Current Transducer LA 125-P
For the electronic measurement of currents : DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
Electrical data
IPN Primary nominal r.m.s. current 125 A
IPPrimary current, measuring range 0 .. ± 200 A
R M Measuring resistance @ TA = 70°C TA = 85°C
RM min RM max RM min RM max
with ± 12 V @ ± 125 A max 552 14 50
@ ± 200 A max 520 14 18
with ± 15 V @ ± 125 A max 25 74 40 72
@ ± 200 A max 25 34 40 1) 40 1)
ISN Secondary nominal r.m.s. current 125 mA
K N Conversion ratio 1 : 1000
VCSupply voltage (± 5 %) ± 12 .. 15 V
ICCurrent consumption 16 (@ ± 15 V) + ISmA
VdR.m.s. voltage for AC isolation test, 50 Hz, 1 mn 3kV
Accuracy - Dynamic performance data
XAccuracy @ IPN , TA = 25°C @ ± 15 V (± 5 %)± 0.60 %
@ ± 12 .. 15 V (± 5 %)± 0.80 %
εLLinearity < 0.15 %
Typ Max
IOOffset current @ IP = 0, TA = 25°C ± 0.40 mA
IOM Residual current 2) @ IP = 0, after an overload of 3 x IPN ± 0.50 mA
IOT Thermal drift of IO0°C .. + 70°C ± 0.15 ± 0.50 mA
- 25°C .. + 85°C ± 0.15 ± 0.60 mA
tra Reaction time @ 10 % of IP max < 500 ns
trResponse time 3) 4) @ 90 % of IP max < 1 µs
di/dt di/dt accurately followed 4) > 200 A/µs
fFrequency bandwidth 4) (- 1 dB) DC .. 100 kHz
General data
TAAmbient operating temperature - 25 .. + 85 °C
TSAmbient storage temperature - 40 .. + 90 °C
R S Secondary coil resistance @ TA = 70°C 32
TA = 85°C 33.5
mMass 40 g
Standards 5) EN 50178
Notes : 1) Measuring range limited to ± 180 A max
2) The result of the coercive field of the magnetic circuit
3) With a di/dt of 100 A/µs
4) The primary conductor is best filling the through-hole and/or the return
of the primary conductor is above the top of the transducer
5) A list of corresponding tests is available
Features
Closed loop (compensated) current
transducer using the Hall effect
Printed circuit board mounting
Insulated plastic case recognized
according to UL 94-V0.
Advantages
Excellent accuracy
Very good linearity
Low temperature drift
Optimized response time
Wide frequency bandwidth
No insertion losses
High immunity to external
interference
Current overload capability.
Applications
AC variable speed drives and servo
motor drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies
(UPS)
Switched Mode Power Supplies
(SMPS)
Power supplies for welding
applications.
IPN =125 A
980716/5
LEM Components www.lem.com
Secondary terminals
Terminal -:supply voltage -12 .. 15 V
Terminal M:measure
Terminal +:supply voltage +12 .. 15 V
Terminal :NC
Connection
Remarks
IS is positive when IP flows in the direction of the arrow.
Temperature of the primary conductor should not exceed
90°C.
Dynamic performances (di/dt and response time) are best
with a primary bar in low position in the through-hole.
In order to achieve the best magnetic coupling, the primary
windings have to be wound over the top edge of the device.
This is a standard model. For different versions (supply
voltages, turns ratios, unidirectional measurements...),
please contact us.
Mechanical characteristics
General tolerance ± 0.2 mm
Primary through-hole 17 x 11 mm
Fastening & connection of secondary 4 pins 0.63 x 0.56 mm
Recommended PCB hole 0.9 mm
Supplementary fastening 2 holes 1.75 mm
Recommended PCB hole 2.4 mm
Recommended screws KA 22 x 6
LEM code 47.30.60.006.0
Dimensions LA 125-P (in mm. 1 mm = 0.0394 inch)