9873 Paired - Audio, Control and Instrumentation Cable For more information please call 1-800-Belden1 See Put-ups and Colors Color Code Chart : No. 3 for Paired Cables (Belden Standard).pdf Description: 20 AWG stranded (7x28) TC conductors, polypropylene insulation, twisted pairs, individually shielded w/Beldfoil(R) (100% coverage), 22 AWG stranded TC drain wire, overall PVC jacket. PHYSICAL CHARACTERISTICS: CONDUCTOR: Number of Pairs 3 Total Number of Conductors 6 AWG 20 Stranding 7x28 Conductor Material TC - Tinned Copper INSULATION: Insulation Material PE - Polyethylene Lay Length 1.75 in. Twists/ft. 6.85 Pair Color Code Chart : Number 1 2 Color Black & Red Black & White Number 3 INNER SHIELD: Inner Shield Material Trade Name Beldfoil(R) (Z-Fold(R)) Inner Shield Type Tape Inner Shield Material Aluminum Foil-Polyester Tape Inner Shield % Coverage 100 % Inner Shield Drain Wire AWG 22 Inner Shield Drain Wire Stranding 19x34 Inner Shield Drain Wire Conductor Material TC - Tinned Copper OUTER JACKET: Page 1 of 3 Color Black & Green 9873 Paired - Audio, Control and Instrumentation Cable Outer Jacket Material PVC - Polyvinyl Chloride OVERALL NOMINAL DIAMETER: Overall Nominal Diameter .341 in. MECHANICAL CHARACTERISTICS: Operating Temperature Range -20C To +80C UL Temperature Rating 80C (UL AWM Style 2919) Bulk Cable Weight 55.7 lbs/1000 ft. Max. Recommended Pulling Tension 106 lbs. Min. Bend Radius (Install) 3.3 in. APPLICABLE SPECIFICATIONS AND AGENCY COMPLIANCE: APPLICABLE STANDARDS: NEC/(UL) Specification CM CEC/C(UL) Specification CM AWM Specification UL Style 2919 (30 V 80C) EU CE Mark (Y/N) Yes EU RoHS Compliant (Y/N) Yes EU RoHS Compliance Date (mm/dd/yyyy): 01/01/2004 FLAME TEST: UL Flame Test UL1685 UL Loading PLENUM/NON-PLENUM: Plenum (Y/N) N ELECTRICAL CHARACTERISTICS: Nom. Characteristic Impedance 50 Ohms Nom. Inductance 0.18 H/ft Nom. Capacitance Conductor to Conductor @ 1 KHz 30 pF/ft Nom. Cap. Cond. to Other Cond. & Shield @ 1 KHz 55 pF/ft Nominal Velocity of Propagation 66 % Nom. Conductor DC Resistance @ 20 Deg. C 10.5 Ohms/1000 ft Ind. Pair Nominal Shield DC Resistance @ 20 Deg. C 14 Ohms/1000 ft Max. Operating Voltage - UL 30 V RMS (UL AWM Style 2919), 300 V RMS (CM) Max. Recommended Current 2.7 Amps per conductor @ 25C PUT-UPS AND COLORS: Item Description Put-Up (ft.) 9873 060100 3 FS PR #20 PP PVC 100 Ship Weight (lbs.) 6.6 Page 2 of 3 Jacket Color CHROME Notes 9873 Paired - Audio, Control and Instrumentation Cable 9873 0601000 3 FS PR #20 PP PVC 1000 58 CHROME C 9873 060250 3 FS PR #20 PP PVC 250 14.5 CHROME C 9873 060500 3 FS PR #20 PP PVC 500 32.5 CHROME C C = CRATE REEL PUT-UP. Revision Number: 1 Revision Date: 07-25-2005 (c) 2005 Belden Wire & Cable Company All Rights Reserved. Although Belden Electronics Division ("Belden") makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications described herein are subject to error or omission and to change without notice, and the listing of such information and specifications does not ensure product availability. Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether express, statutory or implied. In no event will Belden be liable for any damages (including consequential, indirect, incidental, special, punitive, or exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract, negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein. All sales of Belden products are subject to Belden's standard terms and conditions of sale. Belden CDT Electronics Division believes this product to be in compliance with the following environmental regulations: California Proposition 65 Consent Judgment For Wire & Cable Mfgs.(San Francisco Superior Court Nos. 312962 And 320342); EU RoHS (Directive 2002/95/EC, 27-Jan-2003);Material manufactured prior to the compliance date may still be in stock at Belden facilities and in our Distributor's inventory. EU ELV (Directive 2000/53/EC, 18-Sept-2000); EU WEEE (Directive 2002/96/EC, 27-Jan-2003); And EU BFR (Directive 2003/11/EC, 6-Feb-2003). The information provided in this Product Disclosure, and the identification of materials listed as reportable or restricted within the Product Disclosure, is correct to the best of Belden's knowledge, information and belief at the date of its publication. The information provided in the Product Disclosure is designed only as a general guide for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for determining the applicability of legislation and regulations based on their individual usage of the product. Belden CDT Electronics Division declares this product to be in compliance with EU LVD (Low Voltage Directive 73/23/EEC), as amended by directive 93/68/EEC. Page 3 of 3