I-2
Noise
Filter
NAC series
High-attenuation type of common mode noise from 150kHz to 1MHz
NAC -10 -472 -O
Ordering information
1Model Name
2Rated Current
3Line to ground capacitor code:See table 1.1.
table1.1 Line to ground capacitor code
Code Leakage Current
(Input 125/250V 60Hz)
Line to ground
capacitor
(nominal value)
681 75.5 A/ 150 A max 680pF
102 0.13mA/ 0.25mA max 1000pF
222 0.25mA/ 0.5 mA max 2200pF
332 0.38mA/ 0.75mA max 3300pF
472 0.5 mA/ 1.0 mA max 4700pF
*1 When the line to ground capacitor code is
different, the attenuation characteristic is
different.
4Options
D :DIN rail installation type
*
The dimensions change when the option is set.
Refer to External view.
1 2 3 4
Specifications
No. Items NAC-04-472 NAC-06-472 NAC-10-472 NAC-16-472 NAC-20-472 NAC-30-472
1 Rated Voltage[V] AC 1f 250 / DC250
2 Rated Current[A] 4 6 10162030
3 Test Voltage (Terminal-Mounting Plate) 2,500 VAC (Cutoff Current = 20mA), 1minute at room temperature and humidity
4 Isolation Resistance (Terminal-Mounting Plate) 500 VDC 100MW minute at room temperature and humidity
5 Leakage current 125/250V 60Hz 0.5mA/1.0mA max
6 Voltage drop 1.0V max
7 Safety agency approval temperatures -25 to +85C (Refer to Derating Curve)
8 Operating temperature -40 to +85C (Refer to Derating Curve)
9 Operating humidity 20 to 95%RH (Non condensing)
10 Storage temperature/humidity -40 to +85C/20 to 95%RH (Non condensing)
11 Vibration 10 to 55Hz, 19.6m/s2 (2G), 3min. Period, 1hour each X, Y and Z axis
12 Impact 196.1m/s2 (20G), 11ms Once each X, Y and Z axis
13 Safety agency approvals UL1283, CSA C22.2 No.8 (C-UL), DIN EN133200 VDE0565 Teil3-1, ENEC (At only AC input)
14 Case size (without projection) /Mass 53X41X92 mm (WXHXD) /300g max (Option : -D refer to external view)
Features of NAC series
Circuit Diagram Derating Curve
LINE
Case
: Mounting Plate
1
24
3
CY
CY
CY : Line to ground capacitor
LOAD
High-attenuation type of common mode noise from 150kHz to 1MHz
- Single Phase 250 VAC - Quick and easy push-down terminal
Just connect the wires, push down and tighten
the screws with a screwdriver
9050 60 70 80
20
0
-40 40-30 -20
100
80
60
40
55
Ambient Temperature [C]
Load Factor [%]
DIN rail installation type is optionThe terminal cover is retracted inside the unit