1
Power Entry Modules with Line Filter 5120
https://www.schurter.com /PG06
EMC Products
IEC Appliance Inlet C14 or C18 with Filter, ECO design, Front- or Rear Side Mounting
Front side mounting with plastic flange Snap-in mounting
Quick connect terminals 6.3 x 0.8 mm
Protection class II
Screw-on mounting
with wires (stranded)
See below:
Approvals and Compliances
C14
70° C
C18
70° C
Description
- Panel mount :
Screw-on version from front or rear side, snap-in version from front
side, PCB Version from rear side
- 2 Functions :
Appliance Inlet protection class I or II , Line filter in standard and medi-
cal version
- Solder, quick connect or wire (stranded)
- PCB Mounting
- Earth Terminal
Unique Selling Proposition
- Various variants
- Metal flange for optimal shielding
- Compact design
- Variants for protection class I and II
Characteristics
- Compact high performance filter
Optimal shielding due to completely closed filter case, unpotted
- Suitable for assembly in metal plated plastic housings
- Suitable for use in equipment according to IEC/UL 60950
Suitable for use in medical equipment according to IEC/UL 60601-1
Other versions on request
- Snap-in for panel thickness >2mm to 3mm
- flexible wire with various lenghts
- Class X1- and Y1-capacitors for enhanced withstand voltage
- Medical version M80
- Variant with notch for V-Lock mating Cordsets
References
Alternative: version without line filter 6100-3; 6100-4; 6102-3; 6102-5
Weblinks
pdf datasheet, html-datasheet, General Product Information, Distributor-
Stock-Check, Accessories, Detailed request for product, Landing Page
Newly available variants corresponding to V-Lock mating cordset. The connector is equipped with a notch intended for use with the latching cordset.
The cord latching system prevents against accidental removal of the cordset.
Technical Data
Ratings IEC 1 - 10 A @ Ta 40 °C / 250 VAC; 50 Hz
Ratings UL/CSA 1 - 15 A @ Ta 40 °C / 250 VAC; 60 Hz
Leakage Current standard < 0.5 mA (250 V / 60 Hz)
medical < 5 µA (250 V / 60 Hz)
Dielectric Strength > 1.7 kVDC between L-N
> 2.7 kVDC between L/N-PE
Test voltage (2 sec)
Allowable Operation Tempe-
rature
-25 °C to 85 °C
Climatic Category 25/085/21 acc. to IEC 60068-1
IP-Protection from front side IP 40 acc. to IEC 60529
Protection Class Suitable for appliances with protection
class I or II acc. to IEC 61140
Terminal Quick connect terminals 6.3 x 0.8 mm
Solder terminals
Flexible wire AWG18 (15A AWG16),
150 mm
Panel Thickness S Screw with plastic flange: max 8 mm
Mounting screw torque max 0.5 Nm
Snap-in: 0.8 mm to 2 mm
(all steps with one variant)
Material: Housing Themoplast / steel tin-plated, black /
metallic, UL 94V-0
appliance inlet/-outlet C14 / C18 acc. to IEC 60320-1,
UL 498, CSA C22.2 no. 42 (for cold
conditions) pin-temperature 70 °C, 10 A,
Protection Class I or II
Line Filter Standard and Medical Version, IEC
60939, UL 1283, CSA C22.2 no. 8
Technical Details
MTBF > 3'000'000 h acc. to MIL-HB-217 F
Approvals and Compliances
Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in Details about
Approvals