Specifications
No. Items TAC-04-683 TAC-06-683 TAC-10-683 TAC-20-683 TAC-30-683
1Rated Voltage[V] AC Three Phase 500 (voltage range:528 max) 50/60Hz
2 Rated Current[A] 4 6 10 20 30
3 Test Voltage (Terminal-Mounting Plate) 2,000 VAC (Cutoff Current = 100mA), 1minute at room temperature and humidity
4 Isolation Resistance (Terminal-Mounting Plate) 500 VDC 100MW min at room temperature and humidity
5 Leakage current 250/500V 60Hz 2.5mA/5.0mA max
6 Voltage drop 1.5V max 1.0V max
7 Safety agency approval temperatures -25 to +85C (Refer to Derating Curve)
8 Operating temperature -40 to +85C (Refer to Derating Curve)
9 Operating humidity 20 to 95%RH (Non condensing)
10 Storage temperature/humidity -40 to +85C/20 to 95%RH (Non condensing)
11 Vibration 10 to 55Hz, 19.6m/s2(2G), 3min. Period, 1hour each X, Y and Z axis
12 Impact 196.1m/s2(20G), 11ms Once each X, Y and Z axis
13 Safety agency approvals UL1283, CSA C22.2 No.8 (C-UL) , DIN EN60939 VDE0565 Teil3-1, ENEC
14 Case size (without projection) /Weight
63X64X128 mm [2.48X2.52X5.04 inches] (WXHXD) /620g max (Option : -D refer to external view)
TAC series(4-30A)
Three phase input type(1-stage filter)
TAC -10 -683 -O
Ordering information
1 Model Name
2 Rated Current
3 Line to ground capacitor code:See table 1.1.
table1.1 Line to ground capacitor code
Code Leakage Current
(Input 250/500V 60Hz)
Line to ground
capacitor
(nominal value)
103 0.5mA/1.0mA max 10000pF
223 1.0mA/2.0mA max 22000pF
683 2.5mA/5.0mA max 68000pF
4 Options
D
:DIN rail installation type
1 2 3 4
Features of TAC series
Circuit Diagram Derating Curve
Ambient Temperature [C]
Load Factor [%]
70 80 90-20 40 50 60
20
0
-40 -30
100
80
60
40
High-attenuation type of common mode noise from 150kHz to 1MHz (1-stage filter)
- Three phase rated voltage 500 VAC (voltage range:528V max)
- Selectable leakage current value
- Push down type terminal block
R
*
The dimensions change when the option is set.
Refer to External view.
LOAD
Case
LINE
4
5
6
1
2
3
CY : Line to ground capacitor
CY
CY
: Mounting Plate
DIN rail installation type is optionThe terminal cover is retracted inside the unit
TA-1