IEC inlet filters FN 329 Performance IEC inlet filter n n n Rated currents up to 6A Integrated earth line choke Optional medical versions (B type) Technical specifications Maximum continuous operating voltage: Operating frequency: Rated currents: High potential test voltage: Protection category: Temperature range (operation and storage): Design corresponding to: Flammability corresponding to: MTBF @ 40C/230V (Mil-HB-217F): Typical electrical schematic 250VAC, 50/60Hz dc to 400Hz 1 to 6A @ 50C max. P -> E 2000VAC for 2 sec (standard types) P -> E 2500VAC for 2 sec (B types) P -> N 760VAC for 2 sec IP40 according to IEC 60529 -25C to +85C (25/85/21) UL 1283, CSA 22.2 No. 8 1986, EN 60939 UL 94V-2 or better 600,000 hours Features and benefits The FN 321 IEC inlet filter combines an Approvals n High conducted attenuation performance, IEC inlet and mains filter with excellent filter based on chokes with high saturation attenuation in a small form factor. The FN 329 resistance and excellent thermal behavior. performance power entry module offers n Integrated earth line choke. additional EMI suppression for the earth line. n Rear or front flange mounting. Choosing the FN 329 compact power entry n Optional low leakage current versions for module brings you the rapid availability of a Cx R 2xL1 2xCy N N` E E` P` P Load Line L2 Typical applications n Portable electrical and electronic equipment n Small to medium-sized machines and household equipment n Single-phase power supplies, switch mode power supplies medical applications. n Consumer goods standard filter associated with the necessary n Faston or solder terminal connections. n Test and measurement equipment safety acceptances. Standard IEC connector n Rated currents up to 6A. n EDP and office equipment filters are a practical solution helping you to n Custom-specific versions are available on n Medical equipment request. n Rack mounting equipment pass EMI system approval in a short time. A wide selection on current ratings, output connections and low leakage versions for medical applications helping you to select the desired solution for your application. > Components > FN 329 Filter selection table Filter Rated current @ 40C (25C) Leakage current* @ 230VAC/50Hz FN 329-1-.. FN 329-3-.. FN 329-6-.. [A] 1 (1.2) 3 (3.5) 6 (7.2) [A] 560 560 560 [mH] 6.3 1.25 0.48 [mH] 0.4 0.4 0.4 FN 329B-1-.. FN 329B-3-.. FN 329B-6-.. 1 (1.2) 3 (3.5) 6 (7.2) 2 2 2 6.3 1.25 0.48 0.4 0.4 0.4 * Inductance L1 L2 Capacitance Cx Cy [nF] 47 47 47 Resistance Output connections R Weight [nF] [k] 3.3 -01 -05 3.3 -01 -05 3.3 -01 -05 [g] 55 55 55 47 47 47 Max. leakage under normal operating conditions. Note: if the neutral line is interrupted, worst case leakage could reach twice this level. Product selector FN 329x-yy-.. 01: Solder lug 05: Faston 6.3 x 0.8mm 1 to 6: Rated current Blank: Standard version B: Medical version (with bleed resistor and without Y2-capacitor) For example: FN 329-1-01, FN 329-3-05, FN 329B-6-05 Typical filter attenuation Per CISPR 17; A = 50/50 sym; B = 50/50 asym; C = 0.1/100 sym; D = 100/0.1 sym 1A types 3 and 6A types 1000 1000 1000 -05 -05 -05 55 55 55 > Components > FN 329 Mechanical data Connection style -01 Connection style -05 B B 6.3 x 0.8 S C S J E C A J E H A H F G D I G F D I Panel cut out M N P R C Dimensions A B C D E F G H I J M N P R S FN 329 Connection style -01 FN 329 Connection style -05 Tolerances 51.5 26 40 46.6 27.9 5.5 20.1 O3.3 11.4 10.9 R3 21.5 28.5 M3 90 51.5 26 40 46.6 27.9 5.5 20.1 O3.3 13.4 10.9 R3 21.5 28.5 M3 90 0.5 0.3 0.2 0.3 +0.5 0.3 0.5 0.2 0.2 All dimensions in mm; 1 inch = 25.4mm Tolerances according: ISO 2768 / EN 22768 Your local partner: To find your local partner within Schaffner's global network, please go to www.schaffner.com January 2007