SDR-240 series 240W Single Output Industrial DIN RAIL with PFC Function SE PQ M IF SPECIFICATION MODEL OUTPUT SDR-240-24 SDR-240-48 DC VOLTAGE 24V 48V RATED CURRENT 10A 5A CURRENT RANGE 0 ~ 10A 0 ~ 5A RATED POWER 240W 240W PEAK CURRENT 15A 7.5A PEAK POWER Note.6 360W (3sec.) RIPPLE & NOISE (max.) Note.2 100mVp-p 120mVp-p VOLTAGE ADJ. RANGE 48 ~ 55V 1.0% 24 ~ 28V VOLTAGE TOLERANCE Note.3 1.0% LINE REGULATION 0.5% LOAD REGULATION 1.0% SETUP, RISE TIME 1500ms, 60ms/230VAC HOLD UP TIME (Typ.) 20ms/230VAC VOLTAGE RANGE 88 ~ 264VAC FREQUENCY RANGE 47 ~ 63Hz POWER FACTOR (Typ.) INPUT 47 EFFICIENCY (Typ.) 0.93/230VAC GL .. 0.5% 1.0% 3000ms, 60ms/115VAC at full load 20ms/115VAC at full load 124 ~ 370VDC 0.99/115VAC at full load Note.8 94% AC CURRENT (Typ.) INRUSH CURRENT (Typ.) LEAKAGE CURRENT OVERLOAD PROTECTION OVER VOLTAGE OVER TEMPERATURE 2.6A/115VAC 33A/115VAC 1.3A/230VAC 65A/230VAC <1mA / 240VAC Normally works within 110 ~ 150% rated output power for more than 3 seconds and then shut down o/p voltage with auto-recovery >150% rated power, constant current limiting with auto-recovery within 2 seconds and may cause to shut down if over 2 seconds 56 ~ 65V 29 ~ 33V Protection type : Shut down o/p voltage with auto-recovery 955 (TSW : detect on heatsink of power switch) Protection type : Shut down o/p voltage, recovers automatically after temperature goes down FUNCTION DC OK REALY CONTACT RATINGS (max.) 60Vdc/0.3A, 30Vdc/1A, 30Vac/0.5A resistive load WORKING TEMP. Note.5 -25 ~ +70 (Refer to "Derating Curve") 20 ~ 95% RH non-condensing WORKING HUMIDITY ENVIRONMENT STORAGE TEMP., HUMIDITY TEMP. COEFFICIENT VIBRATION SAFETY STANDARDS WITHSTAND VOLTAGE SAFETY & ISOLATION RESISTANCE EMC EMC EMISSION (Note 4) OTHERS 0.03%/ (0 ~ 50) Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 UL508, TUV EN60950-1 approved I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC O/P-DC OK:0.5KVAC I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25/ 70% RH Compliance to EN55011, EN55022 (CISPR22), EN61204-3 Class B, EN61000-3-2,-3 EMC IMMUNITY Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A, SEMI F47, GL approved MTBF 169.3K hrs min. DIMENSION 63*125.2*113.5mm (W*H*D) 1.03Kg; 12pcs/13.4Kg/1.06CUFT PACKING NOTE -40 ~ +85, 10 ~ 95% RH MIL-HDBK-217F (25) File Name:SDR-240-SPEC 2014-10-08 240W Single Output Industrial DIN RAIL with PFC Function SDR-240 series Mechanical Specification Unit:mm 113.5 Case No. 979A 125.2 TB1 DC OK 1 63 DC OK 3 +V ADJ. 2 TB2 1 2 3 4 5 6 + Terminal Pin No. Assignment (TB1) 35 Pin No. 1 2 3 ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15 Assignment FG AC/N AC/L Terminal Pin No. Assignment (TB2) Pin No. 1,2 3,4 5,6 Assignment Relay Contact DC OUTPUT +V DC OUTPUT -V Block Diagram DC OK I/P EMI FILTER & RECTIFIERS POWER SWITCHING PFC CIRCUIT RECTIFIERS & FILTER +V -V O.C.P. U.V.P. FG PFC CONTROL O.L.P. PWM & PFC CONTROL DETECTION CIRCUIT O.V.P. DC OK Relay Contact Contact Close PSU turns on / DC OK. Contact Open PSU turns off / DC Fail. Contact Ratings (max.) 30V/1A resistive load. File Name:SDR-240-SPEC 2014-10-08 SDR-240 series 240W Single Output Industrial DIN RAIL with PFC Function Peak Loading (1) (2) 360W 360W 240W 120W 100 sec. 3 sec. 10 sec. 3 sec. Derating Curve Output derating VS input voltage 100 150 90 For 3 sec. (typ.) 112.5 80 70 LOAD (%) LOAD (%) 100 Continuous 75 60 -25 60 50 40 0 10 20 30 40 50 AMBIENT TEMPERATURE () 60 70 (VERTICAL) 88 100 110 135 155 230 264 INPUT VOLTAGE (V) 60Hz File Name:SDR-240-SPEC 2014-10-08 Mouser Electronics Authorized Distributor Click to View Pricing, Inventory, Delivery & Lifecycle Information: Mean Well: SDR-240-24 SDR-240-48