For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp 47
Low Voltage Supplementary Fuses
Low Voltage
Supplementary
Fuses
Specifications
Class: Supplemental
Description: Time-delay,
pin indication fuse.
Dimensions: 1332” x 1 12
(10.3 x 38.1mm).
Construction: Fiber tube
Ratings:
Volts — 250Vac (110-810A)
— 125Vac (1-15A)
— 32V (20-30A)
Amps 110-30A
IR — 35A (110-810A @ 250Vac)
— 10,000A (110-15A @ 125Vac)
— 1000A (20-30A @ 32V)
Agency Information: CE, Std. 248-
14, UL Listed 110-810A, IR 35A@ 250V,
IR 10kA@ 125V , 1-15A, IR 10kA@
125V, Guide JDYX, File 19180, CSA
Certified, 0-810A/250V, 1-10A/125V,
Class 1422-01, File 53787.
Features and Benefits
• FNA has a pin indicator providing
visual identification of failed circuits,
resulting in reduced circuit downtime.
• Time-delay response allows close
sizing on control transformers and
relays
Typical Applications
• Control Circuits
• Electronic Circuits
Catalog Numbers (Amps)
FNA-110 FNA-810 FNA-2 12FNA-6 14
FNA-18FNA-1 FNA-2 810 FNA-7
FNA-15100 FNA-1 18FNA-3 FNA-8
FNA-210 FNA-1 14FNA-3 210 FNA-9
FNA-14FNA-1 410 FNA-3 12FNA-10
FNA-310 FNA-1 12FNA-4 FNA-12*
FNA-410 FNA-1 610 FNA-4 12FNA-15*
FNA-12FNA-1 810 FNA-5 FNA-20*
FNA-610 FNA-2 FNA-5 610 FNA-25*
FNA-34FNA-2 14FNA-6 FNA-30
*12-30A versions are dual-tube construction
MIC & MIN
Specifications
Class: Supplemental
Description: Fast-
acting, pin indication
fuse.
Dimensions:
1332” x 1 12” (10.3 x
38.1mm) 5AG.
Construction:
Fiber tube
Ratings:
Volts — 250Vac (1-15A)
— 32V (20-30A)
Amps — 1-30A
IR — 35A (1A @250Vac)
— 100A (2-3A @250Vac)
— 200A (5-10A @250Vac)
— 750A (15A @250Vac)
— 10,000A (20-30A @32V)
— 35A (1A @250Vac)
Agency Information: CE, Std. 248-14,
MIC—0-15A UL Listed, Guide JDYX,
File E19180, MIN—1-5A CSA Certified,
Class 1422-01, File 53787.
Features and Benefits
Type MIN has a “red” pin indicator
providing visual identification of failed
circuits, resulting in faster trouble
shooting (reduced circuit downtime).
Type MIC has silver-plated pin transmit-
ting an electrical signal indicating
location of a failed circuit, resulting in
faster troubleshooting (reduced circuit
downtime).
Typical Applications
Control Circuits
PLC Circuits
Electronic Circuits
MIC Catalog Numbers (Amps)
MIC-1 MIC-5 MIC-20
MIC-2 MIC-10 MIC-25
MIC-3 MIC-15 MIC-30
MIC - (1-15)UL Listed 125Vac / IR = 10kA
MIN Catalog Numbers (Amps)
MIN-1 MIN-5 MIN-20
MIN-2 MIN-10 MIN-25N
Specifications
Class: Supplemental
Description: Fast-acting, pin
indication fuse.
Dimensions: 14” x 1 14
(6.6 x 31.7mm) 3AG.
Construction: Fiber tube
Ratings:
Volts — See Agency Info below
Amps 12-15A
IR — See Agency Info below
Agency Information: CE, Std. 248-
14, UL Listed, 0-5A/125Vac, 10,000
AIC, Guide JDYX, File E19180, UL
Recognized, 6A/125Vac, 1000AIC
8-15A/50Vac/dc, 300 AIC Guide
JDYX2, File E19180, CSA Certified:
0-5A/125Vac, 10,000 AIC Class
1422-01, File 53787.
Features and Benefits
• Type GBA has a “red” pin indicator
providing visual identification of failed
circuits, resulting in faster
troubleshooting (reduced circuit
downtime).
• Type GLD has an plated pin to
activate transmitting a electrical
signal to indicate the location of
opened circuits, resulting in reduced
downtime.
Typical Applications
• Control Circuits
• Electronic Circuits
GLD Catalog Numbers (Amps)
GLD-12GLD-2 GLD-6
GLD-34GLD-3 GLD-10
GLD-1 GLD-4 GLD-12
GLD-1 12GLD-5 GLD-15
GBA Catalog Numbers (Amps)
GBA-12GBA-2 GBA-8
GBA-34GBA-3 GBA-10
GBA-1 GBA-4 GBA-15
GBA-1 12GBA-5
Pin indication Fuses
Data Sheet: 2029
Data Sheet: 2047
Data Sheet: 2012
GBA
GLD
FNA
Recommended fuse blocks/fuse
holders for 14”x 1
14 indicating fuses
• Page 41
Recommended signal block for
1332”x 1
12 indicating fuses
• Page 41
Recommended signal block for
1332”x 1
12 indicating fuses
• Page 41