Micro Programmable Controller CPM2A
A--46
Micro Programmable Controller
CPM2A
The CPM2A brick-style controllers offer one of
the most powerful, small-scale control solutions
in the industry today. They provide 20, 30, 40
or 60 I/O point CPUs, pulse I/O for position
control, multiple communications ports and a
powerful instruction set.
DExpandable up to 120 I/O points
DPeripheral and RS-232C ports standard for direct
connection to serial devices and programming tools
DRemovable terminals
DSynchronized pulse control coordinates input devices
with control devices
DAuxiliary 24 VDC supply (AC type only)
DRelay or Transistor outputs
DAnalog I/O expansion modules available
DTemperature sensor input expansion modules available
DReal-time clock
D20 kHz high-speed counter input
DTwo, 10 kHz pulse outputs for position control
applications
Basic Configuration
Up to three Expansion I/O Modules or Special I/O Modules can be connected to any CPM2A CPU. The mounting order does not affect
the number of modules that can be mounted.
CPU Expansion I/O Module
or Special I/O Module
Expansion I/O Module
or Special I/O Module
Expansion I/O Module
or Special I/O Module
Optional Serial Com-
munications Adapters
CPM1-CIF01/CIF11
modify the Peripheral
Port for use as an
additional serial port.
A--47
Micro Programmable Controller CPM2A
Ordering Information
JCPU
Stock Note: Shaded models are normally stocked.
Description Input
i
t
Output
i
t
Power
l
Part number
p
p
points
p
points supply Relay outputs Transistor outputs
y
p
NPN (Sinking) PNP (Sourcing)
CPUs with 20 I/O points 12 8AC CPM2A-20CDR-A
AC model DC models
DC CPM2A-20CDR-D CPM2A-20CDT-D CPM2A-20CDT1-D
CPUs with 30 I/O points 18 12 AC CPM2A-30CDR-A
AC model DC models
DC CPM2A-30CDR-D CPM2A-30CDT-D CPM2A-30CDT1-D
CPUs with 40 I/O points 24 16 AC CPM2A-40CDR-A
AC model DC models
DC CPM2A-40CDR-D CPM2A-40CDT-D CPM2A-40CDT1-D
CPUs with 60 I/O points 36 24 AC CPM2A-60CDR-A
AC model DC models
DC CPM2A-60CDR-D CPM2A-60CDT-D CPM2A-60CDT1-D
A--48 Micro Programmable Controller CPM2A
JEXPANSION I/O AND SPECIAL I/O MODULES
Stock Note: Shaded models are normally stocked.
Description Max. number
of Units
Inputs Outputs Output type Part number
Expansion I/O 3max. 12 8Relay CPM1A-20EDR1
Transistor (NPN) CPM1A-20EDT
Transistor (PNP) CPM1A-20EDT1
8 CPM1A-8ED
8 Relay CPM1A-8ER
8 Transistor (NPN) CPM1A-8ET
Transistor (PNP) CPM1A-8ET1
Analog I/O 3max. 21Analog CPM1A-MAD01
CPM1A-MAD11
Temperature Sensor Inputs 3max. 2 Thermocouple CPM1A-TS001
p
p
1(SeeNote.) 4
p
CPM1A-TS002
3max. 2 Platinum resistance
t
h
t
CPM1A-TS101
21 analog thermometer CPM1A-TS101-DA
1(SeeNote.) 4 CPM1A-TS102
CompoBus/S I/O Link 3max. I/O Link of 8 input
bits and 8 output bits
CPM1A-SRT21
DeviceNet I/O Link
Module
3max. 32 input bits from the
Master and 32 output
bits to the Master
CPM1A-DRT21
Profibus-DP Slave
Module
3max. 16 bits
(Inputs
from the
Master)
16 bits
(Outputs
to the
Master)
CPM1A-PRT21
Shielded twisted pair cable, available commercially Belden #3079A cable
Note: If a CPM1A-TS002/102 is connected, only one other module (and not a CPM1A-TS002/102) can be connected.
JPROGRAMMING CONSOLES AND CABLES
Stock Note: Shaded models are normally stocked.
Product Part number
Programming console (2 m cable attached), connects directly to peripheral port CQM1H-PRO01-E
Programming console (2 m cable attached); order CS1W-CN114 adapter for peripheral port CQM1-PRO01-E
Programming console (Requires separate cable. See below.) C200H-PRO27-E
Connecting cable for C200H-PRO27-E 2 m cable C200H-CN222
g
4 m cable C200H-CN422
A--49
Micro Programmable Controller CPM2A
JSUPPORT SOFTWARE
Stock Note: Shaded models are normally stocked.
Product Functions Part number
CX-Programmer Jr. Windows-based programming software; reduced instruction set
and networking commands.
WS02-CXPC1-EJ-Vj.j
CX-Programmer Full programming software package programs micro, small and
larger controllers.
WS02-CXPC1-E-Vj.j
JSERIAL COMMUNICATIONS ADAPTERS AND CABLES
Stock Note: Shaded models are normally stocked.
CPM2A port Name Appearance Comments Cable length Part number
Peripheral RS-232C
Adapter
Cable-mounted communication
adapter converts peripheral port to
DB9-pin serial port.
3.3 m (10.8 ft) CQM1-CIF02
DIN mount communication adapter
converts peripheral port to DB9-pin
serial port.
3.3 m (10.8 ft) CPM1-CIF01
RS-232C RS-232C
C
a
b
l
e
Program download cable from
c
o
m
p
u
t
e
r
t
o
O
m
r
o
n
D
B
9
s
e
r
i
a
l
2 m (6.6 ft) C200HS-CN220-EU
C
a
b
l
e
c
o
m
p
u
t
e
r
t
o
O
m
r
o
n
D
B
9
s
e
r
i
a
l
port. CBL-202*
Communication cable to other Om-
d
i
i
t
h
D
B
9
i
l
t
3 m (9.8 ft) C200H-CN320-EU
ron devices with DB9 serial port
(
)
CBL-804*
Communication cable to other Om-
ron devices with DB9 serial port
5 m (16.4 ft) C200H-CN520-EU
Communication cable for NT31C
(
t
B
l
)
50 cm NT31C-CN510-EU
(port “B” only). 3m NT31C-CN320-EU
CBL-803*
Communication cable for NT31C
(port “B” only).
5m NT31C-CN520-EU
Programmable download cable
f
r
m
D
-
s
u
b
9
-
p
i
n
c
o
m
p
u
t
e
r
p
o
r
t
t
o
2m C200H-CN229-EU
f
r
m
D
-
s
u
b
9
-
p
i
n
c
o
m
p
u
t
e
r
p
o
r
t
t
o
RS-232C port. CBL-202*
Programmable download cable
f
r
m
D
s
u
b
2
5
p
i
n
c
o
m
p
u
t
e
r
p
o
r
t
t
o
2m XW2Z-200S
f
r
m
D
-
s
u
b
2
5
-
p
i
n
c
o
m
p
u
t
e
r
p
o
r
t
t
o
RS-232C port. 5m XW2Z-500S
Peripheral RS-422/
RS-485
Adapter
Converts CPM2A peripheral port to
RS-422/RS-485 communications.
3.3 m (10.8 ft) CPM1-CIF11
* Available in Canada only.
JBATTERY
Stock Note: Shaded models are normally stocked.
Product Function Part number
Backup Battery Replacement Backs up memory in the CPM2A CPU Unit. (One battery is al-
ready installed in the unit.)
CPM2A-BAT01
JPROGRAM TRANSFER EQUIPMENT
Stock Note: Shaded models are normally stocked.
A--50 Micro Programmable Controller CPM2A
Product Description Part number
Expansion Memory Unit Uploads and downloads program and setup memory areas to and
from the controller.
CPM1-EMU01-V1
EEPROM (256 kbits) Used with the Expansion Memory Unit EEPROM-CPM1-EMU01
JMANUALS
Product Description Part number
Operation manual CPM2A operation manual W352
Programming manual CPM1/CPM1A/CPM2A/CPM2C/SRM1(-V2) Programming Manual W353
S
p
e
c
i
f
i
c
a
t
i
o
n
s
JGENERAL SPECIFICATIONS
Item CPUs with
20 I/O points
CPUs with
30 I/O points
CPUs with
40 I/O points
CPUs with
60 I/O points
Supply voltage AC power 100 to 240 VAC, 50/60 Hz
p
p
y
g
DC power 24 VDC
Operating voltage AC power 85 to 264 VAC
p
g
g
range DC power 20.4 to 26.4 VDC
Power consumption AC power 60 VA max.
p
DC power 20 W max. (See separate table following this one for details)
Inrush current AC power 60 A max.
DC power 20 A max.
External power
s
u
p
p
l
y
(
A
C
p
o
w
e
r
Supply voltage 24 VDC
s
u
p
p
l
y
(
A
C
p
o
w
e
r
supplies only) Output capacity 300 mA (See Notes 1, 2, 3.)
Insulation resistance 20 Mmin. (at 500 VDC) between the external AC terminals and protective earth terminals.
Dielectric strength 2,300 VAC 50/60 Hz for 1 min between the external AC and protective earth terminals, leak-
age current: 10 mA max.
Noise immunity Conforms to IEC61000-4-4, 2 kV (power lines)
Vibration resistance 10 to 57 Hz, 0.075-mm amplitude, 57 to 150 Hz, acceleration: 9.8 m/s2in X, Y, and Z direc-
tions for 80 minutes each.
(Time coefficient; 8 minutes ×coefficient factor 10 = total time 80 minutes)
Shock resistance 147 m/s2three times each in X, Y, and Z directions.
Ambient temperature Operating: 0°to 55°C
p
Storage: --20°to 75°C
Humidity 10% to 90% (with no condensation)
Atmosphere Must be free from corrosive gas
Terminal screw size M3
Power interrupt time AC power supply: 10 ms min.
DC power supply: 2 ms min.
CPU weight AC power 650 g max. 700 g max. 800 g max. 1,000 g max.
g
DC power 550 g max. 600 g max. 700 g max. 900 g max.
Expansion weight Units with 20 I/O points: 300 g max.
Units with 8 output points: 250 g max.
Units with 8 input points: 200 g max.
MAD01 Analog I/O Unit: 150 g max.
MAD11 Analog I/O Unit: 250 g max.
Temperature Sensor Units: 250 g max.
CompoBus/S I/O Link Unit: 200 g max.
DeviceNet I/O Link Unit: 200 g max.
Profibus-DP Slave Unit: 125 g
Note: 1. Use the external power supply as the power supply for input devices only. (It cannot be used to drive output devices.)
2. If the external power supply current exceeds the rated current, or there is a short-circuit, the external power supply voltage will
drop and PLC operation will stop.
3. If there are 3 CPM1A-MAD11 modules mounted to a CPM2A-60CDR-A, the current for the external power supply must not
exceed 200 mA.
A--51
Micro Programmable Controller CPM2A
JCHARACTERISTICS
Control method Stored program method
I/O control method Cyclic scan with direct output (Immediate refreshing can be performed with IORF(97).)
Programming language Ladder diagram
Instruction length 1 step per instruction, 1 to 5 words per instruction
Instructions Basic instructions: 14
Special instructions: 105 instructions, 185 variations
Execution time Basic instructions: 0.64 µs (LD instruction)
Special instructions: 7.8 µs (MOV instruction)
Program capacity 4,096 words
User data memory 2,048 words
I/O
i
t
CPU Unit only 20 points 30 points 40 points 60 points
/
capacity With Expansion
I/O Modules
80 points max. 90 points max. 100 points max. 120 points max.
Memory protection HR area, AR area, program contents, read/write DM area contents, and counter values maintained
during power interruptions.
Memory backup Flash memory:
Program, read-only DM area, and PC Setup
Battery backup:
The read/write DM area, HR area, AR area, and counter values are backed up by a battery. (Battery life
is approximately 5 years.)
Self-diagnostic functions CPU failure (watchdog timer), I/O bus error, and memory failure, battery error
Program checks No END instruction and programming errors are checked at the start of operation.
Communications functions Built-in peripheral port:
Supports host link, peripheral bus, no-protocol, or Programming Console connections.
Built-in RS-232C port:
Supports Host Link, No-protocol, 1:1 Slave Unit link, 1:1 Master Unit link, or 1:1 NT Link connections.
Functions provided by
Expansion Modules
Analog I/O Module: Provides 2 analog inputs and 1 analog output.
CompoBus/S I/O Link Module: Provides 8 inputs and 8 outputs as a CompoBus/S Slave.
Temperature Sensor Modules: Provide 2 or 4 thermocouple inputs, or 2 or 4 temperature-resistance
thermometer inputs.
A--52 Micro Programmable Controller CPM2A
JI/O ALLOCATION
Input bits IR 00000 to IR 00915 (Words not used for input bits can be used for work bits.)
Output bits IR 01000 to IR 01915 (Words not used for output bits can be used for work bits.)
Work bits 928 bits: IR 02000 to IR 04915 (Words IR 020 to IR 049) and IR 20000 to IR 22715 (Words IR 200 to
IR 227)
Special bits (SR area) 448 bits: SR 22800 to SR 25515 (Words IR 228 to IR 255)
Temporary bits (TR area) 8bits(TR0toTR7)
Holding bits (HR area) 320 bits: HR 0000 to HR 1915 (Words HR 00 to HR 19)
Auxiliary bits (AR area) 384 bits: AR 0000 to AR 2315 (Words AR 00 to AR 23)
Link bits (LR area) 256 bits: LR 0000 to LR 1515 (Words LR 00 to LR 15)
Timers/Counters 256 timers/counters (TIM/CNT 000 to TIM/CNT 255)
1-ms timers: TMHH(----)
10-ms timers: TIMH(15)
100-ms timers: TIM
1-s/10-s timers: TIML(----)
Decrementing counters: CNT
Reversible counters: CNTR(12)
Data memory Read/Write: 2,048 words (DM 0000 to DM 2047)
Error Log is contained in DM 2000 to DM 2021
Read-only: 456 words (DM 6144 to DM 6599)
PC Setup: 56 words (DM 6600 to DM 6655)
Basic in-
terrupts
Interrupt
processing
External interrupts: 4
(Shared by the external interrupt inputs (counter mode) and the quick-response inputs.)
e
u
p
s
Interval timer
interrupts
1 (Scheduled Interrupt Mode or Single Interrupt Mode)
High-
speed
c
o
u
n
t
e
r
High-speed
counter
One high-speed counter: 20 kHz single-phase or 5 kHz two-phase (linear count method)
Counter interrupt: 1 (set value comparison or set-value range comparison)
c
o
u
n
t
e
r
Interrupt inputs
(counter mode)
Four inputs (Shared with external interrupt inputs (counter mode) and quick-response inputs.)
Counter interrupts: 4 (Shared by the external interrupt inputs and quick-response inputs.)
Pulse output Two points with no acceleration/deceleration, 10 to 10 kHz each, and no direction control.
One point with waveform acceleration/deceleration, 10 to 10 kHz, and direction control.
Two points with variable duty-ratio outputs using PWM(----).
(Pulse outputs can be used with transistor outputs only, they cannot be used with relay outputs.)
Synchronized pulse control One point:
A pulse output can be created by combining the high-speed counter with the pulse output and multiply-
ing the frequency of the input pulses from the high-speed counter by a fixed factor.
(This output is possible with transistor outputs only, it cannot be used with relay outputs.)
Quick-response inputs Four points (Min. input pulse width: 50 µsmin.)
Analog controls 2 controls, setting range: 0 to 200
Input time constant Can be set for all input points.
(1 ms, 2 ms, 3 ms, 5 ms, 10 ms, 20 ms, 40 ms, or 80 ms; default setting: 10 ms)
Clock function Shows the year, month, day of the week, day, hour, minute, and second. (Battery backup)
A--53
Micro Programmable Controller CPM2A
JI/O SPECIFICATIONS
CPU Input
Item Inputs Specification
Input voltage All 24 VDC +10%/--15%
Input impedance IN00000 to IN00001 2.7 k
p
p
IN00002 to IN00006 3.9 k
IN00007 and up 4.7 k
Input current IN00000 to IN00001 8mAtypical
p
IN00002 to IN00006 6mAtypical
IN00007 and up 5mAtypical
ON voltage/current IN00000 to IN00001 17 VDC min., 5 mA
g
/
IN00002 and up 14.4 VDC min., 3 mA
OFF voltage/current All 5.0 VDC max., 1 mA
ON delay All 1 to 80 ms max. Default: 10 ms (See Note.)
OFF delay All 1 to 80 ms max. Default: 10 ms (See Note.)
Circuit configuration IN00000 to IN00001
2.7 k
Input
LED
Internal
Circuits
680
10,000 pF
IN00002 to IN00006
3.9 k
Input
LED
Internal
Circuits
750
IN00007 and up
4.7 k
Input
LED
Internal
Circuits
750
Note: The input time constant can be set to 1, 2, 3, 5, 10, 20, 40, or 80 ms in the PLC Setup.
High-speed Counter Inputs
Inputs IN00000 through IN00002 can be used as high-speed counter inputs, as shown in the following table. The maximum count fre-
quency is 5 kHz in differential phase mode and 20 kHz in the other modes.
Input Function
p
Differential phase mode Pulse + direction input mode Up/down input mode Increment mode
IN00000 A-phase pulse input Pulse input Increment pulse input Increment pulse input
IN00001 B-phase pulse input Direction input Decrement pulse input Normal input
IN00002 Z-phase pulse input/Hardware reset input (IN00002 can be used as a normal input when it is not used as a high-speed
counter input.)
Interrupt Inputs
Inputs IN00003 through IN00006 can be used as interrupt inputs (interrupt input mode or counter mode) and quick-response inputs. The
minimum pulse width for these inputs is 0.05 ms.
A--54 Micro Programmable Controller CPM2A
Expansion I/O Module Input
Item Specification
Input voltage 24 VDC +10%/--15%
Input impedance 4.7 k
Input current 5mAtypical
ON voltage 14.4 VDC min.
OFF voltage 5.0 VDC max.
ON delay 1 to 80 ms max. Default: 10 ms (See note.)
OFF delay 1 to 80 ms max. Default: 10 ms (See note.)
Circuit configuration
4.7 k
Input
LED
Internal
Circuits
750
Note: The input time constant can be set to 1, 2, 3, 5, 10, 20, 40, or 80 ms in the PLC Setup.
JOUTPUT SPECIFICATIONS (CPU AND EXPANSION I/O MODULE)
Relay Output
Item Specification
Max. switching capacity 2 A, 250 VAC (cosφ=1)
2A,24VDC
(4 A/common)
Min. switching capacity 10 mA, 5 VDC
Service life of relay Electrical: 150,000 operations (30 VDC resistive load)
100,000 operations (240 VAC inductive load, cosφ=4)
Mechanical: 20,000,000 operations
ON delay 15 ms max.
OFF delay 15 ms max.
Circuit configuration
OUT
OUT
Maximum
250 VAC: 2 A
24 VDC: 2 A
COM
Output
LED
Internal
Circuits
A--55
Micro Programmable Controller CPM2A
Transistor Output (Sinking)
Item Specification
20CDT-D 30CDT-D 40CDT-D 60CDT-D 8ET 20EDT1
Max. switching capacity OUT01000, 01001: 4.5 to 30 VDC, 0.2 A/output
OUT01002 and up: 4.5 to 30 VDC, 0.3 A/output
24 VDC+10%/--5%,
0.3 A/output
0.8 A/common
1.6 A/Unit
0.8 A/common
2.4 A/Unit
0.8 A/common
3.2 A/Unit
0.8 A/common
4.8 A/Unit
0.9 A/common
1.8 A/Unit
0.9 A/common
1.8 A/Unit
Leakage current 0.1 mA max.
Residual voltage 1.5 V max.
ON delay OUT01000 and OUT01001: 20 µsmax.
OUT01002 and up: 0.1 ms max.
0.1 ms max.
OFF delay OUT01000 and OUT01001: 40 µs max. (4.5 to 26.5 V, 10 to 100 mA)
0.1 ms max. (4.5 to 30 V, 10 to 300 mA)
OUT01002 and up: 1 ms max. (4.5 to 30 V, 10 to 300 mA)
1msmax.
24 VDC
+10%/--5%,
5to300mA)
Fuse (See Note) 1 fuse/output 1 fuse/common
Circuit configuration
OUT
OUT
COM (--)
Output
LED
Internal
Circuits 24 VDC
Note: Cannot be replaced by the user.
Transistor Output (Sourcing)
Item Specification
20CDT1-D 30CDT1-D 40CDT1-D 60CDT1-D 8ET1 20EDT1
Max. switching capacity OUT01000, 01001: 4.5 to 30 VDC, 0.2 A/output
OUT01002 and up: 4.5 to 30 VDC, 0.3 A/output
24 VDC+10%/--5%,
0.3 A/output
0.8 A/common
1.6 A/Unit
0.8 A/common
2.4 A/Unit
0.8 A/common
3.2 A/Unit
0.8 A/common
4.8 A/Unit
0.9 A/common
1.8 A/Unit
0.9 A/common
1.8 A/Unit
Leakage current 0.1 mA max.
Residual voltage 1.5 V max.
ON delay OUT01000 and OUT01001: 20 µsmax.
OUT01002 and up: 0.1 ms max.
0.1 ms max.
OFF delay OUT01000 and OUT01001: 40 µs max. (4.5 to 26.5 V, 10 to 100 mA)
0.1 ms max. (4.5 to 30 V, 10 to 300 mA)
OUT01002 and up: 1 ms max. (4.5 to 30 V, 10 to 300 mA)
1msmax.
24 VDC+10%/--5%,
5 to 300 mA)
Fuse (See Note) 1 fuse/output 1 fuse/common
Circuit configuration
OUT
COM (+)
Output
LED
Internal
Circuits 24 VDC
OUT
Note: Cannot be replaced by the user.
A--56 Micro Programmable Controller CPM2A
JANALOG I/O MODULE
Up to 3 Expansion I/O Modules or Expansion Modules (including
the CPM1A-MAD01 Analog I/O Module) can be connected to a
CPM2A CPU.
CPM1A--MAD01 CPM1A--MAD11
Item CPM1A-MAD01 CPM1A-MAD11
Voltage I/O Current I/O Voltage I/O Current I/O
Analog
i
t
Number of inputs 22 (allocated 2 words)
g
inputs Input signal ranges 0to10Vor1to5V 4to20mA 0to5V,1to5V,0to
10 V, --10 to 10 V
0to20mA,4to20mA
Maximum rated input ±15 V ±30 mA ±15 V ±30 mA
External input
impedance
1Mmin. 250 rated 1Mmin. 250
Resolution 1/256 1/6,000 (full scale)
Overall precision 1.0% of full scale 25_C: ±0.3% of full
scale
25_C: ±0.4% of full
scale
0to55
_C: ±0.6% of full
scale
0to55
_C: ±0.8% of full
scale
Converted A/D data 8-bit binary Binary data (4-digit hexadecimal)
--10 to 10 V: F448 to 0BB8 Hex full scale
Other: 0000 to 1770 Hex full scale
Analog
t
t
Averaging Supported (set for each input with DIP switch)
g
output
(See
N
o
t
e
1
)
Disconnected line
detection
Supported
N
o
t
e
1
.
)
Number of outputs 11 (allocated 1 word)
Output signal ranges 0to10Vor--10to
10 V
4to20mA 1to5V,0to10V,--10to
10 V
0to20mA,4to20mA
External output max.
current
5mA
External output
allowed load
resistance
350 1kmin. 600 max.
External output
impedance
0.5 max.
Resolution 1/256 (1/512 when the output signal range
is --10 to 10 V.)
1/6,000 (full scale)
Overall precision 1.0% of full scale 25_C: ±0.4% of full scale
p
0to55
_C: ±0.8% of full scale
Data setting 8-bit binary with sign bit
D/A data setting Binary data (4-digit hexadecimal)
--10 to 10 V: F448 to 0BB8 Hex full scale
Other: 0000 to 1770 Hex full scale
Conversion time (See Note 2.) 10 ms/Unit max. 2 ms/point (6 ms/all analog I/O)
Isolation method Photocoupler isolation between I/O termi-
nals and PC
(There is no isolation between the analog
I/O signals.)
Photocoupler isolation between analog I/O and inter-
nal circuits. (Individual analog I/O signals are not iso-
lated.)
Note: 1. The voltage output and current output can be used at the same time, but the total output current cannot exceed 21 mA.
2. The conversion time is the total time for 2 analog inputs and 1 analog output.
A--57
Micro Programmable Controller CPM2A
JTEMPERATURE SENSOR MODULES
By connecting a Temperature Sensor Module
(CPM1A-TS001/TS002/TS101/TS101A/TS102) to the CPM2A,
inputs can be received from thermocouples or temperature-
resistance thermometers. Inputs converted to binary data (4-digit
hexadecimal) and stored in the IR area.
Specifications
Item Specification
Model CPM1A-TS001/TS002 CPM1A-TS101/TS102 CPM1A-TS101-DA
Number of inputs TS001: 2; TS002: 4 TS101: 2; TS102: 4 2
Input types
(See Note 1)
Thermocouple types K or J, selectable Platinum resistance thermometer types Pt100 and JPt1100, selectable
Input resolution 0.1°C in 2’s complement format 0.1°C in 2’s complement format
Input accuracy ±0.5% or ±2% of the stored value
whichever is larger ±1 digit max.
(See Note 2)
±0.5% or ±1% of the stored value
whichever is larger ±1 digit max.
(See Note 2)
1.0% max. full scale
Number of outputs None None 1
Output types Voltage or current output
Output resolution 1/256 (0 to 10 V)
1/512 (--10 to +10 V)
1/256 (4 to 20 mA)
Output accuracy 1.0% max. full scale
Conversion cycle 250 ms for all points 60 ms max. for all points
Converted
temperature data
Binary data (4-digit hexadecimal) Binary data (8-digit hexadecimal)
Isolation method Photocoupler isolation between I/O terminals and the PLC
Note: 1. The same input type must be used for all inputs.
2. Accuracy for K thermocouples at temperatures less than --100°C: ±4°C±1 digit max.
Input Temperature Ranges
The input type is selected with a rotary switch. The ranges for each of the input types are shown in the following table.
Model CPM1A-TS001/TS002 CPM1A-TS101/TS101-DA/TS102
Input type Thermocouple type K Thermocouple type J Platinum RTD Pt100 Platinum RTD JPt100
Range in °C--200 to 1,300, 0.0 to 500.0 --100 to 850, 0.0 to 400.0 --200.0 to 650.0 --200.0 to 650.0
Range in °F--300 to 2300, 0.0 to 900.0 --100 to 1500, 0.0 to 750.0 --300.0 to 1200.0 --300.0 to 1200.0
A--58 Micro Programmable Controller CPM2A
JCOMPOBUS/S I/O LINK MODULE
The CPM2A PLC can function as a Slave to a CompoBus/S Master Module (or SRM1 CompoBus/S Master Controller) when a CPM1A-
SRT21 CompoBus/S I/O Link Module is connected. The CompoBus/S I/O Link Module establishes an I/O link of 8 inputs and 8 outputs
between the Master Module and the CPM2A. Up to 3 Expansion I/O Modules or Expansion Modules can be connected to a CPM2A CPU.
CS1j, C200Hj,
CQM1 (H), or SRM1 PC
Up to 16 Slaves can be connected.
(Up to 8 Slaves with the CQM1-SRM21-V1.)
CompoBus/S Master Module
(or SRM1 CompoBus/S
Master Controller)
CPM2A CPU
C
P
M
1
A
-
S
R
T
2
1
CompoBus/S I/O
Link Module
SCA1-4F10 flat cable or twisted pair Belden #9409 cable
Specifications
Item Specification
Model number CPM1A-SRT21
Master/Slave CompoBus/S Slave
Number of I/O bits 8 input bits, 8 output bits
Number of words occupied in
CPM2A I/O memory
1 input word, 1 output word
(Allocated in the same way as other Expansion I/O Units or Expansion Units)
Node number setting Set using the DIP switch.
Note: See the CompoBus/S section of Omron’s Remote I/O and Wiring Solutions Catalog (GC RIO1)for more details on CompoBus/S
communications.
JCPM1A-DRT21 DEVICENET I/O LINK MODULE
The CPM1A-DRT21 DeviceNet I/O Link Module can be connected to the CPM2A to function as a slave under a DeviceNet Master Mod-
ule. This enables an I/O Link with the Master Module via 32 input and 32 output points.
DeviceNet Master Module
CPM2A CPU Module CPM1A--DRT21 DeviceNet I/O Link Module
Connect up to 63 nodes
(with an CS1 Master Module)
CS1j, C200Hj,CJ1j,
CV-series or CVM1
PLC
A--59
Micro Programmable Controller CPM2A
Specifications
Item Specification
Model number CPM1A-DRT21
Master/slave DeviceNet slave
I/O capacity to master 32 input and 32 output points
I/O memory allocated in CPM2A 2 input words and 2 output words (same as other Expansion Units)
Node address setting DIP switch (Set before turning ON power for the CPU Unit.)
Maximum number of nodes (depending on the PC to which
Master Unit is mounted)
CS1: 63 nodes
CJ1: 63 nodes
CVM1/CV 32nodes
C200HX/HG/HE: 25 nodes
C200HS 16 nodes
JPROFIBUS-DP SLAVE MODULE
The CPM2A controller can function as a Slave to a Profibus-DP Master Module when a CPM1A-PRT21 Profibus-DP Slave Module is
connected. The Profibus-DP Slave Module establishes an I/O link of 16 inputs and 16 outputs between the master and the controller. A
maximum of 3 Profibus-DP Slave Modules can be connected to a CPM1A or CPM2A to create I/O links for up to 96 points (48 inputs and
48 outputs).
Profibus-DP Master Module
PLC supporting Profibus-DP Master,
e.g., CSI, C200Hj,CJ1
j
Each module enables
remote I/O communica-
tions for 16 inputs and
16 output points as a
Profibus-DP Slave.
Up to 124 nodes
(using repeaters)
Shielded twisted pair
Belden #3079A cable
PRT21
CPM2A CPU Module
CPM1A-PRT21 Profibus-DP
Slave Module
Specifications
Storage temperature -- 2 0 t o + 7 5 °C
Ambient temperature 0to+55°C
Ambient humidity 10 to 90% (non-condensing)
EMC compliance EN 50081-2, EN 61131-2
Current consumption 100 mA from the PLC I/O bus
Weight 125 g (typical)
Control data From CPU to unit: none
Status data From unit to CPU: none
I/O data (in bytes) 2 bytes input, 2 bytes output
A--60 Micro Programmable Controller CPM2A
JCOMMUNICATIONS ADAPTER
RS-232C Adapter and RS-422 Adapter CPM1--CIF01 CPM1--CIF11
Part number CPM1-CIF01 CPM1-CIF11
Functions Level conversion between the CMOS level
(CPU side) and the RS-232C (peripheral
device side)
Level conversion between the CMOS level
(CPU side) and the RS-422 (peripheral device
side)
Insulation The RS-232C (peripheral device side) is insu-
lated by a DC/DC converter and photocoupler.
The RS-422 (peripheral device side) is insu-
lated by a DC/DC converter and photocoupler.
Power supply Power is supplied by the CPU.
Power consumption 0.3 A max.
Transmission speed 38.4 kbits/s max.
Vibration resistance 10 to 57 Hz with an amplitude of 0.075 mm, and 57 to 150 Hz with an acceleration of 1 G in the X,
Y and Z directions for 80 minutes each (i.e. for 8 minutes each, 10 times).
Shock resistance 1.5 G in the X, Y and Z directions 3 times each.
Ambient temperature Operating 0°Cto55°C(32°F to 131°F) 0°Cto55°C(32°F to 131°F)
p
Storage -- 2 0 °Cto75°C(--4°F to 167°F) -- 2 0 °Cto75°C(--4°F to 167°F)
Ambient humidity Operating 10% to 90% RH (with no condensation)
Ambient environment Operating With no corrosive gas
Weight 200 g max.
A--61
Micro Programmable Controller CPM2A
D
i
m
e
n
s
i
o
n
s
Unit: mm (inch)
JCPU
C
P
M
2
A
-
2
0
C
D
j
-
j
/
3
0
C
D
j
-
jCPUs with DC Power CPUs with AC Power
CPM2A-40CDj-j
CPUs with DC Power CPUs with AC Power
CPM2A-60CDj-j
CPUs with DC Power CPUs with AC Power
90
(3.54)
90
(3.54)
90
(3.54)
130 (5.12) 55 (2.17) 90 (3.54)
55 (2.17) 90 (3.54)
55 (2.17) 90 (3.54)
195 (7.68)
150 (5.91)
A--62 Micro Programmable Controller CPM2A
JEXPANSION I/O AND SPECIAL I/O MODULES
C
P
M
1
A
-
2
0
E
D
j
E
x
p
a
n
s
i
o
n
I
/
O
M
o
d
u
l
e
s
C
P
M
1
A
-
8
jjj
E
x
p
a
n
s
i
o
n
I
/
O
M
o
d
u
l
e
s
CPM1A-MAD01 Analog I/O Module CPM1A-MAD11 Analog I/O Module
90
(3.54)
50 (1.97)
86 (3.39)
90
(3.54)
50 (1.97)
66 (2.60)
50 (1.97)
66 (2.60)
90
(3.54)
86
76 ±0.2
Two, 4.5 dia.
5
50
8
5
100
±0.2
90
CPM1A-TSjjj Temperature Sensor Input Modules
86 (3.39) 50 (1.97)
43 (1.69)
73 (2.99)
Two, 10
dia. hole
90
(3.54)
A--63
Micro Programmable Controller CPM2A
Unit: mm (inch)
CPM1A-SRT21 CompoBus/S I/O Link Module
50 (1.97)
66 (2.60)
90
(3.54)
CPM1A-DRT21 DeviceNet I/O Link Module
CPM1A-PRT21 Profibus-DP Slave Module
JCOMMUNICATION ADAPTER MODULES
30 (1.18)
21 21
90
(3.54)
81
50
56 (2.20)
81
50
61 (2.40)
CPM1-CIF01 CPM1-CIF11
30 (1.18)
90
(3.54)
A--64 Micro Programmable Controller CPM2A
F
u
n
c
t
i
o
n
s
JCONFIGURATION
The CPM2A PLCs incorporate a variety of features, including
synchronized pulse control, interrupt inputs, pulse outputs,
analog settings, and a clock function. Use the CPM2A CPU as a
stand-alone controller for a broad range of machine control
applications.
The CPM2A easily communicates with personal computers, other
OMRON PLCs, and OMRON Programmable Terminals. These
communications capabilities allow the user to design a low-cost
distributed production system.
The CPU contains 20, 30, 40, or 60 I/O points and Expansion I/O
blocks can be added to provide a total I/O capacity of up to 120 I/O
points. Analog I/O modules, Temperature Sensor modules, and
CompoBus/S I/O Link modules can also be connected.
Peripheral Port
Use this port for programming devices (compa-
tible with other OMRON PLCs) as well as Host
Link and no-protocol communications.
RS-232C Port
This port can be used for a Host
Link, no-protocol, 1:1 data link, or
1:1 NT Link communications.
JTIME-PROPORTIONAL CONTROL
The CPM2A performs simple-to-program, time-proportional
control using up to three Analog I/O modules (maximum 6 analog
inputs and 3 analog outputs) and the PID and PWM expansion
instructions. These instructions set the parameters for PID
control and a pulse output with variable duty ratio. For increased
reliability, an open-circuit detection function can be used with the
1 to 5 VDC and 4 to 20 mA analog input settings.
For temperature monitoring applications, CPM2A accepts up to 6
inputs (two per module) from Temperature Sensor Input modules.
The PID instruction can manipulate the input from either
thermocouple or platinum resistance thermometer sensors.
JDISTRIBUTED I/O CONTROL
Omron’s CompoBus/S Network provides distributed CPU control
based on a “PLC + compact PLC” configuration which provides
improvements over distributed control based on “PLC + remote
I/O” configurations. The distributed CPU control makes
equipment module, so designs can be standardized, special
needs can be addressed and modules can be replaced easily in
the event of breakdown without affecting the main CPU.
Master
PLC
CompoBus/S Master Module
CPM2A
(Slave)
CompoBus/S I/O
Link Module
CompoBus/S
Distributed
CPU control
JBUILT-IN MOTOR CONTROL CAPABILITY
Synchronized Pulse Control (transistor output models only)
Synchronized output pulse control provides an easy way to
coordinate the operation of a peripheral piece of equipment with
the main equipment. The output pulse frequency can be
controlled as a multiple of the input pulse frequency, allowing the
speed of a peripheral piece of equipment (such as a supply
conveyor) to be synchronized with the speed of the main piece of
equipment.
Encoder CPM2A Motor
Pulses are output as a fixed multiple of the input frequency.
3G3MV Drive
A--65
Micro Programmable Controller CPM2A
JHIGH-SPEED COUNTERS AND INTERRUPTS
The CPM2A has a total of five high-speed counter inputs. The
one high-speed counter input has a response frequency of
20 kHz/5 kHz, and the four interrupt inputs (in counter mode)
have a response frequency of 2 kHz.
Four Input Modes
The high-speed counter can be used in any one of the four input
modes: differential phase mode (5 kHz), pulse plus direction input
mode (20 kHz), up/down pulse mode (20 kHz), or increment
mode (20 kHz). Interrupts can be triggered when the count
matches a set value or falls within a specified range.
Interrupt Inputs
The interrupt inputs (counter mode) can be used for incrementing
counters or decrementing counters (2 kHz) and trigger an
interrupt (executing the interrupt program) when the count
matches the target value. Use this for target-value comparison or
range comparison control that is unaffected by the cycle time.
Easy Position Control with Pulse Outputs
(transistor output models only)
The CPM2A PLCs with transistor outputs have two outputs that
can produce 10 Hz to 10 kHz pulses (single-phase outputs).
When used as single-phase pulse outputs, there can be two
outputs with a frequency range of 10 Hz to 10 kHz with a fixed
duty ratio or 0.1 to 999.9 Hz with a variable duty ratio (0 to 100%
duty ratio).
When used as pulse plus direction or up/down pulse outputs,
there can be just one output with a frequency range of 10 Hz to
10 kHz.
Counter inputs
Reset inputs (for differential phase inputs)
Sensor Rotary encoder
(such as E6C2-C)
Input Response frequency Input mode (count value) Control method
00000
0
0
0
0
1
5kHz Differential phase input mode (-8,388,608 to 8,388,607) Target value comparison interrupts
R
i
i
t
t
00001
00002 20 kHz Pulse + direction input mode (-8,388,608 to 8,388,607)
Up/down pulse input mode (-8,388,608 to 8,388,607)
Increment mode (0 to 16,777,215)
g
p
p
Range comparison interrupts
A--66 Micro Programmable Controller CPM2A
JPULSE OUTPUTS
The CPM2A has two pulse outputs. You can configure these outputs as two single-phase outputs without acceleration and deceleration,
two variable duty-ratio pulse outputs, or pulse outputs with trapezoidal acceleration/deceleration (one pulse + direction output and one
up/down pulse output). The pulse output’s PV coordinate system can also be specified in the PLC Setup as either relative or absolute.
Stepping motor
Pulse outputs
SmartStep Servodriver
Item Single-phase pulse
output without
l
i
/
d
l
i
Variable duty-ratio
pulse output
Single-phase pulse output with trapezoidal
acceleration/deceleration
o
u
t
p
u
t
t
o
u
t
acceleration/deceleration
p
u
s
e
o
u
t
p
u
t
Pulse + direction output Up/down pulse output
Controlling instruction(s) PULS(65) and SPED(64) P W M ( -- -- ) PULS(65) and ACC(----)
Output
number
01000 Pulse output 0
(See Note.)
Pulse output 0
(See Note.)
Pulse
output 0
Pulse output Pulse
output 0
CW pulse
output
u
b
e
01001 Pulse output 1
(See Note.)
Pulse output 1
(See Note.)
o
u
p
u
0
Direction output
o
u
p
u
0
CCW pulse
output
Output frequency range 10 Hz to 10 kHz 0.1 Hz to 999.9 Hz 10 Hz to 10 kHz 10 Hz to 10 kHz
Pitch 10 Hz 0.1 Hz 10 Hz 10 Hz
Duty ratio 50% 0 to 100% 50% 50%
Note: With single-phase pulse outputs, pulse outputs 0 and 1 can each be output independently.
Application Example: Adjusting Film/Paper Web Speed in Packaging and Printing
CPM2A PLC
Main Motor
Encoder
SYSDRIVE Inverter
W-Series Servo Motor/Servo Drive
A--67
Micro Programmable Controller CPM2A
JHIGH-SPEED INPUT CAPABILITIES FOR
MACHINE CONTROL
High-speed Interrupt Input Function
There are four inputs used for interrupt inputs (shared with quick-
response inputs and interrupt inputs in counter mode) with a
minimum input signal width of 50 µs and a response time of
0.3 ms. When an interrupt input goes ON, the main program is
stopped and the interrupt program is executed.
Quick-response Input Function
There are four inputs used for quick-response inputs (shared with
interrupt inputs and interrupt inputs in counter mode) that can
reliably read input signals with a signal width as short as 50 µs.
Quick-response inputs are received into an internal buffer, so
signals that change status within a cycle can be processed.
Stabilizing Input Filter Function
The input time constant for all inputs can be set to 1 ms, 2 ms,
3ms,5ms,10ms,20ms,40ms,or80ms.Theeffectsof
chattering and external noise can be reduced by increasing the
input time constant.
Interval Timer Interrupts
The interval timer offers a 0.5 and 319,968 ms range and can be
set to generate just one interrupt (one-shot mode) or periodic
interrupts (scheduled interrupt mode) to match the application.
JOTHER FUNCTIONS
Analog Settings
There are two controls on the CPU that can be turned to change
the analog settings (0 to 200 BCD) of timers and counters. These
controls can be used to easily change or fine-tune machine
settings such as a conveyor belt’s pause time or feed rate.
Calendar/Clock
The built-in clock (accuracy within 1 minute/month) can be read
from the program to show the current year, month, day, day of the
week, and time. The clock can be set from a programming device
(such as a Programming Console) or the time can be adjusted by
rounding up or down to the nearest minute.
Long-term Timer
The long-term timer provides an easy way to control equipment
scheduling. Use two instructions to set this up. The long-term
timer instruction (TIML) lets you set values up to 99,990 seconds
(27 hours, 46 minutes, 30 seconds) and the Seconds-to-Hours
conversion instruction (HMS) lets you schedule this with other
clock functions.
C
o
m
m
u
n
i
c
a
t
i
o
n
s
JNT LINK FOR PROGRAMMABLE TERMINALS
The CPM2A can be connected directly to an OMRON NT-Series Programmable Terminal in NT Link mode (1:1) for high-speed transmis-
sion of data. No separate drivers are required Use the RS-232C port for the NT Link connection.
Serial Port
Peripheral
Port
Operator Interface
Terminal
CBL-804*
CBL-803*
C200H-CN_0-EU,
NT31C-CN_0-EU,
(for NT31C Port B only)
* Available in Canada only.
A--68 Micro Programmable Controller CPM2A
JHOST LINK
A Host Link connection can be made through the CPM2A’s RS-232C port or Peripheral port. A personal computer or Programmable Ter-
minal connected in Host Link mode can be used for operations such as reading/writing data in the CPM2A’s I/O memory or reading/chan-
ging the controller’s operating mode.
1:1 Host Link Communications
CPM1-CIF01*
CPM2A using
direct RS-232C
port connection.
*Optional communications adapter
converts the Peripheral port to
RS-232C.
1:N Host Link Communications
CPM2A
(RS-232C port connection)
*Optional communications adapter converts the
Peripheral Port to RS-422/RS-485. (Up to 32
CPM2As can be connected.)
Commands
Responses
Commands
Responses
Computer with
RS-422/RS-485
Peripheral port connection*
CPM1-CIF11*
No-Protocol Communications
The transmit TXD (48) and receive RXD (47) instructions can be used in No-Protocol mode to exchange data with standard serial de-
vices. For example, data can be received from a bar code reader or transmitted to a serial modem. The serial devices can be connected
directly to the RS-232C port or the Peripheral port using the CPM1-CIF01 serial communications adapter.
CPM2A
(
R
S
-
2
3
2
C
p
o
r
t
c
o
n
n
e
c
t
i
o
n
*
)
I
n
p
u
t
t
i
n
g
d
a
t
a
f
r
o
m
a
b
a
r
code reader
Bar code reader
CPM2A
(
R
S
-
2
3
2
C
p
o
r
t
c
o
n
n
e
c
t
i
o
n
*
)
O
u
t
p
u
t
t
i
n
g
d
a
t
a
t
o
a
serial modem
Serial modem
*An RS-232C Adapter is needed
to connect to the Peripheral port.
J1:1 DATA LINKS
A CPM2A can be linked directly to another CPM2A, CQM1H, CPM1, CPM1A, CPM2C, SRM1(-V2), or a C200HS or C200HX/HG/HE
programmable controller. The 1:1 PLC Link allows automatic data link connections or sharing of memory between two Omron CPUs. The
controller must be connected through the RS-232C port; it cannot be connected through the Peripheral port.
Example of a 1:1 Link between CPM2As
Link bits
WRITE area
READ area
LR 00
LR 07
LR 08
LR 15
WRITE
READ
READ area
WRITE area
LR 00
LR 07
LR 08
LR 15
READ
WRITE
Link bits
M
a
s
t
e
r
S
l
a
v
e
CPM2A
(RS-232C port
connection)
CPM2A
(RS-232C port
connection)
A--69
Micro Programmable Controller CPM2A
JPROGRAM TRANSFER UNIT
Use Omron’s EEPROM program transfer unit to update programs in machines or program multiple controllers with the same program.
The CPM1-EMU01-V1 Expansion Memory Unit connects to the peripheral port of micro and small PLCs.
Uploading
Downloading
EEPROM
Omron SRM1, CPM1A, CPM2A,
CPM2B, CPM2C and CQM1H
programmable controllers
&HUWDLQ7HUPVDQG&RQGLWLRQVRI6DOH
 2IIHU$FFHSWDQFH7KHVHWHUPVDQGFRQGLWLRQVWKHVH7HUPVDUHGHHPHG
SDUWRIDOOFDWDORJVPDQXDOVRURWKHUGRFXPHQWVZKHWKHUHOHFWURQLFRULQZULW
LQJ UHODWLQJ WR WKH VDOH RI JRRGV RU VHUYLFHV FROOHFWLYHO\ WKH *RRGV E\
2PURQ(OHFWURQLFV//&DQGLWVVXEVLGLDU\FRPSDQLHV6HOOHU6HOOHUKHUHE\
REMHFWVWRDQ\WHUPVRUFRQGLWLRQVSURSRVHGLQ%X\HUVSXUFKDVHRUGHURURWKHU
GRFXPHQWVZKLFKDUHLQFRQVLVWHQWZLWKRULQDGGLWLRQWRWKHVH7HUPV3OHDVH
FRQWDFW\RXU 2PURQ UHSUHVHQWDWLYHWRFRQILUPDQ\DGGLWLRQDOWHUPVIRU VDOHV
IURP\RXU2PURQFRPSDQ\
 3ULFHV $OO SULFHV VWDWHG DUH FXUUHQW VXEMHFW WR FKDQJH ZLWKRXW QRWLFH E\
6HOOHU%X\HUDJUHHVWRSD\WKHSULFHLQHIIHFWDWWLPHRIVKLSPHQW
 'LVFRXQWV &DVK GLVFRXQWV LI DQ\ ZLOO DSSO\ RQO\ RQ WKH QHW DPRXQW RI
LQYRLFHV VHQW WR %X\HU DIWHU GHGXFWLQJ WUDQVSRUWDWLRQ FKDUJHV WD[HV DQG
GXWLHVDQGZLOOEHDOORZHGRQO\LILWKHLQYRLFHLVSDLGDFFRUGLQJWR6HOOHUV
SD\PHQWWHUPVDQGLL%X\HUKDVQRSDVWGXHDPRXQWVRZLQJWR6HOOHU
 2UGHUV6HOOHUZLOODFFHSWQRRUGHUOHVVWKDQQHWELOOLQJ
 *RYHUQPHQWDO $SSURYDOV %X\HU VKDOO EH UHVSRQVLEOH IRU DQG VKDOO EHDU DOO
FRVWVLQYROYHGLQREWDLQLQJDQ\JRYHUQPHQWDSSURYDOVUHTXLUHGIRUWKHLPSRU
WDWLRQRUVDOHRIWKH*RRGV
 7D[HV $OOWD[HVGXWLHVDQGRWKHUJRYHUQPHQWDOFKDUJHVRWKHUWKDQJHQHUDO
UHDOSURSHUW\ DQG LQFRPH WD[HVLQFOXGLQJDQ\ LQWHUHVW RUSHQDOWLHVWKHUHRQ
LPSRVHGGLUHFWO\RULQGLUHFWO\RQ6HOOHURUUHTXLUHGWREHFROOHFWHGGLUHFWO\RU
LQGLUHFWO\E\6HOOHUIRUWKHPDQXIDFWXUHSURGXFWLRQVDOHGHOLYHU\LPSRUWDWLRQ
FRQVXPSWLRQ RU XVH RI WKH *RRGV VROG KHUHXQGHU LQFOXGLQJ FXVWRPV GXWLHV
DQGVDOHVH[FLVHXVHWXUQRYHUDQGOLFHQVH WD[HV VKDOOEHFKDUJHG WR DQG
UHPLWWHGE\%X\HUWR6HOOHU
 )LQDQFLDO,IWKHILQDQFLDOSRVLWLRQRI%X\HUDWDQ\WLPHEHFRPHVXQVDWLVIDFWRU\
WR 6HOOHU 6HOOHU UHVHUYHV WKH ULJKW WR VWRS VKLSPHQWV RU UHTXLUH VDWLVIDFWRU\
VHFXULW\RUSD\PHQWLQDGYDQFH,I%X\HUIDLOVWRPDNHSD\PHQWRURWKHUZLVH
FRPSO\ZLWKWKHVH7HUPVRUDQ\UHODWHGDJUHHPHQW6HOOHUPD\ZLWKRXWOLDELOLW\
DQGLQDGGLWLRQWRRWKHUUHPHGLHVFDQFHODQ\XQVKLSSHGSRUWLRQRI*RRGVVROG
KHUHXQGHUDQGVWRSDQ\*RRGVLQWUDQVLWXQWLO%X\HUSD\VDOODPRXQWVLQFOXG
LQJDPRXQWVSD\DEOHKHUHXQGHUZKHWKHURUQRWWKHQGXHZKLFKDUHRZLQJWRLW
E\%X\HU%X\HUVKDOOLQDQ\HYHQWUHPDLQOLDEOHIRUDOOXQSDLGDFFRXQWV
 &DQFHOODWLRQ (WF 2UGHUV DUH QRW VXEMHFW WR UHVFKHGXOLQJ RU FDQFHOODWLRQ
XQOHVV%X\HULQGHPQLILHV6HOOHUIXOO\DJDLQVWDOOFRVWVRUH[SHQVHVDULVLQJLQ
FRQQHFWLRQWKHUHZLWK
 )RUFH0DMHXUH 6HOOHU VKDOOQRWEH OLDEOHIRU DQ\GHOD\ RUIDLOXUH LQGHOLYHU\
UHVXOWLQJIURPFDXVHVEH\RQGLWVFRQWUROLQFOXGLQJHDUWKTXDNHVILUHVIORRGV
VWULNHV RU RWKHU ODERU GLVSXWHV VKRUWDJH RI ODERU RU PDWHULDOV DFFLGHQWV WR
PDFKLQHU\ DFWV RI VDERWDJH ULRWV GHOD\ LQ RU ODFN RI WUDQVSRUWDWLRQ RU WKH
UHTXLUHPHQWVRIDQ\JRYHUQPHQWDXWKRULW\
 6KLSSLQJ'HOLYHU\8QOHVVRWKHUZLVHH[SUHVVO\DJUHHGLQZULWLQJE\6HOOHU
D 6KLSPHQWVVKDOOEHE\DFDUULHUVHOHFWHGE\6HOOHU
E 6XFKFDUULHUVKDOODFWDVWKHDJHQWRI%X\HUDQGGHOLYHU\WRVXFKFDUULHU
VKDOOFRQVWLWXWHGHOLYHU\WR%X\HU
F $OOVDOHVDQGVKLSPHQWVRI*RRGVVKDOOEH)2%VKLSSLQJSRLQWXQOHVVRWK
HUZLVHVWDWHGLQZULWLQJE\6HOOHUDWZKLFKSRLQWWLWOHWRDQGDOOULVNRIORVVRI
WKH*RRGVVKDOOSDVVIURP6HOOHUWR%X\HUSURYLGHGWKDW6HOOHUVKDOOUHWDLQD
VHFXULW\LQWHUHVWLQWKH*RRGVXQWLOWKHIXOOSXUFKDVHSULFHLVSDLGE\%X\HU
G 'HOLYHU\DQGVKLSSLQJGDWHVDUHHVWLPDWHVRQO\
H 6HOOHUZLOOSDFNDJH*RRGVDVLWGHHPVSURSHUIRUSURWHFWLRQDJDLQVWQRUPDO
KDQGOLQJDQGH[WUDFKDUJHVDSSO\WRVSHFLDOFRQGLWLRQV
 &ODLPV $Q\ FODLP E\ %X\HU DJDLQVW 6HOOHU IRU VKRUWDJH RU GDPDJH WR WKH
*RRGVRFFXUULQJEHIRUHGHOLYHU\WRWKHFDUULHUPXVWEHSUHVHQWHGLQZULWLQJWR
6HOOHUZLWKLQGD\VRIUHFHLSWRIVKLSPHQWDQGLQFOXGHWKHRULJLQDOWUDQVSRUWD
WLRQELOOVLJQHGE\WKHFDUULHUQRWLQJWKDWWKHFDUULHUUHFHLYHGWKH*RRGVIURP
6HOOHULQWKHFRQGLWLRQFODLPHG
 :DUUDQWLHVD([FOXVLYH:DUUDQW\6HOOHUVH[FOXVLYHZDUUDQW\LVWKDWWKH
*RRGVZLOOEHIUHHIURPGHIHFWVLQPDWHULDOVDQGZRUNPDQVKLSIRUDSHULRGRI
WZHOYHPRQWKVIURPWKHGDWHRIVDOHE\6HOOHURUVXFKRWKHUSHULRGH[SUHVVHG
LQZULWLQJE\6HOOHU6HOOHUGLVFODLPVDOORWKHUZDUUDQWLHVH[SUHVVRULPSOLHG
E/LPLWDWLRQV6(//(50$.(612:$55$17<255(35(6(17$7,21
(;35(66 25 ,03/,(' $%287 121,1)5,1*(0(17 0(5&+$17$%,/
,7<25),71(66)25$3$57,&8/$5385326(2)7+(*22'6
%8<(5$&.12:/('*(67+$7,7$/21(+$6'(7(50,1('7+$77+(
*22'6 :,// 68,7$%/< 0((7 7+( 5(48,5(0(176 2) 7+(,5
,17(1'('86(6HOOHUIXUWKHUGLVFODLPVDOOZDUUDQWLHVDQGUHVSRQVLELOLW\RI
DQ\W\SHIRUFODLPVRUH[SHQVHVEDVHGRQLQIULQJHPHQWE\WKH*RRGVRURWKHU
ZLVHRIDQ\LQWHOOHFWXDOSURSHUW\ULJKWF%X\HU5HPHG\6HOOHUVVROHREOLJD
WLRQKHUHXQGHUVKDOO EH WRUHSODFHLQWKH IRUP RULJLQDOO\VKLSSHGZLWK%X\HU
UHVSRQVLEOH IRU ODERU FKDUJHV IRU UHPRYDO RU UHSODFHPHQW WKHUHRI WKH QRQ
FRPSO\LQJ *RRG RU DW 6HOOHUV HOHFWLRQ WR UHSD\ RU FUHGLW %X\HU DQ DPRXQW
HTXDOWRWKHSXUFKDVHSULFHRIWKH*RRGSURYLGHGWKDWLQQRHYHQWVKDOO6HOOHU
EHUHVSRQVLEOHIRUZDUUDQW\UHSDLULQGHPQLW\RUDQ\RWKHUFODLPVRUH[SHQVHV
UHJDUGLQJ WKH *RRGV XQOHVV 6HOOHUV DQDO\VLV FRQILUPV WKDW WKH *RRGV ZHUH
SURSHUO\KDQGOHGVWRUHGLQVWDOOHGDQGPDLQWDLQHGDQGQRWVXEMHFWWRFRQWDPL
QDWLRQDEXVHPLVXVHRULQDSSURSULDWHPRGLILFDWLRQ5HWXUQRIDQ\JRRGVE\
%X\HUPXVWEHDSSURYHGLQZULWLQJE\6HOOHUEHIRUHVKLSPHQW6HOOHUVKDOOQRW
EHOLDEOHIRUWKHVXLWDELOLW\RUXQVXLWDELOLW\RUWKHUHVXOWVIURPWKHXVHRI*RRGV
LQFRPELQDWLRQZLWK DQ\ HOHFWULFDORUHOHFWURQLFFRPSRQHQWVFLUFXLWVV\VWHP
DVVHPEOLHV RU DQ\ RWKHU PDWHULDOV RU VXEVWDQFHV RU HQYLURQPHQWV $Q\
DGYLFHUHFRPPHQGDWLRQVRULQIRUPDWLRQJLYHQRUDOO\RULQZULWLQJDUHQRWWREH
FRQVWUXHGDVDQDPHQGPHQWRUDGGLWLRQWRWKHDERYHZDUUDQW\
 'DPDJH/LPLWV(WF6(//(56+$//127%(/,$%/()2563(&,$/,1',
5(&7 25 &216(48(17,$/ '$0$*(6 /266 2) 352),76 25 352
'8&7,2125&200(5&,$//266,1$1<:$<&211(&7(':,7+7+(
*22'6:+(7+(568&+&/$,0,6%$6(',1&2175$&7:$55$17<
1(*/,*(1&(25 675,&7 /,$%,/,7< )XUWKHU LQ QR HYHQW VKDOO OLDELOLW\ RI
6HOOHUH[FHHGWKHLQGLYLGXDOSULFHRIWKH*RRGRQZKLFKOLDELOLW\LVDVVHUWHG
 ,QGHPQLWLHV%X\HUVKDOOLQGHPQLI\DQGKROGKDUPOHVV6HOOHULWVDIILOLDWHVDQG
LWV HPSOR\HHV IURP DQG DJDLQVW DOO OLDELOLWLHV ORVVHV FODLPV FRVWV DQG
H[SHQVHVLQFOXGLQJDWWRUQH\VIHHVDQGH[SHQVHVUHODWHGWRDQ\FODLPLQYHV
WLJDWLRQOLWLJDWLRQRUSURFHHGLQJZKHWKHURUQRW6HOOHULVDSDUW\ZKLFKDULVHV
RULVDOOHJHGWRDULVHIURP%X\HUVDFWVRURPLVVLRQVXQGHUWKHVH7HUPVRULQ
DQ\ZD\ZLWKUHVSHFWWRWKH*RRGV:LWKRXWOLPLWLQJWKHIRUHJRLQJ%X\HUDW
LWVRZQH[SHQVHVKDOOLQGHPQLI\DQGKROGKDUPOHVV6HOOHUDQGGHIHQGRUVHWWOH
DQ\DFWLRQEURXJKWDJDLQVW6HOOHUWRWKHH[WHQWWKDWLWLVEDVHGRQDFODLPWKDW
DQ\*RRGPDGHWR%X\HUVSHFLILFDWLRQVLQIULQJHGLQWHOOHFWXDOSURSHUW\ULJKWVRI
DQRWKHUSDUW\
 3URSHUW\&RQILGHQWLDOLW\7KHLQWHOOHFWXDOSURSHUW\HPERGLHGLQWKH*RRGVLV
WKHH[FOXVLYHSURSHUW\RI6HOOHUDQGLWVDIILOLDWHVDQG%X\HUVKDOOQRWDWWHPSWWR
GXSOLFDWHLWLQDQ\ZD\ZLWKRXWWKHZULWWHQSHUPLVVLRQRI6HOOHU1RWZLWKVWDQG
LQJDQ\FKDUJHVWR%X\HUIRUHQJLQHHULQJRUWRROLQJDOOHQJLQHHULQJDQGWRROLQJ
VKDOO UHPDLQ WKH H[FOXVLYH SURSHUW\ RI 6HOOHU $OO LQIRUPDWLRQ DQG PDWHULDOV
VXSSOLHGE\6HOOHUWR%X\HUUHODWLQJWRWKH*RRGVDUHFRQILGHQWLDODQGSURSUL
HWDU\ DQG %X\HU VKDOO OLPLW GLVWULEXWLRQ WKHUHRI WR LWV WUXVWHG HPSOR\HHV DQG
VWULFWO\SUHYHQWGLVFORVXUHWRDQ\WKLUGSDUW\
0LVFHOODQHRXVD:DLYHU1RIDLOXUHRUGHOD\E\6HOOHULQH[HUFLVLQJDQ\ULJKW
DQGQRFRXUVHRIGHDOLQJEHWZHHQ%X\HUDQG6HOOHUVKDOORSHUDWHDVDZDLYHU
RIULJKWVE\6HOOHUE$VVLJQPHQW%X\HUPD\QRWDVVLJQLWVULJKWVKHUHXQGHU
ZLWKRXW6HOOHUVZULWWHQFRQVHQWF$PHQGPHQW7KHVH7HUPVFRQVWLWXWHWKH
HQWLUHDJUHHPHQWEHWZHHQ%X\HUDQG6HOOHUUHODWLQJWRWKH*RRGVDQGQRSUR
YLVLRQPD\EHFKDQJHGRUZDLYHGXQOHVVLQZULWLQJVLJQHGE\WKHSDUWLHV
G6HYHUDELOLW\,IDQ\SURYLVLRQKHUHRILVUHQGHUHGLQHIIHFWLYHRULQYDOLGVXFK
SURYLVLRQVKDOOQRWLQYDOLGDWHDQ\RWKHUSURYLVLRQH6HWRII%X\HUVKDOOKDYH
QR ULJKW WR VHW RII DQ\ DPRXQWV DJDLQVW WKH DPRXQW RZLQJ LQ UHVSHFW RI WKLV
LQYRLFHI$VXVHGKHUHLQLQFOXGLQJPHDQVLQFOXGLQJZLWKRXWOLPLWDWLRQ
&HUWDLQ3UHFDXWLRQVRQ6SHFLILFDWLRQVDQG8VH
 6XLWDELOLW\RI8VH6HOOHUVKDOOQRWEHUHVSRQVLEOHIRUFRQIRUPLW\ZLWKDQ\VWDQ
GDUGVFRGHVRUUHJXODWLRQVZKLFKDSSO\WRWKHFRPELQDWLRQRIWKH*RRGLQWKH
%X\HUVDSSOLFDWLRQRUXVHRIWKH*RRG$W%X\HUVUHTXHVW6HOOHUZLOOSURYLGH
DSSOLFDEOHWKLUGSDUW\FHUWLILFDWLRQGRFXPHQWVLGHQWLI\LQJUDWLQJVDQGOLPLWDWLRQV
RIXVHZKLFKDSSO\WRWKH*RRG7KLVLQIRUPDWLRQE\LWVHOILVQRWVXIILFLHQWIRUD
FRPSOHWHGHWHUPLQDWLRQRIWKHVXLWDELOLW\RIWKH*RRGLQFRPELQDWLRQZLWKWKH
HQGSURGXFWPDFKLQHV\VWHPRURWKHUDSSOLFDWLRQRUXVH7KHIROORZLQJDUH
VRPH H[DPSOHV RI DSSOLFDWLRQV IRU ZKLFK SDUWLFXODU DWWHQWLRQ PXVW EH JLYHQ
7KLVLVQRWLQWHQGHGWREHDQH[KDXVWLYHOLVWRIDOOSRVVLEOHXVHVRIWKLV*RRG
QRULVLWLQWHQGHGWRLPSO\WKDWWKHXVHVOLVWHGPD\EHVXLWDEOHIRUWKLV*RRG
L 2XWGRRUXVHXVHVLQYROYLQJSRWHQWLDOFKHPLFDOFRQWDPLQDWLRQRUHOHFWULFDO
LQWHUIHUHQFHRUFRQGLWLRQVRUXVHVQRWGHVFULEHGLQWKLVGRFXPHQW
LL (QHUJ\FRQWUROV\VWHPVFRPEXVWLRQV\VWHPVUDLOURDGV\VWHPVDYLDWLRQ
V\VWHPVPHGLFDOHTXLSPHQWDPXVHPHQWPDFKLQHVYHKLFOHVVDIHW\
HTXLSPHQWDQGLQVWDOODWLRQVVXEMHFWWRVHSDUDWHLQGXVWU\RUJRYHUQPHQW
UHJXODWLRQV
LLL 6\VWHPVPDFKLQHVDQGHTXLSPHQWWKDWFRXOGSUHVHQWDULVNWROLIHRU
SURSHUW\3OHDVHNQRZDQGREVHUYHDOOSURKLELWLRQVRIXVHDSSOLFDEOHWR
WKLV*RRG
1(9(586(7+(352'8&7)25$1$33/,&$7,21,192/9,1*6(5,286
5,6.72/,)(253523(57<:,7+287(1685,1*7+$7 7+(6<67(0
$6$:+2/(+$6%((1'(6,*1('72$''5(667+(5,6.6$1'7+$7
7+( 6(//(56 352'8&7 ,6 3523(5/< 5$7(' $1' ,167$//(' )25
7+(,17(1'('86(:,7+,17+(29(5$//(48,30(17256<67(0
 3URJUDPPDEOH 3URGXFWV 6HOOHU VKDOO QRW EH UHVSRQVLEOH IRU WKH XVHUV SUR
JUDPPLQJRIDSURJUDPPDEOH*RRGRUDQ\FRQVHTXHQFHWKHUHRI
 3HUIRUPDQFH'DWD 3HUIRUPDQFHGDWDJLYHQ LQWKLVFDWDORJ LVSURYLGHGDV D
JXLGHIRUWKHXVHULQGHWHUPLQLQJVXLWDELOLW\DQGGRHVQRWFRQVWLWXWHDZDUUDQW\
,WPD\UHSUHVHQWWKHUHVXOWRI6HOOHUVWHVWFRQGLWLRQVDQGWKHXVHUPXVWFRUUH
ODWHLWWRDFWXDODSSOLFDWLRQUHTXLUHPHQWV$FWXDOSHUIRUPDQFHLVVXEMHFWWRWKH
6HOOHUV:DUUDQW\DQG/LPLWDWLRQVRI/LDELOLW\
 &KDQJH LQ 6SHFLILFDWLRQV 3URGXFW VSHFLILFDWLRQV DQG DFFHVVRULHV PD\ EH
FKDQJHGDWDQ\WLPHEDVHGRQLPSURYHPHQWVDQGRWKHUUHDVRQV,WLVRXUSUDF
WLFHWRFKDQJHSDUWQXPEHUVZKHQSXEOLVKHGUDWLQJVRUIHDWXUHVDUHFKDQJHG
RUZKHQVLJQLILFDQWFRQVWUXFWLRQFKDQJHVDUHPDGH+RZHYHUVRPHVSHFLILFD
WLRQVRIWKH*RRGPD\EHFKDQJHGZLWKRXWDQ\QRWLFH:KHQLQGRXEWVSHFLDO
SDUWQXPEHUVPD\ EHDVVLJQHGWRIL[RU HVWDEOLVK NH\VSHFLILFDWLRQVIRU\RXU
DSSOLFDWLRQ 3OHDVH FRQVXOW ZLWK \RXU 6HOOHUV UHSUHVHQWDWLYH DW DQ\ WLPH WR
FRQILUPDFWXDOVSHFLILFDWLRQVRISXUFKDVHG*RRG
 (UURUV DQG 2PLVVLRQV 7KH LQIRUPDWLRQ LQ WKLV FDWDORJ KDV EHHQ FDUHIXOO\
FKHFNHGDQGLVEHOLHYHGWREHDFFXUDWHKRZHYHUQRUHVSRQVLELOLW\LVDVVXPHG
IRUFOHULFDOW\SRJUDSKLFDORUSURRIUHDGLQJHUURUVRURPLVVLRQV
2052121/,1(
*OREDOKWWSZZZRPURQFRP
86$KWWSZZZRPURQFRPRHL
&DQDGDKWWSZZZRPURQFD
Cat. No. R301-E3-01 2/04 Specifications subject to change without notice Printed in USA
20521&$1$'$,1&
0LOQHU$YHQXH
7RURQWR2QWDULR0%9

20521(/(&7521,&6//&
2QH&RPPHUFH'ULYH
6FKDXPEXUJ,/

)RU86WHFKQLFDOVXSSRUWRURWKHULQTXLULHV

&RPSOHWH¦7HUPVDQG&RQGLWLRQVRI6DOH§IRUSURGXFWSXUFKDVHDQGXVHDUHRQ2PURQ©VZHEVLWH
DWZZZRPURQFRPRHL¤XQGHUWKH¦$ERXW8V§WDELQWKH/HJDO0DWWHUVVHFWLRQ
$//',0(16,2166+2:1$5(,10,//,0(7(56
7RFRQYHUWPLOOLPHWHUVLQWRLQFKHVPXOWLSO\E\7RFRQYHUWJUDPVLQWRRXQFHVPXOWLSO\E\
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Omron:
CPM2A-40CDT-D CPM2A-30CDR-D CPM2A-40CDR-A CPM2A-20CDR-A CPM2A-60CDR-A CPM2A-40CDT1-D
CPM2A-30CDR-A CPM2A-60CDR-D CPM2A-BAT01 CPM2A-60CDT1-D CPM2A-40CDR-D CPM2A-20CDR-D
CPM2A-30CDT1-D CPM2A-30CDT-D CPM2A-20CDT-D CPM2A-20CDT1-D CPM2A-60CDT-D