https://www.phoenixcontact.com/us/products/2905232
09/07/2016Page1/6
Type 3 surge protection plug-PLT-SEC-T3-24-P-2905232
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Replacement plug for type 3 device protection from the PLUGTRAB SEC T3 product range. 24 V nominal
voltage.
The illustration shows version PLT-
SEC-T3-230-P
Why buy this product
Varistor-based device protection
Can be used without separate backup fuse thanks to integrated overcurrent protection
Pluggable
Optical status indicator via LED
Plugs can be checked with CHECKMASTER 2
Key Commercial Data
Packing unit 1 STK
Weight per Piece (excluding packing) 40.000 g
Custom tariff number 85363030
Country of origin Germany
Technical data
Environmental Product Compliance
China RoHS No hazardous substances above threshold values
Dimensions
Height 60.9 mm
Width 17.5 mm
Depth 44.8 mm
Horizontal pitch 1 Div.
https://www.phoenixcontact.com/us/products/2905232
09/07/2016Page2/6
Type 3 surge protection plug-PLT-SEC-T3-24-P-2905232
Technical data
Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -40 °C ... 80 °C
Ambient temperature (storage/transport) -40 °C ... 80 °C
Altitude ≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation) 5 % ... 95 %
Shock (operation) 30g (half sinus / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation) 5g (10 ... 150 Hz/20 cycles/axis/X, Y, Z)
General
IEC test classification III
T3
EN type T3
SPD design Combination type
Mode of protection L-N
L-PE
N-PE
(L+) - (L-)
(L+/L-) - PE
Mounting type On base element
Color light grey RAL7035
Housing material PA 6.6-FR 20% GF
PA 6.6-FR
Degree of pollution 2
Flammability rating according to UL 94 V-0
Type Male
Number of positions 2
Surge protection fault message optical
Protective circuit
Nominal voltage UN24V AC(TN-S)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC34 V AC
34 V DC
Residual current IPE ≤ 5 µA
Nominal discharge current In (8/20) µs 1 kA
Standby power consumption PC≤ 30 mVA (at UREF)
≤ 50 mVA (at UC)
Reference test voltage UREF 27 V AC
https://www.phoenixcontact.com/us/products/2905232
09/07/2016Page3/6
Type 3 surge protection plug-PLT-SEC-T3-24-P-2905232
Technical data
Protective circuit
Combination wave UOC 2 kV
Voltage protection level Up (L-N) ≤ 0.25 kV
Voltage protection level Up (L-PE) ≤ 0.65 kV
Voltage protection level Up (N-PE) ≤ 0.65 kV
TOV behavior at UT (L-N) 50 V AC (5 s / withstand mode)
50 V AC (120 min / withstand mode)
TOV behavior at UT (L-PE) 50 V AC (5 s / withstand mode)
50 V AC (120 min / withstand mode)
Response time tA (L-N) ≤ 25 ns
Response time tA (L-PE) ≤ 100 ns
Response time tA (N-PE) ≤ 100 ns
Short-circuit current rating ISCCR 1.5 kA AC
1 kA DC
Connection data
Connection method pluggable
UL specifications
SPD Type 4CA
Maximum continuous operating voltage MCOV 34 V AC
34 V DC
Nominal voltage 24 V DC
Mode of protection L-N
L-G
N-G
(L+) - (L-)
(L+) - G
(L-) - G
Power distribution system 1
Nominal frequency 50/60Hz
Measured limiting voltage MLV (L-N) 290 V
Measured limiting voltage MLV (L-G) 560 V
Measured limiting voltage MLV (N-G) 560 V
Measured limiting voltage MLV (L+) - (L-) 290 V
Measured limiting voltage MLV (L+) - G 560 V
Measured limiting voltage MLV (L-) - G 560 V
Nominal discharge current In1 kA
https://www.phoenixcontact.com/us/products/2905232
09/07/2016Page4/6
Type 3 surge protection plug-PLT-SEC-T3-24-P-2905232
Technical data
Standards and Regulations
Standards/specifications IEC 61643-11 2011
EN 61643-11 2012
Drawings
Circuit diagram
L
N PE
Dimensional drawing
17,544,8
51,4
60,9
Classifications
eCl@ss
eCl@ss 5.1 27130801
eCl@ss 6.0 27130806
eCl@ss 8.0 27130806
eCl@ss 9.0 27130806
ETIM
ETIM 5.0 EC000942
Approvals
Approvals
Approvals
KEMA-KEUR / CCA / IECEE CB Scheme / UL Recognized / cUL Recognized / EAC / GL / cULus Recognized
Ex Approvals
UL Recognized / cUL Recognized / cULus Recognized
Approval details
https://www.phoenixcontact.com/us/products/2905232
09/07/2016Page5/6
Type 3 surge protection plug-PLT-SEC-T3-24-P-2905232
Approvals
KEMA-KEUR http://www.dekra-certification.com2173868.01
CCANTR-NL 7399
IECEE CB Scheme http://www.iecee.org/NL-35777
UL Recognized http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htmFILE E 330181
cUL Recognized http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htmFILE E 330181
EACRU C-DE.A*30.B01561
GLhttp://www.gl-group.com/newbuilding/approvals/index.html14588-15 HH
cULus Recognized http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
Accessories
Accessories
Device marking
Label-EML (20XE)R-0803452
Label, Roll, white, unlabeled, can be labeled with: THERMOMARK ROLL, THERMOMARK ROLL X1, THERMOMARK X,
THERMOMARK S1.1, Mounting type: Adhesive, Lettering field: continuous x 20 mm
https://www.phoenixcontact.com/us/products/2905232
09/07/2016Page6/6
Type 3 surge protection plug-PLT-SEC-T3-24-P-2905232
Accessories
Label-EML (20XE)R YE-0803453
Label, Roll, yellow, unlabeled, can be labeled with: THERMOMARK ROLL, THERMOMARK ROLL X1, THERMOMARK
X, THERMOMARK S1.1, Mounting type: Adhesive, Lettering field: continuous x 20 mm
End block
End clamp-CLIPFIX 35-3022218
Quick mounting end clamp for NS 35/7,5 DIN rail or NS 35/15 DIN rail, with marking option, width: 9.5 mm, color: gray
Marker pen
Marker pen-X-PEN 0,35-0811228
Marker pen without ink cartridge, for manual labeling of markers, labeling extremely wipe-proof, line thickness 0.35 mm
Additional products
Type 3 surge protection base element-PLT-SEC-T3-BE-2905557
Base element for protective plugs from the PLUGTRAB SEC product series with remote indication contact.
Phoenix Contact 2016 © - all rights reserved
http://www.phoenixcontact.com