Surge Voltage Protection Adapter
for Mobile Phone and Radio Link Systems
COAXTRAB
Sta y on the air with COAXTRAB . For the connection
of antennae in transceiver systems with F or N
connectors, COAXTRAB offers ideal surge voltage
protection. Thanks to the good impedance matching,
high transmission capacities of frequencies up to 3
GHz are no problem.
As coarse protection, there is a replaceable gas-
filled surge voltage arrester in the CN-UB-280DC...
adapter housing. In the case of a fault the surge voltage
arrester can be remov ed b y unscrewíng a scre w in the
housing and inserting the replacement CN-UB-G1 gas
arrester.
The protective adapter can be mounted permanently ,
in the switch cabinet, for example, with the CN-UB as-
sembly board.
Phoenix Contact GmbH & Co. KG • 32823 Blomberg, Germany
Phone +49 52 35 3-00 • Fax +49 52 35 3-4 12 00 • www.phoenixcontact.com
Technical data
Type Article no.
Pcs.
Pkt.
COAXTRAB,
as surge voltage protection for coaxial cables N-Connector
N-Connector
CN-UB-280DC-SB
1
)
28 18 14 8 1
CN-UB-280DC-BB
1
)
28 18 85 0 1
Reserve gas-filled surge arrester
CN-UB assembly board
CN-UB-G1 28 18 20 3 10
CN-UB/MP 28 18 13 5 10
Technical data
IEC category/VDE requirement class:
Arrester rated voltage (highest constant volt.) U
C
:
Nominal current I
N
:
Operating current I
C
at U
C
:
Nominal discharge surge current I
n
(8/20):
Output voltage threshold at 1 kV/µs: asym. (
6
)
Protection level U
p
: asym. (
6
)
Response time t
a
: asym. (
6
)
Cut-off frequency f
g
(3 dB) (typ.): asym. in a 50
system
Standing wave ratio (SWR) in a 50
system:
perm. HF power P
max
at SWR= 1.1/
in a 50
system:
Capacitance (typ.): asym. (GND/
6
)
Connection:
Temperature range:
Protection type in acc. with IEC 529/ EN 60 529:
Approvals:
Based on test standards:
C2, C3, D1
280 V DC
5 A/25 °C
1 µA
20 kA
700 V
700 V
100 ns
> 3 GHz
1.1 bis 2.0 GHz
700 W/200 W
1.5 pF
N-Connector 50
– 25 °C bis + 80 °C
IP 55
A
Draft IEC 61643-21:2000-09, E VDE 0845 T.3-1:1999-07
1
) with 7/16 connectors on request
COAXTRAB CN-UB-280DC
with N-Connector
PHOENIX CONTACT Page 2 of 3
Dimensional drawing CN-UB 280 DC-SB and CN-UB 280 DC-BB
25
72 11
13,4
15,8
25
11
13,4
15,8
67
11
11
Typical attenuation curve CN-UB-280DC...
22
22
Typical VSWR on CN-UB-280DC...
a
E
2G
0,2
dB
1M
0,4
0,6
0,8
1,0
1,2
1,4
1,6 1,4 (0,17)
1,3 (0,13)
1,2 (0,09)
1,1 (0,05)
1,0 (0,0)
VSWR ( r)
1G 3G
Frequency
22
22
22
22
11
11
11
11
4,77
6,6 35
16
30
5,2
20,65
2
Dimensional drawing CN-UB assembly board
PHOENIX CONTACT Seite 3 von 3
PHOENIX CONTACT 15.12.00 TNR: 5099935-00 http://www.phoenixcontact.com
Technical data
Type Article no.
Pcs.
Pkt.
COAXTRAB,
as surge voltage protection for coaxial cables N-Connector
N-Connector
CF-UB-280DC-SB-SET 28 39 54 1 1
Reserve gas-filled surge arrester
CN-UB assembly board
CN-UB-G1 28 18 20 3 10
CN-UB/MP 28 18 13 5 10
Technical data
IEC category/VDE requirement class:
Arrester rated voltage (highest constant volt.) U
C
:
Operating current I
C
at U
C
:
Nominal discharge surge current I
n
(8/20):
Output voltage threshold at 1 kV/µs: asym. (
6
)
Protection level U
p
: asym. (
6
)
Response time t
a
: /asym. (
6
)
Cut-off frequency f
g
(3 dB) (typ.): asym. in a 50
system
Capacitance (typ.): asym. (
6
)
Connection:
Temperature range:
Protection type in acc. with IEC 529/ EN 60 529
Based on test standards:
C2, C3, D1
280 V DC
1 µA
10 kA
700 V
700 V
100 ns
> 2 GHz
1.5 pF
F-Connector 75
– 20 °C bis + 80 °C
IP 55
Draft IEC 61643-21:2000-09, E VDE 0845 T.3-1:1999-07
1
) with 7/16 connectors on request
COAXTRAB CF-UB-280DC-SB-SET
with F-Connector
PHOENIX CONTACT Page 3 of 3
Dimensional drawing CN-UB 280 DC-SB and CN-UB 280 DC-BB
Dimensional drawing CN-UB assembly board
4,77
6,6 35
16
30
5,2
20,65
2
25
72 11
13,4
15,8
25
11
13,4
15,8
67