selos/fasis
selos/fasis
As a result of changes to the 2005 NEC, both the operator and
manufacturer of electrical equipment must comply with increased
requirements related to resistance to short-circuiting of equipment.
In accordance with both the NEC 2005 Article 409.110 and UL 508A,
the short circuit resistance of the complete installation must now be
considered. The installation‘s Short Circuit Current Rating must be
indicated on the equipment or control panel‘s legend plate.
Wieland has tested and determined individual SCCR values for
their terminal blocks in connection with the widest variety of
fuses. These ratings are far greater than the default values con-
tained in UL 508A. As a result, when qualifying your installation, you
have increased exibility and accuracy when using Wieland terminal blocks.
SCCR Values for DIN rail terminal blocks
What does SCCR marking mean?
The Short Circuit Current Rating (SCCR) of a component represents the maximum
short circuit current level a device can safely withstand without compromising safety
for installations and personnel. Article 409 on industrial control panels was added
to the NEC in the 2005 edition. This article calls for all industrial control panels to be
marked with a Short Circuit Current Rating. The Short Circuit Current Rating (SCCR)
requirements for UL 508A came into force in April 2006.
How is the SCCR marking determined?
The NEC Article 409 refers to the UL 508A Supplement SB as an approved method for
determining the SCCR of an industrial control panel. This specic method is outlined in
Section SB4.
1. Determination of the SCCR values of individual components,
for example DIN rail terminal blocks
2. Modication of the SCCR values through the use of
current limiting devices per UL 508 SB 4.3
3. Selection of the lowest SCCR value from all the components
SCCR for DIN rail terminal blocks in general
The SCCR of a terminal block can be determined according to UL 508A using one
of the following methods:
1. Use the tested SCCR value
2. Use the default SCCR value as specied in table 4.1 of UL 508
If the DIN rail terminal blocks do not have a tested SCCR, then the UL default value
of 10kA must be used. This relatively low value would limit the SCCR of the entire
system to max. 10 kA.
0119.3 E 07/08
SCCR for Wieland DIN rail terminal blocks
Wieland determined SCCR values for its DIN rail terminal blocks used in conjunction
with fuses and circuit breakers.
The resulting SCCR values are much higher than the values specied for
DIN rail terminal blocks in table SB 4.1 of UL 508A.
You will nd the tested SCCR values for our selos and fasis product series on the
back side of this data sheet.
The SCCR values are also published on the UL website (http://www.ul.com) under
le number E60678.
57.503.0055.0 WK 2,5 / U / V0 14 – 12 100 100 60 30 60 30 100
57.504.0055.0 WK 4 / U / V0 14 – 10 200 200 200 100 60 30 100
57.504.5055.0 WK 4 D1 / 2 / U / V0 14 – 10 200 200 200 100 60 30 100
57.504.5155.0 WK 4 D2 / 2 / U / V0 14 – 10 200 200 200 100 60 30 100
57.506.0055.0 WK 6 / U /V0 14 – 8 200 200 200 100 60 30 100
57.510.0155.0 WKN 10/U /V0 14 – 6 200 200 200 100 60 30 100
57.516.0155.0 WKN 16 / U /V0 12 – 4 200 200 200 100 60 30 100
57.535.0155.0 WKN 35 / U /V0 10 – 2 400 400 400 200 60 30 100
57.570.0155.0 WKN 70 / U /V0 6 – 2/0 400 400 400 200 60 30 100
57.597.0155.0 WKN 150 / U /V0 2/0 – 350 400 400 400 200 60 30 100
fasis
56.703.0055.0 WKFN 2,5 /35 14 – 12 100 100 60 30 60 30 100
56.703.5055.0 WKFN 2,5 D1/2 /35 14 – 12 100 100 60 30 60 30 100
56.703.5155.0 WKFN 2,5 D2 / 2 / 35 14 – 12 100 100 60 30 60 30 100
56.704.0055.0 WKFN 4 /35 14 – 10 200 200 200 100 60 30 100
56.704.5055.0 WKFN 4 D1/2 /35 14 – 10 200 200 200 100 60 30 100
56.704.5155.0 WKFN 4 D2/2 /35 14 – 10 200 200 200 100 60 30 100
56.704.8453.0 WKF 4 3D/SL 14 – 10 200 200 200 100 60 30 100
56.706.0055.0 WKFN 6 /35 14 – 8 200 200 200 100 60 30 100
56.706.5055.0 WKFN 6 D1/2 /35 14 – 8 200 200 200 100 60 30 100
56.710.0055.0 WKFN 10 /35 14 – 6 200 200 200 100 60 30 100
56.710.5055.0 WKFN 10 D1/2 /35 14 – 6 200 200 200 100 60 30 100
56.716.0055.0 WKFN 16 /35 14 – 4 200 200 200 100 60 30 100
56.716.5055.0 WKFN 16 D1/2 /35 14 – 4 200 200 200 100 60 30 100
selos
Industrial technology
Solutions for the control cabinet
• DIN rail terminal blocks
Screw, spring clamp or IDC connection
technology
– Wire cross sections up to 240 mm2
– Numerous special functions
Software solutions interfacing to
CAE systems
• Safety
– Safety sensors
– Safety relays
– Modular safety systems with eldbus link
• PLC and eldbus components
– Standard applications in IP 20
Increased environmental conditions with
railroad and ship approvals
• Interface
– Coupling relays, semiconductor switches
– Measuring and monitoring relays
– Timer and switching relays
– Analog modules
– Passive interfaces
– Power supply units
– Overvoltage protection
Solutions for eld applications
• Remote automation technology
– Power distribution
– Fieldbus interfaces and motor starters
• Connectors for industrial applications
– Square and round connectors
– Aluminum or plastic housings
– Degree of protection up to IP 68
– Current-carrying capacity up to 100 A
– Connectors for hazardous areas
– Modular, application specic technology
PC board terminals and connectors
Screw or spring clamp connection technology
– Spacings: 3.5 mm to 10.16 mm
– Reow or wave soldering process
Building and installation technology
Building installation systems
Main power supply connectors
IP 20/IP 65 ... IP 68
– Bus connectors
– Combined connectors
– Low-voltage connectors
– Power distribution system with at cables
– Distribution systems
Bus systems in KNX, LON and
radio technology
DIN rail terminal blocks for
electrical installations
– Overvoltage protection
Headquarters:
Wieland Electric GmbH
Brennerstraße 10 – 14
D-96052 Bamberg
Sales and Marketing Center:
Wieland Electric GmbH
Benzstraße 9
D-96052 Bamberg
Phone +49 951 93 24-0
Fax +49 951 93 24-1 98
www.wieland-electric.com
www.gesis.com
www.gesis-network.com
info@wieland-electric.com Connectable
conductors
[AWG/kcmil]
Fuse [A] SCCR
value
[kA]
Part Number Type J T RK1 RK5 GCC
Connectable
conductors
[AWG/kcmil]
Fuse [A] SCCR
value
[kA]
Part Number Type J T RK1 RK5 G CC
Rated voltage UL: 600 V
Rated voltage UL: 600 V
DIN rail terminal blocks with
spring clamp connection
DIN rail terminal blocks with screw connection
P r o d u c t R a n g e