Bussmann (R) Square Body - DIN 43 653 10-400A 690V (IEC/U.L.) Electrical Characteristics Size 000 00 n n n Rated Current RMS-Amps 10 16 20 25 32 40 50 63 80 100 125 160 200 250 315 25 32 40 50 63 80 100 125 160 200 250 315 350 400 I2t (A2 Sec) Clearing Pre-arc at 660V 3.8 7.2 11.5 19 40 69 115 215 380 695 1200 2300 4200 7750 12000 19 28.5 50 95 170 310 620 1000 1900 3400 6250 10000 13500 18000 25.5 48 78 130 270 460 770 1450 2550 4650 8500 16000 28000 51500 80500 130 195 360 640 1200 2100 4150 6950 13000 23000 42000 68500 91500 125000 Watts Loss 3.0 5.5 7 9 10 12 15 16 19 24 28 32 37 42 52 6 7 9 10 12 15 20 25 30 35 45 55 60 70 7-11-01 SB01191 (R) Ordering Information -U/80 Without Indicator -/80 Visual Indicator -TN/80 Type T Indicator for Micro 170M1308 170M1309 170M1310 170M1311 170M1312 170M1313 170M1314 170M1315 170M1316 170M1317 170M1318 170M1319 170M1320 170M1321 170M1322 170M1358 170M1359 170M1360 170M1361 170M1362 170M1363 170M1364 170M1365 170M1366 170M1367 170M1368 170M1369 170M1370 170M1371 170M1372 170M2608 170M2609 170M2610 170M2611 170M2612 170M2613 170M2614 170M2615 170M2616 170M2617 170M2618 170M2619 170M2620 170M2621 170M1408 170M1409 170M1410 170M1411 170M1412 170M1413 170M1414 170M1415 170M1416 170M1417 170M1418 170M1419 170M1420 170M1421 170M1422 170M2658 170M2659 170M2660 170M2661 170M2662 170M2663 170M2664 170M2665 170M2666 170M2667 170M2668 170M2669 170M2670 170M2671 U.L. Recognition/CSA Component Acceptance on Size 000. Interrupting rating 200kA (Estimated 300kA) RMS Symmetrical. Watts loss provided at rated current. Microswitch indicator ordered separately. R Curves Carton Qty. Carton Weight (kg) 10 1.34 5 1.05 BIF # 17056310 17056312 1 kg = 2.2 lbs. 1 lb = 0.45 kg Form No. Page 1 of 2 BIF Doc #720013 Bussmann (R) Square Body - DIN 43 653 10-400A 690V (IEC/U.L.) R (R) Electrical Characteristics Total Clearing I2t The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K , given as a function of applied working voltage, E g , (RMS). 1.5 Arc Voltage This curve gives the peak arc voltage, U L , which may appear across the fuse during its operation as a function of the applied working voltage, E g , (RMS) at a power factor of 15%. 1.4 1.2 103 9 8 7 6 K 1.0 0.5 0.4 1.0 Kp 0.8 UL 0.6 0.5 0.4 0.3 5 0.3 Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current . The correction factor, K p , is given as a function of the RMS load current, Ib , in % of the rated current . 0.2 4 0.2 Eg Eg 3 200 100 200 300 400 500 600 690 300 400 500 Ib 0.1 600 690 30 40 50 60 70 80 90 100% Dimensions DIN 43 653: Type -U/80, -/80, -TN/80 Size 000 00 D 40 51 E 21 30 F 20 28 G 51 67 H 8 10 K 2 2 Dimension in mm. 1mm = 0.0394 1 = 25.4mm 54 Indicator* D K G 100 78 E H F *Indication for Size 00 Fuses is a red pin The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications. 7-11-01 SB01191 Form No. Page 2 of 2 BIF Doc #720013