Surge protection device-BXT-M/RS485-TTL-2749987
Technical data
General
Direction of action Line-Line & Line-Signal Ground/Shield & Signal Ground/Shield-Earth
Ground
Protective circuit
IEC test classification B2
C1
C2
C3
D1
Maximum continuous operating voltage UC6.2 V DC
Maximum continuous voltage UC (wire-wire) 6.2 V DC
Maximum continuous voltage UC (wire-ground) 6.2 V DC
Nominal current IN1.5 A (25 °C)
Operating effective current IC at UC≤ 1 µA
Residual current IPE ≤ 5 µA
Nominal discharge current In (8/20) µs (Core-Core) 350 A
Nominal discharge current In (8/20) µs (Core-Earth) 5 kA
Nominal discharge current In (8/20) µs (Core-GND) 350 A
Total surge current (8/20) µs 5 kA
Max. discharge current Imax (8/20) µs maximum (Core-Core) 350 A
Max. discharge current Imax (8/20) µs maximum (Core-Earth) 5 kA
Max. discharge current Imax (8/20) µs maximum (Core-GND) 350 A
Output voltage limitation at 1 kV/µs (Core-Core) spike ≤ 45 V
Output voltage limitation at 1 kV/µs (Core-Earth) spike ≤ 450 V
Output voltage limitation at 1 kV/µs (Core-Core) static ≤ 16 V
Output voltage limitation at 1 kV/µs (Core-Earth) static ≤ 450 V
Voltage protection level UP (Core-Core) ≤ 35 V (C1, 500 V/250 A)
≤ 50 V (C1, 700 V/350 A)
≤ 22 V (C3 - 100 A)
Voltage protection level UP (Core-Earth) ≤ 550 V (B2 - 4 kV/100 A)
≤ 550 V (C2, 4 kV/2 kA)
≤ 600 V (C2, 10 kV/5 kA)
≤ 700 V (C3 - 100 A)
Response time tA (Core-Core) ≤ 500 ns
Response time tA (Core-Earth) ≤ 100 ns
Input attenuation aE, sym. typ. 0.1 dB (≤ 10 MHz/50 Ω)
typ. 0.1 dB (≤ 4 MHz / 150 Ω)