. Magnetic
V
=
50°C
Calibration
(Thermal-Magnetic
Trip
Units
Only)
E:T*N
For
more
information contact
Cutler-Hammer
at:
www.ch.cutler-hammer.com/catalog