Part Number GDB-32mA GDB-40mA GDB-50mA GDB-63mA GDB-80mA GDB-100mA GDB-125mA GDB-160mA GDB-200mA GDB-250mA GDB-315mA GDB-400mA GDB-500mA GDB-630mA GDB-800mA GDB-1A GDB-1.25A GDB-1.6A GDB-2A GDB-2.5A GDB-3.15A GDB-4A GDB-5A GDB-6.3A GDB-8A GDB-10A Voltage Rating Vac 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 Specifications Interrupting Rating (amps) at Rated Voltage (50Hz) Vac 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 40 50 63 80 100 Typical DC Cold Resistance ()* 40 25 17 12.5 5.0 3.8 2.8 9.1 6.8 4.3 3.1 2.0 0.26 0.20 0.14 0.125 0.096 0.066 0.043 0.034 0.025 0.021 0.014 0.010 0.010 0.008 Typical Melting I2t AC 0.000047 0.00011 0.00020 0.00057 0.0012 0.003 0.005 0.008 0.016 0.28 0.58 0.18 0.18 0.35 0.67 0.60 0.84 1.6 4.2 6.1 13 22 42 69 N/A N/A Maximum Agency Approval Voltage Drop (mV) UR VDE 3200 2500 2400 2000 1200 1100 1000 2000 X X 1700 X X 1400 X X 1300 X X 1100 X X 220 X X 220 X X 190 X X 200 X X 200 X X 190 X X 150 X X 150 X X 130 X X 130 X X 120 X X 120 X X 120 X X 120 X X * DC Cold Resistance (Measured at <10% of rated current) Typical Melting I2t (I2t was measured at listed interrupting rating and rated voltage) Maximum Voltage Drop (Voltage drop was measured at 20C ambient temperature at rated current) 0209 BU-SB08762 Page 1 of 2 Data Sheet 2015