2Specifications are subject to change without notice (06.09.99)
Power ON delay Typ. 2 s
Power OFF delay ≤1 s
Output OFF delay
upon loss of Dupline carrier ≤20 ms
Indication for
Supply ON LED, green
Dupline carrier LED, yellow
Environment
Degree of protection IP 20
Pollution degree 3 (IEC 60664)
Operating temperature -20° to +50°C (-4° to +122°F)
Storage temperature
-50° to +85°C (-58° to +185°F)
Humidity (non-condensing) 20 to 80%
Mechanical resistance
Shock 15 G (11 ms)
Vibration 2 G (6 to 55 Hz)
Dimensions
Material
(see Technical information) 4H-housing
Weight
AC types 250 g
DC types 200 g
G 3430 5511, G 3430 5521
Supply Specifications
Power supply AC types
Overvoltage cat. III (IEC 60664)
Rated operational voltage
terminals 21 & 22 230 230 VAC ± 15% (IEC 60038)
115 115 VAC ± 15% (IEC 60038)
024 24 VAC ± 15%
Frequency 45 to 65 Hz
Voltage interruption ≤40 ms
Rated operational power Typ. 3.5 VA
Rated impulse withstand
voltage 230 4 kV
115 2.5 kV
024 800 V
Dielectric voltage
Supply - Dupline ≥4 kVAC (rms)
Supply - Outputs ≥4 kVAC (rms)
General Specifications Mode of Operation
G 3430 55.1 ...
8-channel receivers with 8
open collector NPN or PNP
outputs
Each output may be coded
individually by means of the
code programmer GAP 1605.
See separate data sheet.
The outputs are normally off.
When a transmitter coded to
the selected channel is acti-
vated, the output turns on
and remains on until the
respective channel becomes
deactivated (interruption or
short-circuiting of Dupline
carrier).
Power supply DC types
Overvoltage cat. III (IEC 60664)
Rated operational voltage
terminals 21 & 22 800 10 to 30 VDC
(ripple included)
Ripple ≤3 V
Reverse-polarity protection Yes
Rated operational current ≤150 mA
Inrush current ≤1 A
Rated impulse withstand
voltage 800 V
Dielectric voltage
Supply - Dupline ≥200 VAC (rms)
Supply - Outputs ≥4 kVAC (rms)
Operation Diagram
Dupline carrier
Transmission on channel for output 1
Output 1 (terminal 25)
Transm. on chan. for output 2
Power supply
Output 2 (terminal 26)