836
PRODUCTS UNLIMITED
Dimensions are shown for
reference purposes only.
Dimensions are in inches over
(millimeters) unless otherwise
specified.
Catalog 1308242
Issued 3-03
Specifications and availability
subject to change.
www.tycoelectronics.com
Technical support:
Refer to inside back cover.
Contact Ratings
Features
• 4-pole contactors.
• Convenient “universal” mounting plate.
• Optional interlock/auxiliary switches available.
Coil Data
Nominal Coil Voltage 24 120 208/240 277 480
Maximum Pickup Volts 19.2 93 177 220 384
Drop-Out Volts Range 6 -15 20 - 70 40 - 140 50-185 150 - 270
Nominal Inrush VA @ 50 Hz 68 68 68 58 48
Nominal Inrush VA @ 60 Hz 60 60 60 52 52
Nominal Sealed VA @ 50 Hz 14 14 14 11 11
Nominal Sealed VA @ 60 Hz 9 9 9.5 9.5 9
Nominal DC Resistance - Ohms 5 148 520 750 2700
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that users also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
Full Number Line Locked Resistive Maximum Horsepower
Load of Voltage Rotor Amps Voltage Single Three
Amps Poles Amps Rating Phase Phase
240/277 150 35 110/120 2 -
25 3 480 125 35 200/208 - 7.5
600 100 35 240/277 5 10
480 - 15
240/277 180 40 110/120 2 -
30 3 480 150 40 200/208 - 10
600 120 40 240/277 5 10
480 - 15
240/277 240 50 110/120 3 -
40 3 480 200 50 200/208 - 10
600 160 50 240/277 7.5 10
480 - 20
Contact Data @ 25°C
Arrangements: 4 Form X (4PST-NO-DM).
Maximum Ratings: See Contact Ratings Table.
Material: Silver Cadmium Oxide.
Coil Data @ 25°C
Voltage: 24 - 480 VAC, 50/60 Hz. See Coil Data Table below.
Insulation Class: UL Class B (130°C).
Duty Cycle: Continuous.
Environmental Data
Temperature Range: Storage and Operating: -40°C – +65°C.
Flammability: UL 94-HB housing.
Mechanical Data
Contact Termination:
25, 30 FLA Models
Type: #10-32 Screw with quad 0.250” (6.35 mm) quick connects.
Wire Size: 16-8 AWG (Stranding must be split for 8 AWG wire.)
Tightening Torque: 25 in.-lbs.
40 FLA Models
Type: Box Lug with dual 0.250” (6.35 mm) quick connects.
Wire Size: 14-4 Cu/Al AWG
Tightening Torque: 40 in.-lbs.
Coil Termination: Dual 0.250” (6.35 mm) quick connects, standard.
A 0.250” quick connect and a #6-32 screw, optional.
Arc Cover: Optional on 25-30 FLA models, standard on 40 FLA models.
Weight: 24 oz. (683 g) approximately
Model 93 - 3100 series
Definite Purpose Contactor
4-pole, 25-40 FLA
AC Coil
File E75492
File EN60947-4-1:1991
IEC 947-4-1
837
PRODUCTS UNLIMITED
Dimensions are shown for
reference purposes only.
Dimensions are in inches over
(millimeters) unless otherwise
specified.
Catalog 1308242
Issued 3-03
Specifications and availability
subject to change.
www.tycoelectronics.com
Technical support:
Refer to inside back cover.
None at present.
Standard part numbers listed below are more likely to be available from stock.
Ordering Information
ORDERING NOTE: “Standard” terminals need not be specified
in the “Ordering Information” chart above. “Special” terminals
are offered on a special order basis. Special order items may be
subject to extended leadtimes and significant minimum order
quantities. Your Tyco Electronics sales engineer must consult
with the factory before providing price and availability
information regarding items with these options.
Typical Part No. B3100 - 40 Q 9 999
1. Series:
3100 = 4-pole, 25-40 FLA contactor
2.Packaging:
Y = Individual Pack
- = Bulk Pack
A-ZZZ = Customer specific information (assigned by factory)
3.Pole Configuration:
40 = 4 Form X (4PST-NO-DM)
4.Coil Voltage (50/60 Hz.):
Q = 24VAC U = 208/240VAC H = 480VAC J = 120VAC, molded M = 277VAC, molded
T = 120VAC V = 277VAC I = 24VAC, molded K = 208/240VAC, molded W = 480VAC, molded
5.Contact Ratings (Inductive):
8 = 25 FLA 9 = 30 FLA 10 = 40 FLA
6.Customer ID Suffix:
999 = Standard Model 000-998 = Factory assigned customer ID
7. Option Code:
Leave Blank = No customer-specific options A - ZZ = Factory assigned customer-specific options.
Outline Dimensions Termination Options
Standard on
25, 30 FLA
#10-32 Combination
Phillips, Slotted &
5/16 Hex Head
#12 Washer
Special on
25, 30 FLA
#10-32 Sems
Screw
with Pressure
Plate
Standard
on 40 FLA
Lug accepts 14-4
Cu/Al AWG
.253
(6.43)
Factory Modifications Field Added Kits
Description Contact Config. Kit Catalog Number of
NO NC Number Kits Required
Single unit interlock 1 0 34220-303N 1
configurations listed. 0 1 34220-331N 1
Maximum of two. Must 1 1 34220-332N 1
be same polarity. 2 0 34220-303N 2
See footnote (1) for ratings. 0 2 34220-331N 2
2 2 34220-332N 2
SPDT Circuit 1 1 34220-337N 1
See footnote (2) for ratings. 2 2 34220-337N 2
SPDT Dry Circuit, 0.1 amp max. 1 1 34220-341N 1
Gold Flashed Contacts 2 2 34220-340N 1
Auxiliary Switches
Various interlock / auxiliary switches are available for the Model 93 contactor.
NORMALLY OPEN & CLOSED
-332 STYLE
Equipped with 0.250” (6.35) Quick Connect Terminals
Shown with Optional Auxiliary Switch
NORMALLY CLOSED
-331 STYLE
NORMALLY OPEN
-303 STYLE
Factory Modifications Field Added Kits
Description Contact Config. Kit Catalog Number of
NO NC Number Kits Required
Single unit interlock 1 0 34220-342N 1
configurations listed. 0 1 34220-343N 1
Maximum of two. Must 1 1 34220-344N 1
be same polarity. (note 1)
Equipped with #6-32 Screw Terminals & Saddle Clamps
Footnotes: Ratings of Auxiliary Interlocks / Switches
(1) Contact Rating Single Circuit NO or NC (2) Contact Rating SPDT (337):
and two circuit NO/NC: 10A, 1/3 HP, 125 or 250 VAC
120V 240V 480V 600V 1/2A, 125 VDC; 1/4A, 250 VDC:
Break 3.0A 1.5A 0.75A 0.6A 4A 120 VAC on Lamp Load
Make 30A 15A 7.5A 6A
Continuous 10A 10A 10A 10A
SPDT
-337 & -341 STYLE
W/ #6-32 SCREW & SADDLE CLAMP
-344 STYLE
2.493
(63.3)
2.633
(66.9)
3.055
(77.6)
3.75
(95.25)
2.00
(50.8)
.203 TYP
(5.156)
3.125
(79.38)
3.25
(82.55)
.250
(6.35)
.250
(6.35)
.203 TYP
(5.156)