https://www.phoenixcontact.com/us/products/2866462
04/20/2021Page1/8
Power supply unit-TRIO-PS/3AC/24DC/ 5-2866462
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Primary-switched TRIO POWER power supply for DIN rail mounting, input: 3-phase, output: 24 V DC/5 A
Product Description
TRIO POWER power supplies with standard functionality
TRIO POWER is particularly suited to standard machine production, thanks to 1- and 3-phase versions up to 960W. The wide-range input and the
international approval package enable worldwide use.
The robust metal housing, the high electric strength, and the wide temperature range ensure a high level of power supply reliability.
Your advantages
Use the third negative terminal block as a grounding terminal block and minimize installation costs
Rugged design with metal housing and wide temperature range from -25 to +70°C
Maximum operational reliability thanks to high MTBF (mean time between failures) of more than 500,000 hours and high dielectric strength of up to
300 V AC
Compensation of voltage drops by means of output voltage that can be adjusted on the front
Key Commercial Data
Packing unit 1 pc
GTIN
GTIN 4046356128544
Weight per Piece (excluding packing) 740.000 g
Custom tariff number 85044030
Country of origin China
Technical data
Dimensions
Width 40 mm
https://www.phoenixcontact.com/us/products/2866462
04/20/2021Page2/8
Power supply unit-TRIO-PS/3AC/24DC/ 5-2866462
Technical data
Dimensions
Height 130 mm
Depth 115 mm
Installation distance right/left 0 mm / 0 mm
Installation distance top/bottom 50 mm / 50 mm
Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C ... 70 °C (> 55° C derating : 2.5%/K)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Climatic class 3K3 (in acc. with EN 60721)
Degree of pollution 2
Input data
Nominal input voltage range 2x / 3x 400 VAC ... 500 VAC
Input voltage range 3x 320 VAC ... 575 VAC (for 3-phase operation)
2x 360 VAC ... 575 VAC (for 2-phase operation)
AC frequency range 45 Hz ... 65 Hz
Discharge current to PE < 3.5 mA
Current consumption 3x 0.3 A (400VAC)
3x 0.25 A (500 VAC)
2x 0.65 A (400VAC)
2x 0.5 A (500 VAC)
Nominal power consumption 211 VA
Inrush current < 15 A
Mains buffering time > 20 ms (3x 400 V AC)
> 30 ms (3x 480 V AC)
Recommended breaker for input protection 6 A ... 16 A (Characteristics B, C, D, K)
Power factor (cos phi) 0.64
Type of protection Transient surge protection
Protective circuit/component Varistor
Output data
Nominal output voltage 24 VDC ±1%
Setting range of the output voltage (USet)22.5 VDC ... 29.5 VDC (> 24 VDC, constant capacity restricted)
Nominal output current (IN) 5 A (UOUT = 24 V DC)
Derating 55 °C ... 70 °C (2.5%/K)
Connection in parallel Yes, for redundancy and increased capacity
Connection in series yes
https://www.phoenixcontact.com/us/products/2866462
04/20/2021Page3/8
Power supply unit-TRIO-PS/3AC/24DC/ 5-2866462
Technical data
Output data
Feedback voltage resistance 35 VDC
Protection against overvoltage at the output (OVP) < 35 VDC
Max. capacitive load unlimited
Active current limitation Approx 6 A (in the event of a short-circuit)
Control deviation < 1 % (change in load, static 10 % ... 90 %)
< 2 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple < 30 mVPP
Output power 120 W
Typical response time < 1 s
Peak switching voltages nominal load < 30 mVPP
Maximum power dissipation in no-load condition 4 W
Power loss nominal load max. 15 W
General
Net weight 0.6 kg
Operating voltage display Green LED
Efficiency 89 % (at 400 V AC and nominal values)
MTBF (IEC 61709, SN 29500) > 1474000 h
Insulation voltage input/output 4 kV AC (type test)
2 kV AC (routine test)
Insulation voltage input / PE 2 kV AC (type test)
2 kV AC (routine test)
Insulation voltage output / PE 500 VDC (routine test)
Degree of protection IP20
Protection class I (with PE connection)
Mounting position horizontal DIN rail NS 35, EN 60715
Assembly instructions alignable: horizontally 0mm, vertically 50mm
Connection data, input
Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Stripping length 9 mm
https://www.phoenixcontact.com/us/products/2866462
04/20/2021Page4/8
Power supply unit-TRIO-PS/3AC/24DC/ 5-2866462
Technical data
Connection data, input
Screw thread M2,5
Connection data, output
Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 16
Conductor cross section AWG max. 12
Stripping length 9 mm
Screw thread M2,5
Signaling
Status display "DC OK" LED green
Note on status display UOUT > 21.5 V: LED lights up
Standards and Regulations
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Noise immunity EN 61000-6-2:2005
Connection in acc. with standard CUL
Standards/regulations EN 61000-4-2
Contact discharge 4 kV (Test Level 2)
Standards/regulations EN61000-4-3
Frequency range 80 MHz ... 1 GHz
Test field strength 10 V/m
Frequency range 1.4 GHz ... 2 GHz
Test field strength 3 V/m
Standards/regulations EN61000-4-4
Comments Criterion B
Standards/regulations EN61000-6-3
EN61000-4-6
Frequency range 0.15 MHz ... 80 MHz
Voltage 10 V (Test Level 3)
Standards/regulations EN61000-4-11
Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Standard - Electrical safety EN60950-1/VDE0805 (SELV)
Standard – Electronic equipment for use in electrical power installations
and their assembly into electrical power installations EN50178/VDE0160 (PELV)
https://www.phoenixcontact.com/us/products/2866462
04/20/2021Page5/8
Power supply unit-TRIO-PS/3AC/24DC/ 5-2866462
Technical data
Standards and Regulations
Standard – Safety extra-low voltage EN60950-1 (SELV)
EN60204 (PELV)
Standard - Safe isolation DINVDE0100-410
Standard – Protection against shock currents, basic requirements for
protective separation in electrical equipment EN50178
Standard – Limitation of mains harmonic currents EN61000-3-2
UL approvals UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950-1
Shock 15g in all directions in acc. with IEC 60068-2-27
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min.
Environmental Product Compliance
REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 25;
For details about hazardous substances go to tab “Downloads”, Category
“Manufacturer's declaration”
Drawings
Block diagram
L1
L2
(L3)
PE
Classifications
eCl@ss
eCl@ss 10.0.1 27040701
eCl@ss 11.0 27040701
eCl@ss 4.0 27040700
eCl@ss 4.1 27040700
eCl@ss 5.0 27049000
eCl@ss 5.1 27049000
eCl@ss 6.0 27049000
eCl@ss 7.0 27049002
https://www.phoenixcontact.com/us/products/2866462
04/20/2021Page6/8
Power supply unit-TRIO-PS/3AC/24DC/ 5-2866462
Classifications
eCl@ss
eCl@ss 9.0 27040701
ETIM
ETIM 2.0 EC001039
ETIM 3.0 EC001039
ETIM 4.0 EC000599
ETIM 6.0 EC002540
ETIM 7.0 EC002540
UNSPSC
UNSPSC 6.01 30211502
UNSPSC 7.0901 39121004
UNSPSC 11 39121004
UNSPSC 12.01 39121004
UNSPSC 13.2 39121004
UNSPSC 18.0 39121004
UNSPSC 19.0 39121004
UNSPSC 20.0 39121004
UNSPSC 21.0 39121004
Approvals
Approvals
Approvals
UL Listed / UL Recognized / cUL Recognized / cUL Listed / EAC / EAC / cULus Recognized / cULus Listed
Ex Approvals
Approval details
UL Listed http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 123528
https://www.phoenixcontact.com/us/products/2866462
04/20/2021Page7/8
Power supply unit-TRIO-PS/3AC/24DC/ 5-2866462
Approvals
UL Recognized http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 211944
cUL Recognized http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 211944
cUL Listed http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 123528
EAC EAC-Zulassung
EAC RU*DE*08.B.01873/19
cULus Recognized
cULus Listed
Accessories
Accessories
Assembly adapter
Assembly adapters-UWA 182/52-2938235
Universal wall adapter for securely mounting the device in the event of strong vibrations. The device is screwed directly
onto the mounting surface. The universal wall adapter is attached on the top/bottom.
https://www.phoenixcontact.com/us/products/2866462
04/20/2021Page8/8
Power supply unit-TRIO-PS/3AC/24DC/ 5-2866462
Accessories
Device protection
Type 3 surge protection device-PLT-SEC-T3-3S-230-FM-2905230
Plug-in device protection, according to type 3/class III, for 3-phase power supply networks with separate N and PE (5-
conductor system: L1, L2, L3, N, PE), with integrated surge-proof fuse and remote indication contact.
Type 3 surge protection device-PLT-SEC-T3-24-FM-UT-2907916
Type3 surge protection, consisting of protective plug and base element, with integrated status indicator and remote
signaling for single-phase power supply networks. Nominal voltage: 24VAC/DC
Mounting rail adapter
DIN rail adapter-UTA 107-2853983
Universal DIN rail adapter, for screwing on switchgear
Phoenix Contact 2021 © - all rights reserved
http://www.phoenixcontact.com