B-Series - General Specifications Designed specifically for world market applications, the B-series utilizes the hydraulic magnetic principle which provides precise operation and performance even when exposed to extremely hot and/or cold application environments. Typical applications include power supplies, medical equipment, office equipment, control panels and marine equipment. In addition, these breakes meet CSA Standard 22.2 No. 100 for the Generator & Welder markets. 1-6 poles, 0.02 - 50 amps, up to 277 VAC or 80 VDC, with choice of time delays, terminals and actuator colors. Agency Certifications UL Recognized UL Standard 1077 CSA Accepted Component Supplementary Protector under Class 3215 30, FIle 047848 0 000 CSA Standard C22.2 No. 235 TUV Certified EN60934, under License No. R72040875 VDE Certified EN60934, VDE 0642 under File No. 10537 Component Recognition Program as Protectors Supplementary (Guide CCN/QVNU2, File E75596) UL Standard 508 Switches, Industrial Control (Guide CCN/NRNT2, File E148683) UL Standard 1500 Protectors, Supplementary for Marine Electrical & Fuel Systems (Guide PEQZ2, File E75596) Ignition Protection UL Listed UL Standard 489 Circuit Breakers, Molded Case, (Guide DIVQ, File E189195) UL Standard 489A Communications Equipment (Guide CCN/DITT, File E189195) www.carlingtech.com 57 B-Series - General Specifications Electrical Table A: Lists UL Recognized & CSA Certified configurations and performance capabilities as a Component Supplementary Protector. Notes for Table A: 1 Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse (15A minimum) at no more than 4 times the rating of the protector. 2 Same as note 1, except that backup fuse is limited to 80A maximum. 3 2 pole protector required (with one pole per power line) for: 250/125 VAC, 125/250 VAC and 208Y/120 VAC Power Systems. 1 pole protector required for : 125 VAC, 1O Power System. 58 www.carlingtech.com B-Series - General Specifications Electrical Table B: Lists UL Recognized, CSA, VDE & TUV Certified configurations & performance capabilities as a Component Supplementary Protector. Notes for Table B: 1 General Purpose Ratings for UL/CSA Only. 2 Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse (15A minimum) at no more than 4 times the rating of the protector. 3 Same as note 1, except that backup fuse is limited to 80 A maximum. Table C: Lists UL Recognized, CSA Certified configurations and performance capabilities as Protectors, Supplementary for Marine Electrical and Fuel Systems (CCN/Guide PEQZ2, File E75596). Ignition Protected per UL 1500. UL Classified Small Craft Electrical Devices, Marine in accordance with ISO 8846 (CCN/Guide UZMK, File MQ1515) as Marine Supplementary Protectors. Notes for Table C: 1 Available with special catalog number only (consult factory). 2 2 pole protector required (with one pole per power line) for: 250/125 VAC, 125/250 VAC and 208Y/120 VAC Power Systems. 1 pole protector required for : 125 VAC, 1O Power System. Table D: Lists UL Listed configurations and performance capabilities as Circuit Breakers for use in Communications Equipment (CCN/Guide DITT, File E189195), under UL489A Notes for Table D: 1 60 -90 amp ratings require parallel pole construction www.carlingtech.com 59 B-Series - General Specifications Electrical Maximum Voltage Current Ratings Standard Voltage Coils Auxiliary Switch Rating Insulation Resistance Dielectric Strength Resistance, Impedance Pulse Tolerance Curves 60 Mechanical 277VAC 50/60 Hz, 80VDC Standard current coils: 0.100, 0.250, 0.500, 0.750, 1.00, 2.50, 5.00, 7.50, 10.0, 15.0, 20.0, 25.0, 30.0, 35.0, 40.0 and 50.0 amps. Other ratings available, see ordering scheme. DC - 6V, 12V; AC - 120V, other ratings available, see ordering scheme. SPDT; 10.1 AMPS - 250VAC,1.0A 65 VDC or 0.5A 80 VDC, 0.1 Amps 125VAC (with gold contacts). VDE-1.0 Amp - 125VAC. Minimum of 100 Megohms at 500 VDC. UL, CSA - 1500 V 50/60 Hz for one minute between all electrically isolated terminals. B-Series circuit breakers comply with the 8mm spacing and 3750V 50/60 Hz dielectric requirements from hazardous voltage to operator accessible surfaces, between adjacent poles and from main circuits to auxiliary circuits per Publications EN 60950 and VDE 0805. Values from Line to Load Terminal based on Series Trip Circuit Breaker. Endurance Trip Free Trip Indication 10,000 ON-OFF operations @ 6 per minute; with rated Current and Voltage. All B-Series Circuit Breakers will trip on overload, even when Handle is forcibly held in the ON position. The operating Handle moves positively to the OFF position when an overload causes the breaker to trip. Physical Number of Poles Internal Circuit Config. Weight Standard Colors 1 - 6 poles at 30 Amps or less. 1 and 2 poles at 31 Amps thru 50 Amps. Series, (with or without auxiliary switch), Shunt and Relay with current or voltage trip coils, Dual Coil, Switch Only (with or without auxiliary switch). Approximately 65 grams/pole. (Approximately 2.32 ounces/pole.) Housing- Black; Actuator - See Ordering Scheme. Environmental Designed and tested in accordance with requirements of specification MIL-PRF- 55629 and MIL-STD-202 as follows: Shock Withstands 100 Gs, 6ms, sawtooth while carrying rated current per Method 213, Test Condition "I". Instantaneous and ultra-short curves tested @ 90% of rated current. Vibration Withstands 0.060" excursion from 10-55 Hz, and 10 Gs 55-500 Hz, at rated current per Method 204C, Test Condition A. Instantaneous and ultrashort curves tested at 90% of rated current. Moisture Resistance Method 106D, i.e., ten 24-hour cycles @ + 25C to +65C, 80-98% RH. Salt Spray Method 101, Condition A (90-95% RH @ 5% NaCl Solution, 96 hrs). Thermal Shock Method 107D, Condition A (Five cycles @ -55C to +25C to +85C to +25C). Operating Temperature -40 C to +85 C www.carlingtech.com B-Series Handle UL Recognized - Ordering Scheme B A 3 - B 0 - 10 - 450 - 1 B 1 - C 1 Series 2 Actuator 3 Poles 5 Aux/Alarm Switch 4 Circuit 6 Frequency & Delay 1 SERIES B 2 ACTUATOR1 A Handle, one per pole B Handle, one per multipole unit S Mid-Trip Handle, one per pole T Mid-Trip Handle, one per pole & Alarm Switch 3 POLES 1 One 2 Two 3 4 Three Four 4 CIRCUIT A2 Switch Only (No Coil) B Series Trip (Current) C Series Trip (Voltage) Shunt Trip (Current) D3 Shunt Trip (Voltage) E3 Relay Trip (Current) F3 G3 H3,4 5 AUXILIARY/ALARM SWITCH5 0 w/o Aux Switch 1 S.P.D.T., 0.093 Q.C. Term. 2 S.P.D.T., 0.110 Q.C. Term. 3 S.P.D.T., 0.139 Solder Lug 4 S.P.D.T., 0.110 Q.C. Term. (Gold Contacts) 5 6 FREQUENCY & DELAY 032 DC 50/60Hz, Switch Only 106 DC Instantaneous 11 DC Ultra Short 12 DC Short 14 DC Medium 16 DC Long 6 50/60Hz Instantaneous 20 21 50/60Hz Ultra Short 22 50/60Hz Short 24 50/60Hz Medium 26 50/60Hz Long J3,4 K3,4 6 7 8 9 30 31 32 34 36 427 447 467 527 547 567 5 6 Five Six Relay Trip (Voltage) Dual Coil with Shunt Trip Voltage Coil Dual Coil with Shunt Trip Voltage Coil (side terminal) Dual Coil with Relay Trip Voltage Coil S.P.S.T., 0.093 Q.C. Term.(Gold Contacts) S.P.S.T., 0.139 Solder Lug S.P.S.T., 0.110 Q.C. Term.(Gold Contacts) S.P.S.T., 0.187 Q.C. Term. S.P.D.T., 0.187 Q.C. Term. DC, 50/60Hz Instantaneous DC, 50/60Hz Ultra Short DC, 50/60Hz Short DC, 50/60Hz Medium DC, 50/60Hz Long 50/60Hz Short, Hi-Inrush 50/60Hz Medium, Hi-Inrush 50/60Hz Long, Hi-Inrush DC, Short,Hi-Inrush DC, Medium, Hi-Inrush DC, Long, Hi-Inrush Notes: 1 Actuator Code: A: Handle tie pin spacer(s) and retainers provided unassembled with multi-pole units. B: Handle location as viewed from front of breaker: 2 pole - left pole 3 pole - center pole 4 pole - two handles at center poles 5 pole - three handles at center poles 6 pole - four handles at center poles S: Handle moves to mid-position only upon electrical trip of the breaker. Available with circuit codes B, C, D, E, F, G, H and K. T: Handle moves to mid-position and alarm switch activates only upon electrical trip of the breaker. Available with circuit codes B & C. 2 Switch Only circuits, rated up to 50 amps and 6 poles, and only available with VDE Certification when tied to a protected pole (Circuit Code B, C, D or H.), For .02 to 30 amps, select Current Code 630. For 35 - 50 amps, select Current Code 650. 3 Available with Terminal Codes 1, 2 and 3. Current Rating limited to 30 amps maximum. 4 Consult factory for available Dual Coil options, as special catalog number is required. With Shunt construction, Dual Coils will trip instantaneously on line voltage. Dual coils require 30VA minimum power to trip and are rated for intermittent duty only. 5 Auxiliary Switch breakers with Series Trip and Switch Only circuits. On multi-pole breakers, one aux. switch is supplied, mounted in the extreme right pole. 6 Separate pole type voltage coils not rated for continuous duty. Available only with delay codes 10 and 20. 7 Available with Circuit Codes B & D only. VDE Certified to 30 amps. UL Recognized and CSA Accepted to 50 amps. 8 VDE Certification available with single pole breakers with DC Delay only. UL Recognition and CSA Accepted available in one and two pole breakers. 9 Screw Terminals are recommended on ratings greater than 20 amps. Ratings over 30 amps are only available with Terminal Codes 5, 9, G, H, M and Q. 10 VDE Certification up to 25 amps and UL Recognition and CSA Acceptance up to 30 amps, but not recommended over 20 amps. 11 Terminal Codes 3, 5 E and H (Bus Type) with VDE, are supplied with Lock Washers, and Terminal Code M (M6 Threaded Stud) with VDE is supplied with Lock and Flat Washers. These breakers are only VDE Certified when the washers are used. 12 VDE Cert. available up to 12 amps. UL Rec. & CSA Acceptance available up to 30 amps. 13 Single pole breakers with Terminal Code P (Printed Circuit Board) are available up to 30 amps with VDE Certification and 50 amps with UL Recognition and CSA Acceptance, with Circuit Codes A, B and C. Two pole breakers with Terminal Code P (Printed Circuit Board) are available up to 40 amps with UL Recognition and CSA Acceptance with Circuit Codes A, B and C. 14 Available with Actuator Codes A, S and T. 15 Available with voltage coils only. 16 Terminal Code Q not available with VDE approvals. www.carlingtech.com 7 Current Rating 8 Terminal 10 Mounting/ Barriers 9 Actuator Color 7 CURRENT RATING (AMPERES) 425 2.500 230 0.300 020 0.020 527 2.750 235 0.350 025 0.025 430 3.000 240 0.400 030 0.030 435 3.500 245 0.450 035 0.035 440 4.000 250 0.500 040 0.040 445 4.500 255 0.550 045 0.045 450 5.000 260 0.600 050 0.050 455 5.500 265 0.650 055 0.055 460 6.000 270 0.700 060 0.060 465 6.500 275 0.750 065 0.065 470 280 0.800 070 0.070 7.000 285 0.850 075 0.075 475 7.500 290 0.900 080 0.080 480 8.000 295 0.950 085 0.085 485 8.500 410 1.000 090 0.090 490 9.000 512 1.250 095 0.095 495 9.500 415 1.500 210 0.100 610 10.000 517 1.750 215 0.150 710 10.500 420 2.000 220 0.200 611 11.000 522 2.250 225 0.250 711 11.500 OR VOLTAGE COIL (NOMINAL RATED VOLTAGE)6 J12 12 AC A32 32 DC A06 6 DC J18 18 AC A48 48 DC A12 12 DC J24 24 AC A65 65 DC A18 18 DC J48 48 AC J06 6 AC A24 24 DC 8 TERMINAL9 110 Push-On 0.250 Tab (Q.C.) 2 Screw 8-32 w/upturned lugs 11 Screw 8-32 (Bus Type) 3 4 Screw 10-32 w/upturned lugs 11 Screw 10-32 (Bus Type) 5 6 Screw 8-32 w/upturned lugs and 30 bend 7 Screw 8-32 (Bus Type) and 30 bend 8 Screw 10-32 w/upturned lugs and 30 bend 9 Screw 10-32 (Bus Type) and 30 bend B Screw M5 w/upturned lugs C Screw M4 w/upturned lugs 9 ACTUATOR COLOR & LEGEND I-O ON-OFF Dual White A B 1 Black C D 2 Red F G 3 Green H J 4 Blue K L 5 Yellow M N 6 Gray P Q 7 Orange R S 8 E11 F G H L12 M11 P13 Q16 R S15 T 11 Agency Approval 612 712 613 614 615 616 617 618 620 622 624 625 630 6358 6408 6458 6508 12.000 12.500 13.000 14.000 15.000 16.000 17.000 18.000 20.000 22.000 24.000 25.000 30.000 35.000 40.000 45.000 50.000 J65 65 AC K20 120 AC L40 240 AC Screw M4 (Bus Type) Screw M5 w/upturned lugs and 30 bend Screw M5 (Bus Type) and 30 bend Screw M5 (Bus Type) 0.250 Q.C./ Solder Lug M6 Threaded Studs Printed Circuit Board Terminals Push-In Stud Screw M4 w/upturned lugs and 30 bend Push-On 0.110 Tab (Q.C.) Screw M4 (Bus Type) and 30 bend Legend Color Black White White White White Black Black Black 10 MOUNTING/BARRIERS MOUNTING STYLE BARRIERS Threaded Insert, 2 per pole 1 6-32 x 0.195 inches no A 6-32 X 0.195 inches (multi-pole units only) yes 2 ISO M3 x 5mm no B ISO M3 x 5mm yes Rectangular Adapter Plate with mounting centers of 2.062" [52.37mm] and Threaded insert, 2 per pole 314 6-32 x 0.225 inches no C14 6-32 X 0.225 inches (multi-pole units only) yes 14 4 ISO M3 x 6.5mm no 14 D ISO M3 x 6.5mm yes Front panel Snap-In, 0.75" [19.05mm] wide bezel 5 without Handleguard no 6 without Handleguard (multi-pole units only) yes Front panel Snap-In, 0.96" [24.48mm] wide bezel 7 without Handleguard, 1-pole units 0.96" wide; no multipole units have .105" bezel overhang on all sides 8 without Handleguard, 1-pole units 0.96" wide; yes (multi-pole units only) .105" bezel overhang on all sides 11 AGENCY APPROVAL C UL Recognized & CSA Accepted D VDE Certified, UL Recognized & CSA Accepted E TUV Certified, UL Recognized & CSA Accepted I UL Rec. STD 1077, UL Rec. 1500 (ignition protected), & CSA Accepted 61 B-Series Handle UL489A - Ordering Scheme B A 1 - B 0 - 14 - 450 - 1 B 1 - M T 1 Series 2 Actuator 3 Poles 5 Aux/Alarm Switch 4 Circuit 6 Frequency & Delay 1 SERIES B 2 ACTUATOR1 A Handle, one per pole B Handle, one per multipole unit S Mid-Trip Handle, one per pole T Mid-Trip Handle, one per pole & Alarm Switch 3 POLES 1 One 2 Two 3 Three 4 Four 4 CIRCUIT B Series Trip (Current) 5 AUXILIARY/ALARM SWITCH2 0 w/o Aux Switch 1 S.P.D.T., 0.093 Q.C. Term. 2 S.P.D.T., 0.110 Q.C. Term. 3 S.P.D.T., 0.139 Solder Lug 6 FREQUENCY & DELAY4 11 DC Ultra Short 12 DC Short 14 DC Medium 16 DC Long 7 8 9 S.P.S.T., 0.110 Q.C. Term.(Gold Contacts) S.P.S.T., 0.187 Q.C. Term. S.P.D.T., 0.187 Q.C. Term. 52 54 56 DC, Short,Hi-Inrush DC, Medium, Hi-Inrush DC, Long, Hi-Inrush 7 CURRENT RATING (AMPERES) 210 215 220 225 230 235 240 245 250 255 260 265 270 275 280 285 290 295 410 512 0.100 0.150 0.200 0.250 0.300 0.350 0.400 0.450 0.500 0.550 0.600 0.650 0.700 0.750 0.800 0.850 0.900 0.950 1.000 1.250 415 517 420 522 527 430 435 440 445 450 455 460 465 470 475 480 485 490 495 610 1.500 1.750 2.000 2.250 2.750 3.000 3.500 4.000 4.500 5.000 5.500 6.000 6.500 7.000 7.500 8.000 8.500 9.000 9.500 10.000 710 611 711 612 712 613 614 615 616 617 618 620 622 624 625 630 6353 6403 6453 6503 10.500 11.000 11.500 12.000 12.500 13.000 14.000 15.000 16.000 17.000 18.000 20.000 22.000 24.000 25.000 30.000 35.000 40.000 45.000 50.000 Notes: 1 Actuator Code: A: Handle tie pin spacer(s) and retainers provided unassembled with multi-pole units. S: Handle moves to mid-position only upon electrical trip of the breaker. T: Handle moves to mid-position and alarm switch activates only upon electrical trip of the breaker. 2 On multi-pole breakers, one auxiliary switch is supplied, mounted in the extreme right pole. 3 VDE Certification available with single pole breakers only. UL489A Listing available with one and two pole breakers. 4 Screw Terminals are recommended on ratings greater than 20 amps. Ratings over 30 amps are only available with Terminal Codes 5, 9, G, H, M and Q. 5 Terminal Code 1 (Push-On) available up to 25 amps with TUV or VDE Certification and 30 amps with UL489A Listing, but is not recommended over 20 amps. 6 Terminal Codes 3, 5 and H (Bus Type) with TUV or VDE, are supplied with Lock Washers, and Terminal Code M (M6 Threaded Stud) with TUV or VDE is supplied with Lock and Flat Washers. These breakers are only TUV or VDE Certified when the washers are used. 7 Single pole breakers with Terminal Code P (Printed Circuit Board) are available up to 30 amps with VDE Certification and 50 amps with UL489A Listing. 8 Terminal Code Q not available with VDE approvals. 62 7 Current Rating 8 Terminal 9 Actuator Color 8 TERMINAL4 15 Push-On 0.250 Tab (Q.C.) 2 Screw 8-32 w/upturned lugs 36 Screw 8-32 (Bus Type) 4 Screw 10-32 w/upturned lugs 56 Screw 10-32 (Bus Type) 6 Screw 8-32 w/upturned lugs and 30 bend 7 Screw 8-32 (Bus Type) and 30 bend 8 Screw 10-32 w/upturned lugs and 30 bend 9 ACTUATOR COLOR LEGEND ON-OFF White B Black D Red G Green J Blue L Yellow N Gray Q Orange S Dual 1 2 3 4 5 6 7 8 10 Mounting/ Barriers 9 B F G H M6 P7 Q8 11 Max. Appl. Rating 12 Agency Approval Screw 10-32 (Bus Type) and 30 bend Screw M5 w/upturned lugs Screw M5 w/upturned lugs and 30 bend Screw M5 (Bus Type) and 30 bend Screw M5 (Bus Type) M6 Threaded Stud Printed Circuit Board Terminals Push-In Stud Legend Color Black White White White White Black Black Black 10 MOUNTING/BARRIERS MOUNTING STYLE BARRIERS Threaded Insert, 2 per pole 1 6-32 x 0.195 inches no A 6-32 X 0.195 inches (multi-pole units only) yes 2 ISO M3 x 5mm no yes B ISO M3 x 5mm (multi-pole units only) Rectangular Adapter Plate with mounting centers of 2.062 inches and Threaded insert, 2 per pole 3 6-32 x 0.225 inches no yes C 6-32 X 0.225 inches (multi-pole units only) 4 ISO M3 x 6.5mm no D ISO M3 x 6.5mm (multi-pole units only) yes Front panel Snap-In, 0.75" wide bezel 5 without Handleguard no 6 without Handleguard (multi-pole units only) yes Front panel Snap-In, 0.96" wide bezel 7 without Handleguard, 1-pole units 0.96" wide; no multipole units have .105" bezel overhang on all sides 8 without Handleguard, 1-pole units 0.96" wide; yes (multi-pole units only).105" bezel overhang on all sides 11 MAXIMUM APPLICATION RATING M 80 DC 12 AGENCY APPROVAL T UL489A Listed K UL489A Listed, VDE Certified J UL489A Listed, TUV Certified www.carlingtech.com B-Series Handle UL489 Listed - Ordering Scheme B A 1 - B 0 - 24 - 450 - 1 B A - K G 1 Series 2 Actuator 3 Poles 4 Circuit 5 Aux/Alarm Switch 6 Frequency & Delay 1 SERIES B 2 Two 3 Three 3 4 CIRCUIT B Series Trip (Current) 5 AUXILIARY/ALARM SWITCH4 0 w/o Aux Switch 1 S.P.D.T., 0.093 Q.C. Term. 2 S.P.D.T., 0.110 Q.C. Term. 6 FREQUENCY & DELAY 21 AC Ultra Short 22 AC Short 24 AC Medium 26 AC Long 3 8 9 S.P.D.T., 0.139 Solder Lug S.P.S.T., 0.187 Q.C. Term. S.P.D.T., 0.187 Q.C. Term. 42 44 46 AC, Short,Hi-Inrush AC, Medium, Hi-Inrush AC, Long, Hi-Inrush 7 CURRENT RATING (AMPERES) 210 215 220 225 230 235 240 245 250 255 260 265 270 275 280 285 290 295 410 0.100 0.150 0.200 0.250 0.300 0.350 0.400 0.450 0.500 0.550 0.600 0.650 0.700 0.750 0.800 0.850 0.900 0.950 1.000 512 415 517 420 522 527 430 435 440 445 450 455 460 465 470 475 480 485 490 1.250 1.500 1.750 2.000 2.250 2.750 3.000 3.500 4.000 4.500 5.000 5.500 6.000 6.500 7.000 7.500 8.000 8.500 9.000 495 610 710 611 711 612 712 613 614 615 616 617 618 620 622 624 625 630 8 Terminal 9 Actuator Color 8 TERMINAL5 1 Push-On 0.250 Tab (Q.C.) 2 Screw 8-32 w/upturned lugs 3 Screw 8-32 (Bus Type) 4 Screw 10-32 w/upturned lugs 5 Screw 10-32 (Bus Type) 6 Screw 8-32 w/upturned lugs and 30 bend 7 Screw 8-32 (Bus Type) and 30 bend 8 Screw 10-32 w/upturned lugs and 30 bend 2 ACTUATOR1 A Handle, one per pole B Handle, one per mulit-pole unit S Mid-Trip Handle, one per pole T Mid-Trip Handle, one per pole & Alarm Switch 3 POLES2 1 One 7 Current Rating 9.500 10.000 10.500 11.000 11.500 12.000 12.500 13.000 14.000 15.000 16.000 17.000 18.000 20.000 22.000 24.000 25.000 30.000 9 ACTUATOR COLOR6 LEGEND ON-OFF White B Black D Red G Green J Blue L Yellow N Gray Q Orange S Dual 1 2 3 4 5 6 7 8 10 Mounting/ Barriers 9 A B F G H M Q 11 Max. Appl. Rating 12 Agency Approval Screw 10-32 (Bus Type) and 30 bend Load Terminal: #8 Screw/QC Combination. (Special Cat.#) Screw M5 w/upturned lugs Screw M5 w/upturned lugs and 30 bend Screw M5 (Bus Type) and 30 bend Screw M5 (Bus Type) M6 Threaded Stud Push-In Stud Legend Color Black White White White White Black Black Black 10 MOUNTING/BARRIERS MOUNTING STYLE BARRIERS9 Threaded Insert, 2 per pole A 6-32 X 0.195 inches yes B ISO M3 x 5mm yes Rectangular Adapter Plate with mounting centers of 2.062 inches 7 and Threaded insert, 2 per pole C 6-32 X 0.225 inches yes D ISO M3 x 6.5mm yes Front panel Snap-In, 0.75" wide bezel 6 without Handleguard yes Front panel Snap-In, 0.96" wide bezel 8 without Handleguard, 1-pole units 0.96" wide; yes .105" bezel overhang on all sides 11 MAXIMUM APPLICATION RATING C8 120/240VAC K 120VAC 12 AGENCY APPROVAL G UL489 Listed 3 UL489 Listed, TUV Certified Notes: 1 Actuator Code: A: Handle tie pin spacer(s) and retainers provided unassembled with multi-pole units. B: Handle location as viewed from front of breaker: 2 pole - left pole 3 pole - center pole S: Handle moves to mid-position only upon electrical trip of the breaker. Available with circuit codes B, C, D, E, F, G, H and K. T: Handle moves to mid-position and alarm switch activates only upon electrical trip of the breaker. Available with circuit codes B & C. 2 All poles must be same polarity. 3 3 pole units available only when 1 of 3 poles is neutral. 4 Auxiliary/Alarm Switch circuit must be same polarity as the main circuit. On multi-pole breakers, one aux. switch is supplied, mounted in the extreme right pole. 5 Screw Terminals are recommended on ratings greater than 20 amps. 6 Standard actuator colors are black and white. 7 Adapter plate with mounting centers of 2.082 inches. Available with Actuator Codes A, S and T. 8 Voltage Rating available with 2 and 3-pole breakers only. 9 Barriers supplied on multi-pole units only. www.carlingtech.com 63 B-Series Rocker UL489 Listed - Ordering Scheme B F 1 - B 0 - 24 - 630 - 2 3 A - K G 1 Series 2 Actuator 3 Poles 5 Aux/Alarm Switch 4 Circuit 6 Frequency & Delay 1 SERIES B Push-To-Reset, Visi-Rocker N Indicate OFF, vertical legend O Indicate OFF, horizontal legend Push-To-Reset , Single color R Vertical legend U Horizontal legend 2 ACTUATOR Two Color Visi-Rocker C Indicate ON, vertical legend D Indicate ON, horizontal legend F Indicate OFF, vertical legend G Indicate OFF, horizontal legend Single color J Vertical legend K Horizontal legend 3 POLES 1,2 1 One 2 3 Two 3 Three 4 CIRCUIT B Series Trip (Current) 5 AUXILIARY/ALARM SWITCH 4 0 w/o Aux Switch 1 S.P.D.T., 0.093 Q.C. Term. 2 S.P.D.T., 0.110 Q.C. Term. 3 S.P.D.T., 0.139 Solder Lug 6 FREQUENCY & DELAY 21 AC Ultra Short 22 AC Short 24 AC Medium 26 AC Long 7 8 9 S.P.S.T., 0.110 Q.C. Term.(Gold Contacts) S.P.S.T., 0.187 Q.C. Term. S.P.D.T., 0.187 Q.C. Term. 42 44 46 AC, Short,Hi-Inrush AC, Medium, Hi-Inrush AC, Long, Hi-Inrush Notes: 1 Multi-pole breakers have all breakers identical except when specifying Aux. switch and/or mixed poles, and have one rocker per breaker. 2 All poles must be same polarity. 3 3 pole units available only when1 of 3 poles is neutral. 4 On multi-pole breakers, one aux. switch is supplied, mounted in the extreme right pole. 5 Screw Terminals are recommended on ratings greater than 20 amps. 6 Terminal Code 1 (Push-On) available up to 30 amps, but are not recommended over 20 amps. 7 Dual legend = ON-OFF/I-O 8 Voltage Rating available with 2 and 3-pole breakers only. 9 Barriers supplied on multi-pole units only. 64 7 Current Rating 8 Terminal 9 Actuator Color 7 CURRENT RATING (AMPERES) 280 0.800 210 0.100 285 0.850 215 0.150 290 0.900 220 0.200 295 0.950 225 0.250 410 1.000 230 0.300 512 1.250 235 0.350 415 1.500 240 0.400 517 1.750 245 0.450 420 2.000 250 0.500 522 2.250 255 0.550 527 2.750 260 0.600 430 3.000 265 0.650 435 3.500 270 0.700 440 4.000 275 0.750 8 TERMINAL 5 16 Push-On 0.250 Tab (Q.C.) 2 Screw 8-32 w/upturned lugs 3 Screw 8-32 (Bus Type) 4 Screw 10-32 w/upturned lugs 5 Screw 10-32 (Bus Type) 6 Screw 8-32 w/upturned lugs and 30 bend 7 Screw 8-32 (Bus Type) and 30 bend 8 Screw 10-32 w/upturned lugs and 30 bend 9 ACTUATOR COLOR & LEGEND Actuator or Marking Visi-Color 7 ON-OFF Dual7 White B 1 Black D 2 Red G 3 Green J 4 Blue L 5 Yellow N 6 Gray Q 7 Orange S 8 10 MOUNTING/BARRIERS STANDARD ROCKER BEZEL Threaded Insert, 2 per pole A 6-32 X 0.195 inches B ISO M3 x 5mm ROCKERGUARD BEZEL Threaded Insert, 2 per pole C 6-32 x 0.195 inches D ISO M3 x 5mm 10 Mounting/ Barriers 12 11 Max. Appl. Agency Approval Rating 711 612 712 613 614 615 616 617 618 620 622 624 625 630 11.500 12.000 12.500 13.000 14.000 15.000 16.000 17.000 18.000 20.000 22.000 24.000 25.000 30.000 445 450 455 460 465 470 475 480 485 490 495 610 710 611 4.500 5.000 5.500 6.000 6.500 7.000 7.500 8.000 8.500 9.000 9.500 10.000 10.500 11.000 9 Screw 10-32 (Bus Type) and 30 bend Screw M5 w/upturned lugs Screw M4 w/upturned lugs Screw M5 w/upturned lugs and 30 bend Screw M5 (Bus Type) and 30 bend Screw M5 (Bus Type) B C F G H Marking Color: Single Color Visi-Rocker Black White White n/a White Red White Green White Blue Black Yellow Black Gray Black Orange BARRIERS9 yes yes yes yes 11 MAXIMUM APPLICATION RATING C8 120/240 VAC K 120 VAC 11 AGENCY APPROVAL G UL489 Listed www.carlingtech.com B-Series Flat Rocker UL489 Listed - Ordering Scheme B 1 1 - B 0 - 24 - 630 - 2 3 A - K G 1 Series 2 Actuator 3 Poles 5 Aux/Alarm Switch 4 Circuit 6 Frequency & Delay 2 ACTUATOR 1 Two Color Visi-Rocker 1 Indicate OFF, vertical legend 2 Indicate OFF, horizontal legend Single color 3 Vertical legend 4 Horizontal legend Push-To-Reset, Visi-Rocker 5 Indicate OFF, vertical legend 6 Indicate OFF, horizontal legend Push-To-Reset , Single color 7 Vertical legend 8 Horizontal legend 2 4 Two 3 Three 4 CIRCUIT B Series Trip (Current) 5 AUXILIARY/ALARM SWITCH 5 0 w/o Aux Switch 1 S.P.D.T., 0.093 Q.C. Term. 2 S.P.D.T., 0.110 Q.C. Term. 3 S.P.D.T., 0.139 Solder Lug 6 FREQUENCY & DELAY 21 AC Ultra Short 22 AC Short 24 AC Medium 26 AC Long 8 Terminal 9 Actuator Color 7 CURRENT RATING (AMPERES) 280 0.800 210 0.100 285 0.850 215 0.150 290 0.900 220 0.200 295 0.950 225 0.250 410 1.000 230 0.300 512 1.250 235 0.350 415 1.500 240 0.400 517 1.750 245 0.450 420 2.000 250 0.500 522 2.250 255 0.550 527 2.750 260 0.600 430 3.000 265 0.650 435 3.500 270 0.700 440 4.000 275 0.750 1 SERIES B 3 POLES 2,3 1 One 7 Current Rating 7 8 9 42 44 46 S.P.S.T., 0.110 Q.C. Term.(Gold Contacts) S.P.S.T., 0.187 Q.C. Term. S.P.D.T., 0.187 Q.C. Term. AC, Short,Hi-Inrush AC, Medium, Hi-Inrush AC, Long, Hi-Inrush 8 TERMINAL 6 17 Push-On 0.250 Tab (Q.C.) 2 Screw 8-32 w/upturned lugs 3 Screw 8-32 (Bus Type) 4 Screw 10-32 w/upturned lugs 5 Screw 10-32 (Bus Type) 6 Screw 8-32 w/upturned lugs and 30 bend 7 Screw 8-32 (Bus Type) and 30 bend 8 Screw 10-32 w/upturned lugs and 30 bend 9 ACTUATOR COLOR & LEGEND Actuator or Marking Visi-Color 8 ON-OFF Dual8 White B 1 Black D 2 Red G 3 Green J 4 Blue L 5 Yellow N 6 Gray Q 7 Orange S 8 10 Mounting/ Barriers 12 11 Max. Appl. Agency Approval Rating 711 612 712 613 614 615 616 617 618 620 622 624 625 630 11.500 12.000 12.500 13.000 14.000 15.000 16.000 17.000 18.000 20.000 22.000 24.000 25.000 30.000 445 450 455 460 465 470 475 480 485 490 495 610 710 611 4.500 5.000 5.500 6.000 6.500 7.000 7.500 8.000 8.500 9.000 9.500 10.000 10.500 11.000 9 Screw 10-32 (Bus Type) and 30 bend Screw M5 w/upturned lugs Screw M4 w/upturned lugs Screw M5 w/upturned lugs and 30 bend Screw M5 (Bus Type) and 30 bend Screw M5 (Bus Type) B C F G H Marking Color: Single Color Visi-Rocker Black White White n/a White Red White Green White Blue Black Yellow Black Gray Black Orange 10 MOUNTING/BARRIERS9 BARRIERS12 STANDARD ROCKER BEZEL,Threaded Insert, 2 per pole FLAT ROCKER ACTUATOR A 6-32 X 0.195 inches yes B ISO M3 x 5mm yes RECESSED OFF SIDE ROCKER ACTUATOR 10 E 6-32 x 0.195 inches yes F ISO M3 x 5mm yes PUSH-TO-RESET BEZEL,Threaded Insert, 2 per pole C 6-32 x 0.195 inches yes D ISO M3 x 5mm yes Notes: 1 Push-To-Reset actuators have OFF portion of rocker shrouded. 2 Multi-pole breakers have all breakers identical except when specifying Aux. switch and/or mixed poles, and have one rocker per breaker. 3 All poles must be same polarity. 4 3 pole units available only when1 of 3 poles is neutral. 5 On multi-pole breakers, one aux. switch is supplied, mounted in the extreme right pole. 6 Screw Terminals are recommended on ratings greater than 20 amps. 7 Terminal Code 1 (Push-On) available up to 30 amps, but are not recommended over 20 amps. 8 Color shown is visi and legend with remainder of rocker black, Dual = ON-OFF/I-O legend. 9 Legend on Push-to-reset bezel/shroud is white with single color actuator codes 7 & 8. Legend on Push-To-Reset bezel/shroud matches Visi-Color of rocker with actuator codes 5 & 6. 10 Recessed "off-side" available with actuator codes 1, 2, 3 & 4. Legends on rocker are available in ink stamping only. 11 Voltage rating available with 2 & 3-pole breakers only. 12 Barriers supplied on multi-pole units only. www.carlingtech.com 11 MAXIMUM APPLICATION RATING C11 120/240 VAC K 120 VAC 12 AGENCY APPROVAL G UL489 Listed 65 B-Series Handle - Circuit & Terminal Diagrams Notes: 1 All dimensions are in inches [millimeters]. 2 Tolerance .020 [.51] unless otherwise specified. 3 Alarm Switch available with .110 x .020 Q.C. & Solder Lug Terminals Only. 66 www.carlingtech.com B-Series Handle - Circuit & Terminal Diagrams Notes: 1 All dimensions are in inches [millimeters]. 2 Tolerance .020 [.51] unless otherwise specified. www.carlingtech.com 67 B-Series Handle - Front Panel Snap-In Mounting Style 5 Notes: 1 All dimensions are in inches [millimeters]. 2 Tolerance .020 [.51] unless otherwise specified. 68 www.carlingtech.com B-Series Handle - Front Panel Snap-in Mounting Style 5 Notes: 1 All dimensions are in inches [millimeters]. 2 Recommended panel thickness: .040 [1.02] to .100 [2.54]. 3 Tolerance .020 [.51] unless otherwise specified. www.carlingtech.com 69 B-Series Handle - Front Panel Snap-In Mounting Style 7 Notes: 1 All dimensions are in inches [millimeters]. 2 Recommended panel thickness .040 [1.02] to .100 [2.54]. 3 Tolerance .020 [.51] unless otherwise specified. 70 www.carlingtech.com B-Series PC Terminal Diagrams Notes: 1 All dimensions are in inches [millimeters]. 2 For pole orientation with horizontal legend, rotate front view clockwise 90. 3 Tolerance .010 [.25] unless otherwise specified. www.carlingtech.com 71 B-Series Rocker UL489 Listed - Form & Fit Drawings Notes: 1 Dimensions apply to all variations shown. Notice that circuit breaker line & load terminal orientation on indicate "OFF" is opposite of indicate "ON". 2 For pole orientation with horizontal legend, rotate front view clockwise 90. 3 All dimensions are in inches [millimeters]. 4 Tolerance .020 [.51] unless otherwise specified. 72 www.carlingtech.com B-Series Flat Rocker UL489 Listed - Form & Fit Drawings Notes: 1 All dimensions are in inches [millimeters]. 2 For pole orientation with horizontal legend, rotate front view clockwise 90. 3 Tolerance .020 [.51] unless otherwise specified. www.carlingtech.com 73