DET3TC
Digital Ground Tester
n IP54 rated
n 2 and 3 point testing
n Selectable 25 V or 50 V output
n Complete with lead and stake kit
n Simple one button operation
n Hardwearing carry case
n Delivered with calibration certificate
n Attached Rod Technique (ART)
DET3TC
Digital Ground Tester
DESCRIPTION
The new ground testing instrument family from Megger
offers a unique solution to your ground stake testing needs.
The complete kit of instrument, test leads, stakes, batteries
and calibration certificate are delivered in a tough poly-
propylene carry case - everything you need to start testing in
one kit.
The ground rod tester is rated to IP54 meaking it truly an
outdoor instrument. The ground tester has been designed
to be easy to use - a large selectror switch makes selection of
2 pole or 3 pole test easy with gloved hands - and the design
makes the fitting of shorting links to perform 2 pole tests
a thing of the past. Using the optional clamp around the
ground rod connection allows the testing of the rod without
the need for disconnection, leaving the earthing system
intact during testing (ART). A large, clear, easy to read LCD
display and thumb sized test button again makes the
instrument particularly suited to the outdoor conditions of
ground testing.
In addition to this ease of use, the ground tester also auto-
matically checks the connection of the P spike and C spike,
indicating the status on the display. The instrument also
includes a voltmeter to allow you to measure the ground
voltage. The ground tester can measure resistance from
0.01 Ω through to 2000 Ω and earth voltages up to 100 V. To
allow accurate testing in noisy environments the instrument
is capable of rejecting noise of up to 40 V peak to peak.
The Megger digital ground tester is powered by eight AA
batteries which are widely available and also give excellent
testing time - the status of these batteries is given bya bar
graph on the LCD display allowing you to decide when to
change the batteries, before they expire.
The Megger ground testers are designed to meet stringnet
safety standards and are rated CAT IV 100 V.
OTHER TECHNICAL SALES OFFICES
Norristown USA, Sydney AUSTRALIA,
Toronto CANADA, Trappes FRANCE,
Kingdom of BAHRAIN, Mumbai INDIA,
Johannesburg SOUTH AFRICA and
Conjure THAILAND
UK
Archcliffe Road, Dover
CT17 9EN England
T (0) 1 304 502101
F (0) 1 304 207342
UNITED STATES
4271 Bronze Way
Dallas, TX 75237-1019 USA
T 1 800 723 2861
T 1 214 333 3201
F 1 214 331 7399
ISO STATEMENT
Registered to ISO 9001:2000 Cert. no. Q 09250
Registered to ISO 14001-1996 Cert. no. EMS 61597
DET3TC_DS_en_V07
www.megger.com
Megger is a registered trademark
Earth voltage accuracy:
2% ±2 V
Display
LCD
Battery type:
8 off AA cells
Operating temperature range:
-15 to +55 ºC
Storage temperature range:
-40 to +70 ºC
Safety
IEC61010-1 CAT IV 100 V*
EN61557-1
EN61557-5
EMC
IEC61326-1
Dimensions:
203 x 148 x 78 mm (8 x 5.7 x 3.2 inches)
Weight:
1 kg
* The CAT IV 100 V rating is dependant on the use of a
leadset of least this rating, for example the optional two wire
leadset part number 1001-858.
DET3TC
Digital Ground Tester
Item (Qty) Order Code
Digital tester 2 and 3 terminal DET3TC
Included Accessories
Hard carry case
Stake and wire kit
Optional Accessories
ICLAMP Current measuring clamp 1001-012
Right angled terminal adaptor set 6220-803
2 replacement earth test spikes (200 mm, 8 mm dia.) 6220-804
3 replacement test leads (15 m, 10 m, 3 m) 6220-805
‘Getting down to earth’ A Megger guide to earth testing 21500-072
Black crocodile clip (1) 6220-850
Leadset 1001-858
ORDERING INFORMATION
ELECTRICAL SPECIFICATIONS
Ingress protection:
IP54
C spike check:
Automatic
P spike check:
Automatic
Noise check:
Automatic
Noise rejection:
40 V peak to peak
2-wire test:
Yes
3-wire test:
Yes
No disconnect testing (ART):
Yes, with optional ICLAMP
Earth current range with ICLAMP:
0.5 mA to 19.9 A
Earth current accuracy:
5% ±3 digits
Resistance range:
0.01 to 2000 Ω
Resistance accuracy:
2% ±3 digits
Maximum probe resistance:
Rp limit: 100 kΩ (50 V output voltage)
Rc limit: 100 kΩ (50 V output voltage)
Limits reduced to 50 kΩ for 25 V output voltage
Limits reduced to 5 kΩ for 0.01 Ω resolution on 18 Ω range
Earth voltage range:
0 - 100 V a.c.