NH DIN Dual Indication Fuse Links NH
Class of Operation gL/gG, 400V AC, 35 to 400 Amps
Sizes 02 & 2
Form No. NH
Page 5 of 7
Data sheet 720099
Bussmann®
Cooper Bussmann®
Size 02 &2 Details:
Standards/Approvals: IEC60269, DIN 43 620, VDE0636
Rated Currents: 35, 40, 50, 63, 80, 100, 125, 160, 200,
224, 250, 315, 355 and 400 Amps
Time Current Characteristics for Size 02 & 2
Part
Number
Amp
Rating
I2t(Ampere 2seconds) Watts
Loss
Net weight
per fuse
Rated
Voltage
Minimum
Pre-arcing
I1120kA
@ 400Vac
35NHG02B-400 35 2400 7600 4.4
0.402kg 400Vac
40NHG02B-400 40 3300 10600 5.0
50NHG02B-400 50 4200 10400 6.5
63NHG02B-400 63 6600 16300 5.5
80NHG02B-400 80 10000 34800 5.5
100NHG02B-400 100 16000 56000 6.6
125NHG02B-400 125 24000 86400 8.7
160NHG02B-400 160 50000 185000 10.0
200NHG02B-400 200 89000 232000 12.0
224NHG02B-400 224 119000 322000 12.0
250NHG02B-400 250 171000 479000 14.0
0.630kg
315NHG2B-400 315 280000 924000 19.0
355NHG2B-400 355 350000 1155000 22.0
400NHG2B-400 400 504000 1673100 24.0