HS201DR Series * 35 & 38 amp AC output @ 40C * Dual Channel output * 4 to 32 VDC input control voltage * DIN Rail mounted * UL, cUL, CE approved SSRs PRODUCT SELECTION Description 4-32 VDC Control 35 A 38 A HS201DR-CC2425W3U HS201DR-CD4850W4U HS201DR-CC2425W3U HS201DR-CD4850W4U 24-280 600 0.1 500 35 0.15 275/300 1.3 380/370 0.5 48-660 1200 0.25 500 38 0.15 710/750 1.7 2520/2320 0.5 OUTPUT SPECIFICATIONS (1) Description Operating Voltage (47-63Hz) [Vrms] Transient Overvoltage [Vpk] Maximum Off-State Leakage Current @ Rated Voltage [mArms] Minimum Off-State dv/dt @ Maximum Rated Voltage [V/sec] (2) Maximum Load Current [Arms] Minimum Load Current [Arms] Maximum 1 Cycle Surge Current (50/60 Hz) [Apk] Maximum On-State Voltage Drop @ Rated Current [Vpk] Maximum It for fusing (50/60 Hz, 1/2 cycle) [A sec] Minimum Power Factor (with Maximum Load) INPUT SPECIFICATIONS (1) Description Control Voltage Range Minimum Turn-On Voltage Minimum Turn-Off Voltage Maximum Reverse Voltage Typical Input Current Nominal Input Impeadance Maximum Turn-On Time [msec] Maximum Turn-Off Time [msec] Parameters 4-32 VDC 4.0 VDC 1.0 VDC 32 VDC 10 mA @ 12 VDC (3) 1/2 Cycle 1/2 Cycle GENERAL SPECIFICATIONS Description Dielectric Strength, Input/Output/Base (50/60Hz) Minimum Insulation Resistance (@ 500 V DC) Maximum Capacitance, Input/Output Ambient Operating Temperature Range Ambient Storage Temperature Range Status Indicator Display Weight (typical) Encapsulation Load Terminals Screw Torque Range Thermal pad installed GENERAL NOTES 1) All parameters at 25C unless otherwise specified. 2) Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1 3) Input circuitry for DC control version incorporates active current limiter. NOTE: For more information see Evolution Dual spec sheet. Parameters 4000 Vrms 109 Ohms 10 pF -40 to 80C -40 to 125C Yes 1.03 lb (453g) Themally Conductive Epoxy 18-20 in/lbs (2.0-2.26 Nm) Yes MECHANICAL SPECIFICATIONS THERMAL DERATE INFORMATION AGENCY APPROVALS Designed in accordance with the requirements of IEC 62314 Agency approvals are for relay only. E116950 Rev. 110911 ANNEX - ENVIROMENTAL INFORMATION