100507/11 www.lem.com
Page 1/3
Current Transducer HAIS 50..400-P
and HAIS 50..100-TP
For the electronic measurement of currents: DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
Primary nominal Primary current Type RoHS since
current rms measuring range date code
IPN (A) IPM (A)
50 ± 150 HAIS 50-P, HAIS 50-TP 1) 45231, 46272
100 ± 300 HAIS 100-P, HAIS 100-TP 1) 45231, 46012
150 ± 450 HAIS 150-P 46172
200 ± 600 HAIS 200-P 45231
400 ± 600 HAIS 400-P 47096
VOUT Output voltage (Analog) @ IP VOE ± (0.625· IP/IPN) V
GTH Theoretical sensitivity 0.625 V/IPN
VREF Reference voltage 2) - Output voltage 2.5 ± 0.025 V
VREF Output impedance typ. 200 W
VREF Load impedance ≥ 200 kW
RL Load resistance ≥ 2 kW
ROUT Output internal resistance < 5 W
CL Capacitive loading (± 20 %) =4.7 nF
VC Supply voltage (± 5 %)3) 5 V
IC Current consumption @ VC = 5 V 19 mA
X Accuracy 4) @ IPN , TA = 25°C ≤ ± 1 % of IPN
εL Linearity error 0 .. IPM ≤ ± 0.5 % of IPN
TCVOE Temperature coefcient of VOE ≤ ± 0.3 mV/K
TCVREF Temperature coefcient of VREF, +25°C...+85°C ≤ ± 0.01 %/K
-40°C...+25°C ≤ ± 0.015 %/K
TCVOE/VREF
Temperature coefcient of VOE / VREF ≤ ± 0.2 mV/K
TCG Temperature coefcient of G
≤ ± 0.05 % of reading/K
VOE Electrical offset voltage @ IP = 0, TA = 25°C VREF ± 0.025 V
VOM Magnetic offset voltage @ IP = 0,
after an overload of IPM HAIS 50-(T)P < ± 0.5 % of IPN
HAIS 100-(T)P..400-P < ± 0.4 % of IPN
tra Reaction time @ 10 % of IPN < 3 µs
tr Response time to 90 % of IPN step < 5 µs
di/dt di/dt accurately followed > 100 A/µs
Vno Output voltage noise (DC ..10 kHz) < 15 mVpp
(DC .. 1 MHz) < 40 mVpp
BW Frequency bandwidth (- 3 dB) 5) DC .. 50 kHz
Notes:
1)
-TP version is equipped with a primary bus bar.
2)
It is possible to overdrive V
REF
with an external reference voltage
between 1.5 - 2.8 V providing its ability to sink or source approximately 5 mA.
3)
Maximum supply voltage (not operating) < 6.5 V
4)
Excluding Offset and Magnetic offset voltage.
5) Small signal only to avoid excessive heatings of the magnetic core.
LEM reserves the right to carry out modications on its transducers, in order to improve them, without prior notice.
IPN = 50 .. 400 A
Features
●Hall effect measuring principle
●Galvanic isolation between
primary and secondary circuit
●Isolation test voltage 2500V
●Low power consumption
●Single power supply +5V
●Fixed offset & gain
●Bus bar version available for 50A
and 100A ratings.
● Isolated plastic case recognized
according to UL94-V0.
Advantages
● Small size and space saving
●Only one design for wide current
ratings range
●High immunity to external
interference.
●VREF. IN/OUT
Applications
●AC variable speed drives
●Static converters for DC motor
drives
●Battery supplied applications
●Uninterruptible Power Supplies
(UPS)
●Switched Mode Power Supplies
(SMPS)
●Power supplies for welding
applications.
Application domain
●Industrial
All data are given with a RL = 10 kW
Accuracy - Dynamic performance data
Electrical data