1
Capacitive sensor CCN15-30GS60-A2-V1
Release date: 2012-05-29 15:29 Date of issue: 2012-05-29 189958_eng.xml
Germany: +49 621 776-4411
Subject to modifications without notice
Pepperl+Fuchs Group
fa-info@pepperl-fuchs.comwww.pepperl-fuchs.com
USA: +1 330 486 0001
fa-info@us.pepperl-fuchs.com
Singapore: +65 6779 9091
fa-info@sg.pepperl-fuchs.com
Copyright Pepperl+Fuchs
Model Number
CCN15-30GS60-A2-V1
Features
15 mm non-flush
Operating distance adjustable via po-
tentiometer
High EMC resistance
Stainless steel version
Complementary outputs
Operating voltage range 10 V
... 60 V DC
Connection
Pinout
Accessories
BF 30
Mounting flange, 30 mm
V1-G
4-pin, M12 female field-attachable connector
V1-W
4-pin, M12 female field-attachable connector
V1-G-2M-PUR
1L+
L-
4
2
3
1
3
4
2
1 BN
2 WH
3 BU
4 BK
Wire colors in accordance with EN 60947-5-2
(brown)
(white)
(blue)
(black)
Dimensions
Technical Data
General specifications
Switching element function PNP NO/NC
Rated operating distance sn15 mm
Installation non-flush
Output polarity DC
Assured operating distance sa0 ... 12.1 mm
Nominal ratings
Installation conditions
A 18 mm
B 10 mm
C 30 mm
F 60 mm
Operating voltage UB10 ... 60 V DC
Switching frequency f 0 ... 10 Hz
Reverse polarity protected reverse polarity protected
Short-circuit protection pulsing
Voltage drop Ud 2.8 V
Operating current IL0 ... 200 mA
Off-state current Ir0 ... 0.5 mA typ. 0.1 µA at 25 °C
No-load supply current I0 20 mA
Indication of the switching state LED, yellow
Functional safety related parameters
MTTFd 750 a
Mission Time (TM) 20 a
Diagnostic Coverage (DC) 0 %
Indicators/operating means
Potentiometer sensitivity adjustment
Ambient conditions
Ambient temperature -25 ... 70 °C (-13 ... 158 °F)
Storage temperature -40 ... 85 °C (-40 ... 185 °F)
Mechanical specifications
Connection type Device connector M12 x 1 , 4-pin
Housing material Stainless steel 1.4305 / AISI 303
Sensing face PBT
Protection degree IP67
Compliance with standards and directives
Standard conformity
Standards EN 60947-5-2:2007
IEC 60947-5-2:2007
Approvals and certificates
UL approval cULus Listed, General Purpose
CSA approval cCSAus Listed, General Purpose
Installation conditions
36
LED
18
59
60
75
5
M30 x 1.5
M12 x 1
CA
B F
metal-free zone
sensing face
support