Technical Data 1006 Effective August 2018
Supersedes February 2016
Low-Peak™ LPJ Class J 600Vac/300Vdc, 1-60A,
dual element, time-delay fuses
Catalog symbol:
• LPJ-(amp)SP (non-indicating)
• LPJ-(amp)SPI (indicating)
Description:
Bussmann® series Ultimate protection LPJ Class
J dual element, current-limiting, time-delay fuses
available with optional open fuse indication. Time-
delay – 10 seconds (minimum) at 500% of rated
current.
Specifications:
Ratings
• Volts
• 600Vac
• 300Vdc*
• Amps 1-60A
• IR
• 300kA Vac RMS Sym.
• 100kA Vdc
* Indicating versions not Vdc rated.
Agency information
• UL® Listed, Guide JDDZ, File E4273
• CSA® Certified, Class 1422-02, File 53787,
Class J per CSA 22.2 No. 248.
• CE
• RoHS compliant
Catalog numbers (amps) – non-indicating fuses
LPJ-1SP LPJ-3SP LPJ-7SP* LPJ-25SP*
LPJ-1-1/4SP LPJ-3-2/10SP LPJ-8SP* LPJ-30SP*
LPJ-1-6/10SP LPJ-3-1/2SP LPJ-9SP* LPJ-35SP*
LPJ-1-8/10SP LPJ-4SP LPJ-10SP* LPJ-40SP*
LPJ-2SP LPJ-4-1/2SP LPJ-12SP* LPJ-45SP*
LPJ-2-1/4SP LPJ-5SP LPJ-15SP* LPJ-50SP*
LPJ-2-1/2SP LPJ-5-6/10SP LPJ-17-1/2SP* LPJ-60SP*
LPJ-2-8/10SP LPJ-6SP* LPJ-20SP*
* Open fuse indication available by inserting the suffix
“I,” e.g., LPJ-15SPI. Requires 75Vac minimum voltage.
Indicating fuses are not Vdc rated.
Carton quantity:
Amp rating Carton qty.
1–60 10
Dimensions - in
2.38"
0.63"
35 to 60A
1.06"
0.5"
1 to 30A
0.81"
2.25"
(±0.03)
(±0.03) (±0.03)
(±0.03)
Features:
• Industry’s only UL Listed and CSA Certified fuse
with a 300kA interrupting rating that allows for
simple, worry-free installation in virtually any
application.
• Fast short-circuit protection and dual-element,
time-delay performance provide ultimate
protection.
• Reduces existing fuse inventory by up to 33%
when upgrading to Low-Peak fuses.
• Consistent 2:1 ampacity ratios for all Low-Peak
fuses make selective coordination easy.
• Long time-delay minimizes needless fuse
openings due to temporary overloads and
transient surges.
• Current-limitation protects downstream
components against damaging thermal and
magnetic effects of short-circuit currents.
• Dual-element fuses have lower resistance than
ordinary fuses so they run cooler. They can
often be sized for back-up protection against
motor burnout from overload or single-phasing if
other overload protective devices fail.
• Proper sizing can provide “no damage” Type
2 coordinated protection for NEMA® and IEC®
motor controllers.
• Space-saving package for equipment
downsizing.
Available with
easy
ID™
open fuse indication