Power Supplies
3
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com.
134
SDP™ Low Power DIN Rail Series
The compact, lightweight DIN Rail power supplies come
in output voltages from 5 to 48 Vdc and power ratings of
up to 100 Watts. These extra small, efcient units are
designed specically for the industrial environment. Each
unit is rated from -10ºC to 70ºC, with no derating necessary
until above 60ºC.
Many extra “industrial” features are standard for the
SDP PowerBoostTM overload circuitry can start up
industrial loads (i.e. motors, relays, solenoids and DC-DC
converters), that can cause ordinary power supplies to
foldback or shutdown. Each unit contains a DC indicator
and front panel adjustment potentiometer. With the SolaHD
SDP series, you can count on a high grade design.
Applications
Industrial Control
Process Control
Machine Control
Building Automation
Instrumentation
Features
Ultra slim 15W footprint
No tools required for mounting
Adjustable output
PowerBoostTM industrial overload design
Overvoltage, short circuit protection
Continuous short circuit protection
Low output noise
Screw terminal connections
Three year limited warranty
• NEC Class 2 power supply acc. to NFPA 70 article
725-41 (a)(2) except Model SDP 4-24-100RT
Certifications and Compliances
Listed, Industrial Control Equipment, E61379
- UL 508, CSA C22.2 No. 107.1
UL 60950
E137632
CUL/CSA-C22.2
No. 234-M90
Recognized Component, ITE, E137632
- UL 60950-1/CSA C22.2 No. 60950-1, 2nd Edition
UL 60950
E137632
CUL/CSA-C22.2
No. 234-M90
Recognized Component, Haz. Loc., E234790
- ISA 12.12.01, CSA C22.2 No. 213
- Class I, Division 2, Groups A, B, C, D
- IEC/EN60950-1, 2nd Edition
• RoHS Compliant
Related Products
SDN™ Series
SCP Series
Selection Table
Catalog Number DC Output Voltage Output Current Ripple / Noise Size (H x W x D) - in. (mm)
SDP 5-5-100T 5 - 6 V 5 A
<50 mVpp
2.95 in x 1.77 in x 3.58 in
(75.0 mm x 45.0 mm x 91.0 mm)
SDP 2-12-100T 10 - 12 V 3 - 2.5 A
SDP 3-15-100T 12 - 15 V 4.2 - 3.4 A
SDP 1-48-100T 48 - 56 V 1 A
SDP 06-24-100T
24-28 Vdc
0.6 A 2.95 in x 0.9 in x 3.8 in
(75.0 mm x 22.8 mm x 96.7 mm)
SDP 1-24-100T 1.3 A 2.95 in x 1.77 in x 3.58 in
(75.0 mm x 45.0 mm x 91.0 mm)
SDP 2-24-100T 2.1 A
SDP 4-24-100LT 3.8 A 2.95 in x 2.85 in x 3.8 in
(75.0 mm x 72.5 mm x 96.7 mm)
SDP 4-24-100RT * 4.2 A
* NEC Class 1
E61379 E137632
E234790
Power Supplies 3
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com.
135
SDP™ Series Specifications (24 V models)
Description Catalog Number
SDP 06-24-100T SDP 1-24-100T SDP 2-24-100T SDP 4-24-100LT SDP 4-24-100RT
Input
Input Voltage 185-264 Vac, 90-375 Vdc 85-132 / 176-264 Vac, 210-375 Vdc
Input Frequency 47-63 Hz
Input Current 0.4 A / 0.25 A 0.7 A / 0.4 A 1.1 A / 0.7 A 1.8 A / 1.0 A 2.2 A / 1.2 A
External Fusing Not required. Unit provides internal fuse (T3A, not accessible)
Hold-Up Time > 25 ms
Efficiency > 80% typ. > 83% typ. > 86% typ. > 88% typ.
Losses < 3.75 W typ. < 6.1 W typ. < 8.1 W typ. < 12 W typ.
Output
Output Voltage 24 V (22.5 - 28.5 Vdc Adj.) 24 V (24 - 25.7 Vdc Adj.) 24 V (22.5 - 28.5 Vdc Adj.)
Voltage Regulation Static 0.5% Vout, dynamic + 2% Vout overall\
Ripple/Noise 2< 50 mVpp
Overvoltage Protection (OVP) > 30 Vdc, but < 33 Vdc, auto recovery > 26 Vdc, but < 27.2
Vdc, auto recovery
> 30 Vdc, but < 33 Vdc,
auto recovery
Output Noise
Suppression Radiated EMI values below EN61000-6-2
Rated Continuous
Loading
0.63 A @ 24 Vdc /
0.54 A @ 28 Vdc
1.3 A @ 24 Vdc /
1.1 A @ 28 Vdc
2.1 A @ 24 Vdc /
1.8 A @ 28 Vdc 3.8 A @ 24.5 Vdc 4.2 A @ 24.5 Vdc /
3.6 A @ 28 Vdc
Overload Behavior Continuous operation at overload/short-circuit: up to 1.5 x Nominal Current Continuous
Protection Unit is continuously protected against short-circuit, overload and open-circuit.
Power Back Immunity 35 V
Installation
Status Indicators Green LED on, when Vout “OK”.
Case & Mounting Molded plastic housing using UL 94 approved ameproof material rating 94V-2.
Simple snap-on to DIN TS35/7.5 or TS35/15 rail system.
Dimensions
H x W x D - inches (mm) 2.95 x 0.90 x 3.80
(75.0 x 22.8 x 96.7)
2.95 x 1.77 x 3.58
(75.0 x 45.0 x 91.0)
2.95 x 2.85 x 3.80
(75.0 x 72.5 x 96.7)
Weight - lbs (kg) 0.4 lbs (.18 kg) 0.5 lbs (.23 kg) 0.7 lbs (.32 kg)
Mounting Orientation Standard: Vertical; Optional: Horizontal or on top (Contact Technical Services).
Ventilation/Cooling
•Free space for cooling Normal convection, no fan required; Above/below: 25 mm recommended.
Connection
•Connector size range Input: screw terminals, connector size range: 20-12AWG (1.5 - 6 mm2) for solid or stranded conductors.
General
Electromagnetic
Emissions (EMC) EN61000-6-3 (Includes EN61000-6-4) Class B (EN 55022) incl. Annex A
Electromagnetic
Immunity (EMI) EN61000-6-2 (Includes EN61000-6-1) (EN55024) Criterion A: no derogation of performance
Temperature Storage: -25°C to +85°C Operation: -10° to +60°C full power with linear derating to half power from 60°C to 70°C.
(Convection cooling, no forced air required).
MTBF > 500,000 hours according to Telcordia/Bellcore Document SR-332, Issue 1
Humidity Up to 90% RH, noncondensing; IEC 68-2-2, 68-2-3
Safe Low Voltage SELV (acc. EN60950)
Protection Class/Voltage IP20 (IEC529), Protection Class 1 (IEC536)
Warranty 3 year limited warranty
Notes:
1. Not UL listed for DC input.
2. Ripple/noise is stated as typical values when measured with a 20 MHz, bandwidth scope and 50 Ohm resistor.
Power Supplies
3
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com.
136
SDP™ Series Specifications (Other Voltages)
Description Catalog Number
SDP 5-5-100T SDP 2-12-100T SDP 3-15-100T SDP 1-48-100T
Input
Input Voltage 185-264 Vac, 90-375 Vdc
Input Frequency 47 - 63 Hz
Input Current 0.6 A @ 102 Vac;
0.33 A @196 Vac
1.0 A @ 102 Vac;
0.6 A @ 196 Vac
<1.0 A @ 100 Vac;
<0.6 A @ 196 Vac
External Fusing Not required. Unit provides internal fuse (T3A, not accessible)
Hold-Up Time > 25 ms
Efficiency > 80% typ. > 86% typ. > 90% typ.
Losses 7.5 W typ. 8.1 W typ. < 8.1 W typ.
Output
Output Voltage 5 - 5.5 Vdc (5 - 6 min adj.) 12 Vdc (9.9 - 12.1 min adj. ) 15 Vdc (11.9 - 15.1 min adj.) 48 Vdc (48 - 56 min adj.)
Voltage Regulation < 2% Dynamic; < 0.5% Static
Ripple/Noise 2< 50 mVpp
Overvoltage Protection (OVP) > 6.7 Vdc > 18 Vdc > 20 Vdc > 56 Vdc
Output Noise Suppression Radiated EMI values below EN61000-6-2
Rated Continuous Loading lout = 5A @ Vout = 5.1V 3A @ 10 Vdc
2.5A @12 Vdc
4.2A @ 12 Vdc
3.4A @ 15 Vdc
Up to 1.05A @ 48 V
0.9A @ 56 V
Overload Behavior Continuous operation at overload/short-circuit: up to 1.5 x Nominal Current Continuous
Protection Unit is continuously protected against short-circuit, overload and open-circuit.
Power Back Immunity 10 V 22 V 80 V
Installation
Status Indicators Green LED on, when Vout “OK”.
Case & Mounting Molded plastic housing using UL 94 approved ameproof material rating 94V-2.
Simple snap-on to DIN TS35/7.5 or TS35/15 rail system.
Dimensions
(H x W x D) (in/mm) 2.95 x 1.77 x 3.58 (75.0 x 45.0 x 91.0)
Weight - lbs (kg) 0.5 lbs (.23 kg)
Mounting Orientation Standard: Vertical; Optional: Horizontal or On Top (Contact Technical Services).
Ventilation/Cooling
•Free space for cooling Normal convection, no fan required; Above/below: 25 mm recommended.
Connection
•Connector size range Input: screw terminals, connector size range: 20-12 AWG (1.5 - 6 mm2) for solid or stranded conductors.
General
Temperature Storage: -25°C to +85°C Operation: -10°C to +60°C full power with linear derating to half power from +60°C to +70°C.
(Convection cooling, no forced air required).
MTBF > 500,000 hours according to Telcordia/Bellcore Document SR-332, Issue 1.
Humidity Up to 90% RH, noncondensing; IEC 68-2-2, 68-2-3
Electromagnetic Emissions
(EMC) EN61000-6-3 (Includes EN61000-6-4) Class B (EN 55022) incl. Annex A
Electromagnetic Immunity
(EMI) EN61000-6-2 (Includes EN61000-6-1) (EN55024) Criterion A: no degradation of performance
Safe Low Voltage SELV (acc. EN60950)
Protection Class/Voltage IP20 (IEC529), Protection Class 1 (IEC536)
Warranty 3 year limited warranty
Notes:
1. Not UL listed for DC input.
2. Ripple/noise is stated as typical values when measured with a 20 MHz, bandwidth scope and 50 Ohm resistor.