9363 Triad - 300V Power-Limited Tray Cable
For more information please
call
1-800-Belden1
See Put-ups and Colors
Color Code Chart : ICEA
Table E1.pdf
Description:
22 AWG triads stranded (7x30) tinned copper conductors, twisted triads, PVC insulation, overall Beldfoil shield (100% coverage), PVC
jacket.
PHYSICAL CHARACTERISTICS:
CONDUCTOR:
Number of Triads 1
Total Number of Conductors 3
AWG 22
Stranding 7x30
Conductor Material TC - Tinned Copper
INSULATION:
Insulation Material PVC - Polyvinyl Chloride
Insulation Diameter .062 in.
OVERALL CABLING:
Overall Cabling Color Code Chart :
Number Color
1 Black & White & Red
OUTER SHIELD:
Outer Shield Material Trade Name Beldfoil®
Outer Shield Type Tape
Outer Shield Material Aluminum Foil-Polyester Tape
Outer Shield %Coverage 100 %
OUTER SHIELD DRAIN WIRE :
Outer Shield Drain Wire AWG 22
Outer Shield Drain Wire Stranding 7x30
Outer Shield Drain Wire Conductor Material TC - Tinned Copper
OUTER JACKET:
Page 1 of
3
9363 Triad - 300V Power-Limited Tray Cable
Outer Jacket Material PVC - Polyvinyl Chloride
Outer Jacket Nominal Wall Thickness .037 in.
Outer Jacket Ripcord Yes
OVERALL NOMINAL DIAMETER:
Overall Nominal Diameter .208 in.
MECHANICAL CHARACTERISTICS:
Operating Temperature Range -30°C To +105°C
UL Temperature Rating 105°C
Bulk Cable Weight 26 lbs/1000 ft.
Max. Recommended Pulling Tension 29 lbs.
Min. Bend Radius (Install) 2 in.
APPLICABLE SPECIFICATIONS AND AGENCY COMPLIANCE:
APPLICABLE STANDARDS:
NEC/(UL) Specification PLTC, ITC, CMG
CEC/C(UL) Specification CMG
EU CE Mark (Y/N) Yes
EU RoHS Compliant (Y/N) Yes
EU RoHS Compliance Date (mm/dd/yyyy): 04/01/2005
FLAME TEST:
UL Flame Test UL1685 FT4 Loading
C(UL) Flame Test FT4
IEEE Flame Test 1202
ICEA Flame Test T-29-520
SUITABILITY:
Suitability - Indoor Yes
Suitability - Outdoor Yes
Suitability - Burial Yes
Sunlight Resistance Yes
PLENUM/NON-PLENUM:
Plenum (Y/N) N
ELECTRICAL CHARACTERISTICS:
Nom. Inductance .21 µH/ft
Nom. Capacitance Conductor to Shield @ 1 KHz 45 pF/ft
Nom. Capacitance Conductor to Conductor @ 1 KHz 26 pF/ft
Nom. Conductor DC Resistance @ 20 Deg. C 15 Ohms/1000 ft
Page 2 of
3
9363 Triad - 300V Power-Limited Tray Cable
Nominal Outer Shield DC Resistance 60 Ohms/1000 ft
Max. Operating Voltage - UL 300
Max. Recommended Current 3.8 Amps per conductor @ 25°C
PUT-UPS AND COLORS:
Item Description Put-Up (ft.) Ship Weight (lbs.) Jacket Color Notes
9363 060U1000 3 #22 PVC SHLD
PVC U1000 26 CHROME
9363 060U500 3 #22 PVC SHLD
PVC U500 13.5 CHROME
Revision Number: 1 Revision Date: 09-20-2005
© 2005 Belden Wire & Cable Company
All Rights Reserved.
Although Belden Electronics Division ("Belden") makes every reasonable effort to ensure their accuracy at the time of this publication,
information and specifications described herein are subject to error or omission and to change without notice, and the listing of such
information and specifications does not ensure product availability.
Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether express,
statutory or implied. In no event will Belden be liable for any damages (including consequential, indirect, incidental, special, punitive, or
exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract,
negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described
herein.
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden CDT Electronics Division believes this product to be in compliance with the following environmental regulations: California
Proposition 65 Consent Judgment For Wire & Cable Mfgs.(San Francisco Superior Court Nos. 312962 And 320342); EU RoHS
(Directive 2002/95/EC, 27-Jan-2003);Material manufactured prior to the compliance date may still be in stock at Belden facilities and in our
Distributor's inventory. EU ELV (Directive 2000/53/EC, 18-Sept-2000); EU WEEE (Directive 2002/96/EC, 27-Jan-2003); And EU BFR
(Directive 2003/11/EC, 6-Feb-2003). The information provided in this Product Disclosure, and the identification of materials listed as
reportable or restricted within the Product Disclosure, is correct to the best of Belden's knowledge, information and belief at the date of its
publication. The information provided in the Product Disclosure is designed only as a general guide for the safe handling, storage, and any
other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not to be considered a warranty or quality
specification. Regulatory information is for guidance purposes only. Product users are responsible for determining the applicability of
legislation and regulations based on their individual usage of the product.
Belden CDT Electronics Division declares this product to be in compliance with EU LVD (Low Voltage Directive 73/23/EEC), as amended
by directive 93/68/EEC.
Page 3 of
3