490
E5_N-H/E5_N-HT Advanced and Multi-Loop controllers
Universal compact digital
process controllers
The E5_N-H series of process controllers take the proven concept of the general
purpose E5_N series to a process level. Main features of the E5_N-H series are
universal inputs, process outputs and options such as transfer output, remote set-
point and setvalue programmer.
Control mode: ON/OFF or 2-PID, Valve control on EN-H/AN-H
Control output: relay, voltage (pulse), SSR, linear current and voltage
Power supply: 100/240 VAC or 24 VDC/VAC
Easy PC connection for parameter cloning, setting and tuning
Clear and intuitive set-up and operation
Ordering information
Note: - Output and Alarm Relays: 3 A/250 VAC, electrical life: 100,000 operations
-Output voltage (pulse): 12 V, 21 mA (ie. to drive solid state relays)
-Linear current: 0(4) to 20 mA
-Linear voltage output: 0 to 10 V
Accessories
E5CN-H option boards
(One slot available in each instrument)
Type Input Output Fixed option Alarms Order code
48x48 mm model (includes supply voltage indication)
On-panel Universal
TC/Pt/mV
mA/V
Relay output 3 software
alarms
2SUB
outputs
E5CN-HR2M-500 AC100-240 E5CN-HR2MD-500 AC/DC24
Voltage (pulse) E5CN-HQ2M-500 AC100-240 E5CN-HQ2MD-500 AC/DC24
Current output E5CN-HC2M-500 AC100-240 E5CN-HC2MD-500 AC/DC24
Linear voltage output E5CN-HV2M-500 AC100-240 E5CN-HV2MD-500 AC/DC24
Relay output SV programmer
(8 programs of
32 segments)
E5CN-HTR2M-500 AC100-240 E5CN-HTR2MD-500 AC/DC24
Voltage (pulse) E5CN-HTQ2M-500 AC100-240 E5CN-HTQ2MD-500 AC/DC24
Current output E5CN-HTC2M-500 AC100-240 E5CN-HTC2MD-500 AC/DC24
Linear voltage output E5CN-HTV2M-500 AC100-240 E5CN-HTV2MD-500 AC/DC24
Option Order code
Event inputs E53-CNBN2
Event inputs Control output 2
Voltage (for driving SSR)
E53-CNQBN2
Event inputs Heater burnout/SSR failure/
Heater overcurrent detection
E53-CNHBN2
Event inputs Transfer output E53-CNBFN2
Communications
RS-232C
Control output 2
Voltage (for driving SSR)
E53-CN01N2
Communications
RS-232C
E53-CNQ01N2
Communications
RS-232C
Heater burnout/SSR failure/
Heater overcurrent detection
E53-CNH01N2
Communications
RS-485
E53-CN03N2
Communications
RS-485
Control output 2
Voltage (for driving SSR)
E53-CNQO3N2
Communications
RS-485
Heater burnout/SSR failure/
Heater overcurrent detection
E53-CNH03N2
Communications
RS-485
3-phase heater burnout/SSR failure/
Heater overcurrent detection
E53-CNHH03N2
Control output 2
Voltage (for driving SSR)
Transfer output E53-CNQFN2
Control output 2
Voltage (for driving SSR)
Heater burnout/SSR failure/
Heater overcurrent detection
E53-CNQHN2
Control output 2
Voltage (for driving SSR)
3-phase heater burnout/SSR failure/
Heater overcurrent detection
E53-CNQHHN2
E5_N-H/E5_N-HT Advanced and Multi-Loop controllers
491
21 Temperature controllers
Note: - All E5EN-H/AN-H have 2 event inputs
-All E5EN-H/AN-H have Remote Setpoint 4 to 20 mA input
Specifications E5CN-H/EN-H/AN-H E5AN-H/EN-H output option boards
(2 slots available in E5_N-HAA__-500 models:
SS models have 2 fixed SSR output modules)
E5AN-H/EN-H option boards
(one slot available in each instrument)
E5AN-H/EN-H series optional tools
Control method Auxiliary output Control output 1/2 Heater burnout Transfer output Order code (includes supply voltage indication)
96x96 mm model 48x96 mm model
Basic 2 alarm relays none fitted, 2 slots 1-phase E5AN-HAA2HBM-500 AC100-240 E5EN-HAA2HBM-500 AC100-240
none fitted, 2 slots E5AN-HAA2HBMD-500 AC/DC24 E5EN-HAA2HBMD-500 AC/DC24
2 SSR output fitted E5AN-HSS2HBM-500 AC100-240 E5EN-HSS2HBM-500 AC100-240
2 SSR output fitted E5AN-HSS2HBMD-500 AC/DC24 E5EN-HSS2HBMD-500 AC/DC24
none fitted, 2 slots 3-phase
4 to 20 mA
output
E5AN-HAA2HHBFM-500 AC100-240 E5EN-HAA2HHBFM-500 AC100-240
none fitted, 2 slots E5AN-HAA2HHBFMD-500 AC/DC24 E5EN-HAA2HHBFMD-500 AC/DC24
2 SSR output fitted E5AN-HSS2HHBFM-500 AC100-240 E5EN-HSS2HHBFM-500 AC100-240
2 SSR output fitted E5AN-HSS2HHBFMD-500 AC/DC24 E5EN-HSS2HHBFMD-500 AC/DC24
3 alarm relays none fitted, 2 slots E5AN-HAA3BFM-500 AC100-240 E5EN-HAA3BFM-500 AC100-240
none fitted, 2 slots E5AN-HAA3BFMD-500 AC/DC24 E5EN-HAA3BFMD-500 AC/DC24
2 SSR output fitted E5AN-HSS3BFM-500 AC100-240 E5EN-HSS3BFM-500 AC100-240
2 SSR output fitted E5AN-HSS3BFMD-500 AC/DC24 E5EN-HSS3BFMD-500 AC/DC24
Valve controller 2 alarm relays 2 relay output fitted E5AN-HPRR2BM-500 AC100-240 E5EN-HPRR2BM-500 AC100-240
E5AN-HPRR2BMD-500 AC/DC24 E5EN-HPRR2BMD-500 AC/DC24
4 to 20 mA
output
E5AN-HPRR2BFM-500 AC100-240 E5EN-HPRR2BFM-500 AC100-240
E5AN-HPRR2BFMD-500 AC/DC24 E5EN-HPRR2BFMD-500 AC/DC24
SV programmer
(8 programs of
32 segments
2 alarm relays none fitted, 2 slots 1-phase E5AN-HTAA2HBM-500 E5EN-HTAA2HBM-500 AC100-240
E5AN-HTAA2HBMD-500 E5EN-HTAA2HBMD-500 AC/DC24
3-phase
4 to 20 mA
output
E5AN-HTAA2HHBFM-500 E5EN-HTAA2HHBFM-500
E5AN-HTAA2HHBFMD-500 E5EN-HTAA2HHBFMD-500
3 alarm relays E5AN-HTAA3BFM-500 E5EN-HTAA3BFM-500
E5AN-HTAA3BFMD-500 E5EN-HTAA3BFMD-500
SV programmer and
valve controller
2 alarm relays 2 relay output fitted E5AN-HTPRR2BM-500 E5EN-HTPRR2BM-500
E5AN-HTPRR2BMD-500 E5EN-HTPRR2BMD-500
4 to 20 mA
output
E5AN-HTPRR2BFM-500 E5EN-HTPRR2BFM-500
E5AN-HTPRR2BFMD-500 E5EN-HTPRR2BFMD-500
Supply voltage 100 to 240 VAC 50/60 Hz or 24 VAC, 50/60Hz; 24 VDC
Sensor input Thermocouple: K, J, T, E, L, U, N, R, S, B, W or PL II
Platinum resistance thermometer: Pt100 or JPt100
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V or 0 to 10 V
Control mode ON/OFF, 2-PID and valve (PRR)
Accuracy Thermocouple: (± 0.1% of indicated value or ±1°C, whichever
is greater) ± digit max. *1
Platinum resistance thermometer: (± 0.1% of indicated value
or ± 0.5°C, whichever is greater) ± 1 digit max.
Analogue input: ± 0.1% FS ± 1 digit max.
Auto-tuning yes, 40% and 100% MV output limit selection. When using
Heat/Cool: automatic cool gain adjustment
Self-tuning yes
RS-232C/RS-422/RS-485 optional, CompowayF or Modbus selectable
Event input Optional (Standard 2 event input in EN-H/AN-H)
QLP port (USB connection PC) yes
Ambient temperature -10 to 55°C
IP Rating front panel IP66
Sampling period 60 ms
Option Order code
Relay E53-RN
Voltage (pulse) PNP 12 VDC E53-QN
Voltage (pulse) NPN 12 VDC E53-Q3
Voltage (pulse) PNP 24 VDC E53-Q4
Linear 4 to 20 mA E53-C3N
Linear 0 to 20 mA E53-C3DN
Linear 0 to 10 V E53-V34N
Linear 0 to 5 V E53-V35N
Option Order code
RS-232C communications (CompoWay/F/Modbus) E53-EN01
RS-422 communications (CompoWay/F/Modbus) E53-EN02
RS-485 communications (CompoWay/F/Modbus) E53-EN03
event input E53-AKB
Option Order code
USB PC based configuration cable E58-CIFQ1