TM221ME16R Product data sheet Characteristics Logic controller, Modicon M221, 16 IO relay Ethernet Product availability : Stock - Normally stocked in distribution facility Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications Price* : 309.00 USD Main Range of product Modicon M221 Product or component type Logic controller [Us] rated supply voltage 24 V DC Discrete input number 8, discrete input IEC 61131-2 Type 1 Analogue input number 2 0...10 V Discrete output type Relay normally open Discrete output number 8 relay Discrete output voltage 5...125 V DC 5...250 V AC Discrete output current 2A Complementary Discrete I/O number 16 Maximum number of I/O expansion module 7 relay output Supply voltage limits 20.4...28.8V Inrush current 35A Maximum power consumption in W 23.3W 24 V with max number of I/O expansion module) 4.3W 24 V without I/O expansion module) Power supply output current 0.52A 5 V expansion bus 0.46A 24 V expansion bus Discrete input logic Sink or source (positive/negative) Discrete input voltage 24 V Discrete input voltage type DC Analogue input resolution 10 bits LSB value 10 mV *Price is "List Price" and may be subject to a trade discount - check with your local distributor or retailer for actual price. Apr 16, 2021 1 Conversion time 1 ms per channel + 1 controller cycle time analog input Permitted overload on inputs +/- 30 V DC 5 min maximum)analog input +/- 13 V DC permanent)analog input Voltage state 1 guaranteed >= 15 V for input Voltage state 0 guaranteed <= 5 V for input Discrete input current 7mA discrete input 5mA fast input Input impedance 100 kOhm analog input 3.4 kOhm input 4.9 kOhm fast input Response time 35 s turn-off, I2...I5 input 5 s turn-on, I0, I1, I6, I7 fast input 35 s turn-on, other terminals input 5 s turn-off, I0, I1, I6, I7 fast input 100 s turn-off, other terminals input 5 s turn-on, turn-off, Q0...Q1 output 50 s turn-on, turn-off, Q2...Q3 output 300 s turn-on, turn-off, other terminals output Configurable filtering time 0 ms input 3 ms for input 12 ms input Output voltage limits 125 V DC 277 V AC Maximum current per output common 7A Absolute accuracy error +/- 1 % of full scale analog input Electrical durability 100000cycles AC-12, 120 V, 240VA, resistive 100000cycles AC-12, 240 V, 480VA, resistive 300000cycles AC-12, 120 V, 80VA, resistive 300000cycles AC-12, 240 V, 160VA, resistive 100000cycles AC-15, cos phi = 0.35, 120 V, 60VA, inductive 100000cycles AC-15, cos phi = 0.35, 240 V, 120VA, inductive 300000cycles AC-15, cos phi = 0.35, 120 V, 18VA, inductive 300000cycles AC-15, cos phi = 0.35, 240 V, 36VA, inductive 100000cycles AC-14, cos phi = 0.7, 120 V, 120VA, inductive 100000cycles AC-14, cos phi = 0.7, 240 V, 240VA, inductive 300000cycles AC-14, cos phi = 0.7, 120 V, 36VA, inductive 300000cycles AC-14, cos phi = 0.7, 240 V, 72VA, inductive 100000cycles DC-12, 24 V, 48W, resistive 300000cycles DC-12, 24 V, 16W, resistive 100000cycles DC-13, 24 V, 24W, inductive (L/R = 7 ms) 300000cycles DC-13, 24 V, 7.2W, inductive (L/R = 7 ms) Switching frequency 20 switching operations/minute with maximum load Mechanical durability 20000000cycles relay output Minimum load 1mA 5 V DC relay output Protection type Without protection 5A Reset time 1s Memory capacity 256 kB user application and data RAM 10000 instructions 256 kB internal variables RAM Data backed up 256 kB built-in flash memory backup of application and data Data storage equipment 2 GB SD card optional) Battery type BR2032 lithium non-rechargeable 4year(s) Backup time 1 year 77F (25C) by interruption of power supply) Execution time for 1 KInstruction 0.3ms event and periodic task 0.7ms other instruction Execution time per instruction 0.2 s Boolean Exct time for event task 60 s response time Application structure 1 configurable freewheeling/cyclic master task 1 cyclic auxiliary task 8 interrupt tasks Maximum size of object areas 512 %KW constant words 255 %C counters 8000 %MW memory words 255 %TM timers 512 %M memory bits 2 Realtime clock With Clock drift <= 30 s/month 77F (25C) Regulation loop Adjustable PID regulator up to 14 simultaneous loops Function available Frequency generator PWM PLS Counting input number 4 fast input (HSC mode) 100kHz 32 bits Counter function Single phase A/B Pulse/direction Integrated connection type USB port mini B USB 2.0 Non isolated serial link serial 1 RJ45 RS232/RS485 Ethernet RJ45 Supply Serial 1)serial link supply 5 V, <200mA Transmission rate 1.2...115.2 kbit/s (115.2 kbit/s by default) 49.21ft (15m) RS485 1.2...115.2 kbit/s (115.2 kbit/s by default) 9.84ft (3m) RS232 480 Mbit/s USB Communication port protocol USB port USB - SoMachine-Network Non isolated serial link: Modbus master/slave - RTU/ASCII or SoMachine-Network Ethernet Port Ethernet 10BASE-T/100BASE-TX 1 328.08ft (100m) copper cable Communication service DHCP client Modbus TCP slave device Ethernet/IP adapter Modbus TCP client Modbus TCP server Local signalling for PWR 1 LED (green) for RUN 1 LED (green) for module error (ERR) 1 LED (red) for SD card access (SD) 1 LED (green) for BAT 1 LED (red) for I/O state 1 LED per channel (green) for SL 1 LED (green) for ACT Ethernet network activity (green) for Link (Link Status) Ethernet network link (yellow) Electrical connection terminal block, 3 for connecting the 24 V DC power supply connector, 4 for analogue inputs Mini B USB 2.0 connector for a programming terminal removable screw terminal block, 10 for inputs removable screw terminal block, 11 for outputs Maximum cable distance between devices Shielded cable <32.81ft (10m) fast input Unshielded cable <98.43ft (30m) output Unshielded cable <98.43ft (30m) digital input Unshielded cable <3.28ft (1m) analog input Shielded cable <9.84ft (3m) fast output Insulation Between input and internal logic 500V AC Between fast input and internal logic 500V AC Non-insulated between inputs Between output and internal logic 500V AC Between output groups 500V AC Non-insulated between analogue input and internal logic Non-insulated between analogue inputs Marking CE Mounting support Top hat type TH35-15 rail IEC 60715 Top hat type TH35-7.5 rail IEC 60715 plate or panel with fixing kit Height 3.54in (90mm) Depth 2.76in (70mm) Width 2.76in (70mm) Net weight 0.58lb(US) (0.264kg) Environment Standards EN/IEC 61010-2-201 EN/IEC 61131-2 EN/IEC 60664-1 3 Product certifications LR CULus CSA DNV-GL RCM EAC ABS IACS E10 Environmental characteristic Ordinary and hazardous location Resistance to electrostatic discharge 8kV in air EN/IEC 61000-4-2 4kV on contact EN/IEC 61000-4-2 Resistance to electromagnetic fields 9.14V/m (10V/m) 80 MHz...1 GHz EN/IEC 61000-4-3 2.74V/m (3V/m) 1.4 GHz...2 GHz EN/IEC 61000-4-3 0.91V/m (1V/m) 2...2.7 GHz EN/IEC 61000-4-3 Resistance to magnetic fields 98.43A/m (30A/m) 50/60 Hz EN/IEC 61000-4-8 Resistance to fast transients 2kV EN/IEC 61000-4-4 power lines) 2kV EN/IEC 61000-4-4 relay output) 1kV EN/IEC 61000-4-4 I/O) 1kV EN/IEC 61000-4-4 Ethernet line) 1kV EN/IEC 61000-4-4 serial link) Surge withstand 2kV power lines (AC) common mode EN/IEC 61000-4-5 2kV relay output common mode EN/IEC 61000-4-5 1kV I/O common mode EN/IEC 61000-4-5 1kV shielded cable common mode EN/IEC 61000-4-5 0.5kV power lines (DC) differential mode EN/IEC 61000-4-5 1kV power lines (AC) differential mode EN/IEC 61000-4-5 1kV relay output differential mode EN/IEC 61000-4-5 0.5kV power lines (DC) common mode EN/IEC 61000-4-5 Resistance to conducted disturbances 10V 0.15...80 MHz EN/IEC 61000-4-6 3V 0.1...80 MHz Marine specification (LR, ABS, DNV, GL) 10V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) Marine specification (LR, ABS, DNV, GL) Electromagnetic emission Conducted emissions 79 dBV/m QP/66 dBV/m AV power lines (AC))0.15...0.5MHz EN/IEC 55011 Conducted emissions 73 dBV/m QP/60 dBV/m AV power lines (AC))0.5...300MHz EN/IEC 55011 Conducted emissions 120...69 dBV/m QP power lines)10...150kHz EN/IEC 55011 Conducted emissions 63 dBV/m QP power lines)1.5...30MHz EN/IEC 55011 Radiated emissions 40 dBV/m QP class A 10 m)30...230MHz EN/IEC 55011 Conducted emissions 79...63 dBV/m QP power lines)150...1500kHz EN/IEC 55011 Radiated emissions 47 dBV/m QP class A 10 m)200...1000MHz EN/IEC 55011 Immunity to microbreaks 10ms Ambient air temperature for operation 14...131F (-10...55C) horizontal installation) 14...95F (-10...35C) vertical installation) Ambient air temperature for storage -13...158F (-25...70C) Relative humidity 10...95%, without condensation in operation) 10...95%, without condensation in storage) IP degree of protection IP20 with protective cover in place Pollution degree <= 2 Operating altitude 0...6561.68 ft (0...2000 m) Storage altitude 0.00...9842.52ft (0...3000m) Vibration resistance 3.5 mm 5...8.4Hz symmetrical rail 3.5 mm 5...8.4Hz panel mounting 1 gn 8.4...150Hz symmetrical rail 1 gn 8.4...150Hz panel mounting Shock resistance 98 m/s 11ms Ordering and shipping details Category 22533 - M2XX PLC & ACCESSORIES Discount Schedule MSX GTIN 00785901956563 Nbr. of units in pkg. 1 Package weight(Lbs) 0.97lb(US) (0.44kg) Returnability Yes Country of origin TW 4 Packing Units Package 1 Height 3.82in (9.700cm) Package 1 width 4.21in (10.700cm) Package 1 Length 5.04in (12.800cm) Offer Sustainability Sustainable offer status Green Premium product California proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov REACh Regulation REACh Declaration EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope) EU RoHS Declaration Mercury free Yes RoHS exemption information Yes China RoHS Regulation China RoHS declaration Environmental Disclosure Product Environmental Profile Circularity Profile End of Life Information WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. PVC free Yes 5 Product data sheet Dimensions Drawings Dimensions 6 TM221ME16R Product data sheet Mounting and Clearance TM221ME16R Mounting on a Rail 7 Product data sheet Mounting and Clearance Direct Mounting on a Panel Surface (1) Install a mounting strip 8 TM221ME16R Product data sheet Mounting and Clearance TM221ME16R Mounting Correct Mounting Position Acceptable Mounting Position Incorrect Mounting Position 9 Product data sheet Mounting and Clearance Clearance 10 TM221ME16R Product data sheet Connections and Schema TM221ME16R Digital Inputs (1) A: B: The COM0 terminals are connected internally. Sink wiring (positive logic). Source wiring (negative logic). Ix I0, I1, I6, I7 11 Product data sheet Connections and Schema TM221ME16R Digital Outputs () (1) (2) A: B: 12 Type T fuse The COM1 and COM2 terminals are not connected internally. To improve the life time of the contacts, and to protect from potential inductive load damage, you must connect a free wheeling diode in parallel to each Source wiring (negative logic). Sink wiring (positive logic). Product data sheet Connections and Schema TM221ME16R Analog Inputs The (-) poles are connected internally. Pin Wire Color AN0 / AN1 Red 0V Black 13 Product data sheet Connections and Schema TM221ME16R Ethernet Connection Pin N Signal 1 TD+ 2 TD- 3 RD+ 4 - 5 - 6 RD- 7 - 8 - 14 Product data sheet Connections and Schema TM221ME16R USB Mini-B Connection 15 TM221ME16R Product data sheet Connections and Schema SL1 Connection SL1 N RS 232 RS 485 1 RxD N.C. 2 TxD N.C. 3 RTS N.C. 4 N.C. D1 5 N.C. D0 6 CTS N.C. 7 N.C.* 5Vdc 8 Common Common N.C.: not connected * : 5 Vdc delivered by the controller. Do not connect. 16