‧2/3/8 stage charging (Note 4)
‧Universal AC input / Full range
‧Built-in active PFC function PF>0.95
‧Protection: Reverse polarity / Short circuit / Over voltage / Over temperature
‧Charger for lead-acid batteries
‧3 color LED loading indicator
‧Built-in remote ON-OFF control
‧Built-in temperature compensation function
‧(depends on charging current)Built-in fan speed control
‧3 years warranty
■ Features :
SPECIFICATION
PB-600-12 PB-600-24 PB-600-48
MODEL
BOOST CHARGE VOLTAGE
FLOAT CHARGE VOLTAGE
OUTPUT CURRENT
BATTERY TYPE
RECOMMENDED BATTERY
CAPACITY(AMP HOURS)
(Note 3)
OUTPUT
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
INPUT
ENVIRONMENT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVER TEMPERATURE
SAFETY STANDARDS
SAFETY &
EMC
(Note 2)
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
OVER VOLTAGE
PROTECTION
AC CURRENT (Typ.)
14.4V 28.8V 57.6V
13.8V
40A
Open & Sealed Lead Acid
135 ~ 400AH
27.6V 55.2V
21A 10.5A
70 ~ 210AH 35 ~ 105AH
90 ~ 264VAC 127 ~ 370VDC
47 ~ 63Hz
86% 87% 89%
6.8A/115VAC 3.4A/230VAC
25A/115VAC 50A/230VAC
<3.5mA / 240VAC
16 ~ 18V 32 ~ 35V 64.5 ~ 69.5V
Protection type : Shut down o/p voltage, re-power on to recover
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
UL1012, TUV EN60335-1, EN60335-2-29 (except for 48V), EN60950-1(48V only) approved
Compliance to EN55022 class B (CISPR22), EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024; light industry level, criteria A
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH℃
-20 ~ +60 (Refer to "Derating Curve")℃
20 ~ 90% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH ℃
± ℃ ℃0.05%/ (0 ~ 50 )
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
MTBF 135.6K hrs min. MIL-HDBK-217F (25 )℃
230*158*67mm(L*W*H)
DIMENSIONOTHERS
NOTE
PACKING 2.2Kg; 6pcs/14.2Kg/1.76CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.℃
2. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
3. This is Mean Well's suggested range. Please consult your battery manufacturer for their suggestions about maximum charging current limitation.
4. Please choose the "3 stage" selection when the charger is used to charge the batteries and power the loads in the same time.
PB-600 series
600W Single Output Battery Charger
FUNCTION
REMOTE CONTROL
LEAKAGE CURRENT FROM BATTERY (Typ.)
FAST CHARGE
OUTPUT OK
CHARGER OK
TEMPERATURE SENSE
Open: Normal work Short: Stop Charging
1mA
2 / 3 / 8 stage selectable
Relay contact (RY13)
Relay contact (RY15)
By NTC
File Name:PB-600-SPEC 2014-09-15
POWER FACTOR (Typ.) 0.95/230VAC 0.98/115VAC at full load
EMC IMMUNITY
EMC EMISSION