5-02-01 SB01155
HRCII-C Current-Limiting Fuses CGL
600 Volt, 1 to 600 Amps
Form No. CGL
Page 1 of 3
BIF Doc #4125
Bussmann®
General Information:
TRON®HRC FORM II Class C Fuses
• TRON®HRCII-C fuses are designed to withstand inrush
currents on typical motor start-ups while offering high
current limitation in the short-circuit region.
• The TRON®HRCII-C fuses can be sized close to the motor
nameplate rating.
• Closer protection is offered for many motor sizes with the
availability of these additional fuse ratings.
• TRON®HRCII-C fuses have a high degree of current-limitation
greatly reducing the magnetic forces and thermal stresses
produced in today’s high capacity systems.
• TRON®HRCII-C fuses have an interrupting rating of 200,000
RMS symmetrical amperes at 600 volts.
• TRON®HRCII-C fuses are dimensionally interchangeable with
other Form II fuses on the market and can be used with the
same confidence as other High Quality Buss Fuses.
Catalog Symbol: CGL
Current-Limiting
Ampere Rating: 1 to 600 Amperes
Voltage Rating: 600 Volts AC (or less)
1 to 30 Amps, 250 Volts DC (or less)
Interrupting Rating: 200,000A RMS Sym.
40,000A DC (1 to 30A)
Agency Approval:
CSA Certified, C22.2106, Class 1422, File 53787