Products and specifications subject to change without notice.
Consult factory for application assistance.
204 Airline Drive, Suite 300, Coppell, Texas 75019 / Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com
2-30
DIGITAL I/O MODULES
DIN-RAIL MOUNTABLE OUTPUT MODULES
1.96 (50)
2.77 (70)
0.125 (3)
1.77 (45) 0.56 (14)
2.36 (60)
2.46 (62)
0.16 (4)
0.69 (17.5)
DIMENSIONS: INCHES (MILLIMETERS)
TOLERANCE: ±0.020 (±0.50)
CASE COLORS:
AC-BLACK
DC-RED
FEATURES:
CE Compliant
DIN-Rail Mountable Single Point Output Modules (35mm DIN)
UL Recognized/Horse Power Rated (E46203)/
CSA certified (38595)
AC Output Rating 5 Amp at 12 to 280 VAC,
with 250 Amp Single Cycle Surge Capability
DC Output Rating 3 Amp at 3 to 60 VDC
3 to 32 VDC Input for AC Module, 5V or 24V for
DC Module
Zero Voltage Turn-on for AC Module
4 kV Optical Isolation with LED Indicator
Barrier Strips Accept 14 to 28 AWG Wire
Configured for Panel Mounting
*LOAD MAY BE WIRED IN LOCATION A OR B.
DC INDUCTIVE LOADS MUST BE DIODE SUPRESSED
TO PREVENT DAMAGE TO THE I/O MODULE.
VAC
+VCC LOGIC
VAC
DIN RAIL
DC OUTPUT MODULE
1
+VDC
INPUT
LED
REPLACEABLE
5A FUSE
SCREW
TERMINALS
2
3
4
+VCC LOGIC SUPPLY
–VDC
AMPLIFIER
Rc
(EQUIVALENT CIRCUIT DIAGRAMS)
LOAD* (A)
LOAD* (B)
DIN RAIL
AC OUTPUT MODULE
1
VAC
INPUT
LED
REPLACEABLE
5A FUSE
SCREW
TERMINALS
2
3
4
+VCC LOGIC SUPPLY
*LOAD MAY BE WIRED IN LOCATION A OR B
ZERO
VOLTAGE
CIRCUIT
LOAD* (A)
VAC LOAD* (B)
S
N
U
B
Products and specifications subject to change without notice.
Consult factory for application assistance.
204 Airline Drive, Suite 300, Coppell, Texas 75019 / Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com
2-31
DIGITAL I/O MODULES
DIN-RAIL OUTPUT MODULES
INPUT SPECIFICATIONS: (1)
Model Number DROAC DRODC5 DRODC24
Parameter Units
Nominal Voltage 5-24 5.0 24.0 VDC
Minimum Voltage 3.7 3.5 18.0 VDC
Maximum Voltage 32 8.0 32.0 VDC
Drop-Out Voltage 1.0 1.0 1.0 VDC
Maximum Current (2) 18.0 18.0 13.0 mA
Resistance (3) 250 2000 Ohms
OUTPUT SPECIFICATIONS: (1)
Model Number DRODC5
DROAC DRODC24
Parameter
Nominal Line Voltage 120/240 VAC 5-48 V
Minimim Line Voltage 12 VAC 3.0 V
Maximum Line Voltage 280 VAC 60 V
Max Off-State Voltage (4) 600 Vpeak 60 V
Max Off-State Leakage (5) .1 mArms 10 µA
Static Off-State dv/dt (6) 200 V / µsec N/A
Maximum Rated On-State
Current (7) 5.0 Arms 3.0 A
Min On-State Current 50 mArms 10 mA
Max Surge Current (8) 250 Apeak 5.0 A
On-State Voltage Drop (9) 1.6 V 1.5 V
Horse Power Rating (13) 1/2 H.P. N/A
GENERAL SPECIFICATIONS: (1)
Model Number DROAC DRODC5
DRODC24
Parameter Units
Operating Temperature Range -30 to 80 -30 to 80 °C
Storage Temperature Range -40 to 100 -40 to 100 °C
Maximum Turn-on Time (10) 8.33 0.1 mSec
Maximum Turn-off Time (10) 8.33 0.75 mSec
Input/Output Isolation Voltage (11) 4000 4000 VAC
Input/Output Capacitance (typical) 8 8 pF
Line Frequency Range 47 to 63 DC Hertz
Fuse (12) 5 5 Amps
Notes:
(1) Specifications apply to an ambient temperature of -30 to 80°C unless otherwise noted.
(2) At nominal input voltage for DC modules, AC modules are current limited +/-10% at 25°C .
(3) +/-10% at 25°C for DC modules.
(4) Maximum 1 minute duration for OAC modules when applied as a DC voltage rather than
peak AC voltage.
(5) At maximum line voltage, 25°C for OAC modules, and 80°C for ODC modules.
(6) Minimum dv/dt per EIA/NARM RS443, method RS397. dv/dt ratings do not apply to ODC modules.
(7) At 40°C, derate OAC modules by 125 mA/°C to 80°C; derate ODC modules by 50 mA/°C to 80°C.
(8) At 25°C. Maximum duration: 1 AC cycle for OAC modules, 1 second for ODC modules.
(9) At maximum rated on-state current and 25°C.
(10) At maximum line voltage, maximum rated output current, nominal input voltage, 25°C.
Switching speed of OAC modules based upon 60 Hz line frequency.
(11) At 25°C for 1 second maximum duration.
(12) Fuse is Buss, PC-TRON #PCE5.
(13) 1/2 H.P. at 240 VAC, 1/4 H.P. at 120 VAC.
2