1
PHASE-OUT
Thermal-magnetic (TM and AS-line) AS168XAC3
https://www.schurter.com /PG20
Circuit Breakers
Manual Motor Controller / Circuit Breaker for Equipment thermal-magnetic, 3 poles
See below:
Approvals and Compliances
Description
- Thermal-magnetic circuit breaker
- High short circuit performance
- Availability of AC and DC in the same frame size
- DIN-Rail Mounting
Applications
- Industrial appliances
References
Last order possibility: 31.08.2018
Last delivery date: 30.09.2018
Weblinks
pdf datasheet, html-datasheet, General Product Information, Distributor-
Stock-Check, Detailed request for product, Product News
Technical Data
General data
Rated Voltage AC IEC : 420 V Y / 240 V; 50/60 Hz
UL/CSA : 480 V Y / 277 V; 50/60 Hz
Rated Voltage DC 65 V
Rated current 0.5 - 52 A , see approbations
Conditional short circuit capa-
city IEC 60934
Icn: AC 420 V Y/240 V / DC 65 V: 5 kA
(no fuse)
Conditional short circuit capa-
city UL 1077
Inc: AC 480 V Y/277 V: 10 kA (with fuse
class H/J, 4x rated current (min. 15 A))
Icn: AC 480 V Y/277 V: 5 kA (no fuse)
Icn: DC 65 V: 2 kA (no fuse)
Conditional short circuit capa-
city UL 508
Icn: AC 480 V Y/277 V: 5 kA (no fuse)
Degree of Protection from front side IP 40 acc. to IEC 60529
Lifetime 1 x Ir 6000 switching cycles
Dielectric Strength 50 Hz: > 2 kV
Impulse 1.2/50 μs
Vibration Resistance ± 0.75 mm @ 5 - 60 Hz
acc. to IEC 60068-2-6, test Fc
10 G @ 60 - 500 Hz
acc. to IEC 60068-2-6, test Fc
Insulation Resistance 250/440 VAC > 5 MΩ
Shock Resistance 30 G / 18 ms
acc. to IEC 60068-2-27, test Ea
Ambient temperature -10 °C to 55 °C
Weight 100 - 130 g
Tripping Type
Positively trip free
Actuation Type Manual ON/OFF
Permissible wire cross section 1.5 - 25 mm² / 16 - 4 AWG
Switched neutral
Rated Voltage AC 277 V
Rated current AC/DC 65 A
Function The switched neutral closes with ma-
nual closure of the poles and opens
automatically with thermal magnetic
tripping of the poles.
Add-on modules
Add-on modules Technical data for the additional module
see separate data sheet
Approvals and Compliances
Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in Details about
Approvals
2
PHASE-OUT
Thermal-magnetic (TM and AS-line)
AS168XAC3 https://www.schurter.com /PG20
Circuit Breakers
Approvals
The approval mark is used by the testing authorities to certify compliance with the safety requirements placed on electronic products.
Approval Reference Type: AS168X
Approval Logo Certificates Certification Body Description
VDE Approvals VDE VDE Certificate Number: 40005743
UL Approvals UL UL File Number: E216629 / E71572
UL Approvals UL UL File Number: E216629 / E71572
Product standards
Product standards that are referenced
Organization Design Standard Description
Designed according to IEC 60934 Circuit-breakers for equipment (CBE)
Designed according to UL508, UL1077 Standard for Supplementary Protectors for Use in Electrical Equipment
Designed according to UL 508 Standard for Industrial Control Equipment
Designed according to CSA C22.2 Supplementary Protectors
Application standards
Application standards where the product can be used
Organization Design Standard Description
Designed for applications acc. IEC/UL 60950 IEC 60950-1 includes the basic requirements for the safety of information
technologyequipment.
Compliances
The product complies with following Guide Lines
Identification Details Initiator Description
CE declaration of conformity SCHURTER AG The CE marking declares that the product complies with the applicable
requirements laid down in the harmonisation of Community legislation on
its affixing in accordance with EU Regulation 765/2008.
RoHS SCHURTER AG EU Directive RoHS 2011/65/EU
China RoHS SCHURTER AG The law SJ / T 11363-2006 (China RoHS) has been in force since 1 March
2007. It is similar to the EU directive RoHS.
REACH SCHURTER AG On 1 June 2007, Regulation (EC) No 1907/2006 on the Registration,
Evaluation, Authorization and Restriction of Chemicals 1 (abbreviated as
"REACH") entered into force.
3
PHASE-OUT
Thermal-magnetic (TM and AS-line) AS168XAC3
https://www.schurter.com /PG20
Circuit Breakers
Dimension [mm]
AS168X 3 pole
45
35
90
1.9
44.4
61.6
68.4
5.1
A)
26.6
52.5
B)
A) 35 mm DIN rail EN 50022
B) Max. torque
Wire crosssection Max. torque
1.5 ... 10 mm2 2.5 Nm
16 ... 25 mm2 3.1 Nm
AWG #16 ... 8 20 ... 22 lb –in
AWG #6 ... 4 26 ... 28 lb –in
AS168X 3 pole and switched neutral pole
45
35
90
1.9
44.4
61.6
68.4
5.1
26.6
70
A)
B)
A) 35 mm DIN rail EN 50022
B) Max. torque
Wire crosssection Max. torque
1.5 ... 10 mm2 2.5 Nm
16 ... 25 mm2 3.1 Nm
AWG #16 ... 8 20 ... 22 lb –in
AWG #6 ... 4 26 ... 28 lb –in
PHASE-OUT
4
PHASE-OUT
Thermal-magnetic (TM and AS-line)
AS168XAC3 https://www.schurter.com /PG20
Circuit Breakers
Diagrams
AS168X-CB1... AS168X-CB1...N
AS168X-CB1... / AS168X-ACBH1 AS168X-CB1... / AS168X-ACBH2
AS168X-CB1... / AS168X-ACBS1 AS168X-CB1... / AS168X-ACBS2
AS168X-CB1... / AS168X-ACBA
5
PHASE-OUT
Thermal-magnetic (TM and AS-line) AS168XAC3
https://www.schurter.com /PG20
Circuit Breakers
Symbol Standard Rated current Rated voltage AC Conditional short circuit
capacity Icn
Rated voltage DC Conditional short circuit
capacity Icn
UL 508
CSA C22.2 no. 14
0.5 - 52 A 480Y/277 V 5 kA - -
UL 1077 0.5 - 40 A 480 V 10 kA - -
CSA C22.2 no. 235 0.5 - 50 A 480 V 5 kA 65 V 2 kA
EN 60934 0.5 - 30 A 240/420 V 4.5 kA 65 V 4.5 kA
GB 17701 - - - - -
Effect of ambient temperature
AC-breaker are calibrated for an ambient temperature of +40°C, DC-breakers for +23°C. To determine the rated current for a lower or
higher ambient temperature, use a correction factor from the table below:
Ambient temperature [°C] Correction factor AC version Correction factor DC version
-20 0.78 0.80
-5 0.82 0.87
0 0.83 0.90
+10 0.87 0.95
+23 0.91 1.00
+30 0.95 1.05
+40 1.00 1.10
+50 1.05 1.20
+60 1.11 1.30
Example DC version: Rated current = 10 A; Environmental temperature = 50 °C; --> Correction factor = 1.2; Resulting current = 12 A
PHASE-OUT
6
PHASE-OUT
Thermal-magnetic (TM and AS-line)
AS168XAC3 https://www.schurter.com /PG20
Circuit Breakers
Ampere-Horsepower
Horsepower
(FLA & LRC Ratings Apply where no HP Rating is given)
Nominal Circuit Voltage, VAC
AS168X-CB Motor Nameplate
110-
120 200208 220-
240 265 277 380-
415
440-
480
Rated Current
(See Note #1)
FLA
Rating
Starting/
LRC Rating 2 pole1 pole
0.5A 0.5A
1A 1A
1.5A 1.5A
2A 2A
3A 3A
4A 4A
5A 5A
6A 6A
7A 7A
8A 8A
9A 9A
10A 10A
12A 12A
13A 13A
15A 15A
16A 16A
18A 18A
20A 20A
23A 23A
25A 25A
27A 27A
30A 30A
AS168X-CB
Nominal Circuit Voltage, VAC
110-120 200208 220-240 380-415 440-480
Rated Current
(See Note #1)
Note #1: For AC motor circuit nameplate FLA loads, AC general-use loades, AC resistance loads
FLA Starting/ 3 pole
0.5A 0.5A
1A 1A
1.5A 1.5A 1/2
2A 2A 3/4
3A 3A 1 1/ 2
4A 4A 2
5A 5A 3
6A 6A 3
7A 7A 3
8A 8A 5
9A 9A 5
10A 10A 5
12A 12A 7 1/ 2
13A 13A 7 1/ 2
15A 15A 10
16A 16A 10
18A 18A 10
20A 20A 10
23A 23A 15
25A 25A 15
27A 27A 20
30A 30A 20
Motor Nameplate
Horsepower
(FLA & LRC Ratings Apply where no HP Rating is given)
Rating LRC Rating
10A 1/2
12.5A 3/4
20A 1/2 1/2 1/2 1
25A 3/4 3/4 3/4 1 1/2
32A 1/2 1 1 1 2
32A 1/2 1 1 1/2 2
32A 3/4 1/2 1/2 2 3
46A 3/4 2 2 2 3
46A 1 2 2 2 3
46A 1 2 2 3 5
63.5A 1 1/2 3 3 3 5
63.5A 1 1/2 3 3 3 5
81A 2 3 3 3 7 1/2
81A 2 3 3 5 7 1/2
81A 2 5 5 5 10
81A 3 5 5 5 10
116A 3 5 5 7 1/2 10
116A 3 5 7 1/2 7 1/2 10
145A 3 7 1/2 7 1/2 7 1/2 15
145A 3 7 1/2 7 1/2 10 15
1/10
1/10 1/10 1/10 1/6
12A 1/8 1/6 1/6 1/4
18A 1/10 1/6 1/6 1/4 1/4 1/3 1/3 1/2
24A 1/8 1/4 1/3 1/3 1/3 1/3 1/2 1
30A 1/6 1/3 1/3 1/2 1/2 1/2 3/4 1 1/2
36A 1/4 1/2 1/2 1/2 3/4 3/4 1 2
42A 1/4 1/2 1/2 3/4 1 1 1 1/2 2
48A 1/3 3/4 3/4 1 1 1 2 2
54A 1/3 3/4 1 1 1 1 1/2 2 3
60A 1/2 1 1 1 1/2 1 1/2 2 2 3
72A 1/2 1 1/2 1 1/2 2 2 2 3 3
78A 1/2 1 1/2 1 1/2 2 2 2 3 3
90A 3/4 2 2 2 3 3 3 5
96A 1 2 2 2 3 3 3 5
108A 1 2 2 3 3 3 5 5
120A 1 1/2 3 3 3 3 3 5 5
138A 1 1/2 3 3 3 3 3 5 7 1/2
150A 2 3 3 3 5 5 5 7 1/2
162A 2 3 3 3 5 5 7 1/2 10
180A 2 3 3 5 5 5 7 1/2 10
7
PHASE-OUT
Thermal-magnetic (TM and AS-line) AS168XAC3
https://www.schurter.com /PG20
Circuit Breakers
Time-Current-Curves
Version F / Magnetic 3-5 xln
Time in Seconds
110 100 1000 x I
n
0,1ms
1ms
10ms
0,1s
1s
10s
100s
1000s
1hr
Multiple of Rated Current In
Reference Temperature +23°
Version G / Magnetic 6-10 xln
Time in Seconds
110 100 1000 x I
n
0,1ms
1ms
10ms
0,1s
1s
10s
100s
1000s
1hr
Multiple of Rated Current In
Reference Temperature +23°
Version H / Magnetic 12-20 xln
Time in Seconds
110 100 1000 x I
n
0,1ms
1ms
10ms
0,1s
1s
10s
100s
1000s
1hr
Multiple of Rated Current In
Reference Temperature +23°
Config. Code
AS168X-CB|1|DG|200|N|
The characters are placeholders for the correspondingly keys of selections from the key tables.
AS168X-CB| 1 |DG|200|N| = Number ofPoles
Number of Poles Configuration
key
3-pole 3
PHASE-OUT
8
PHASE-OUT
Thermal-magnetic (TM and AS-line)
AS168XAC3 https://www.schurter.com /PG20
Circuit Breakers
AS168X-CB|1| DG |200|N| = Tripping characteristics
Tripping characteristics Configuration
key
1.0-1.25xIn / 3-5xIn / 0.5-52 A F
1.0-1.25xIn / 6-10xIn / 0.5-52 A G
1.0-1.25xIn / 12-20xIn / 0.5-52 A H
AS168X-CB|1|DG| 200 |N| = Rated current
Rated current Configuration
key
0.05 A 005
1.0 A 010
1.5 A 015
2.0 A 020
3.0 A 030
4.0 A 040
5.0 A 050
6.0 A 060
7.0 A 070
8.0 A 080
9.0 A 090
10.0 A 100
Other rated currents on request
Rated current Configuration
key
12.0 A 120
15.0 A 150
16.0 A 160
18.0 A 180
20.0 A 200
23.0 A 230
25.0 A 250
27.0 A 270
30.0 A 300
32.0 A 320
35.0 A 350
40.0 A 400
45.0 A 450
50.0 A 500
52.0 A 520
Other rated currents on request
AS168X-CB|1|DG|200| N | = Switched neutral
Switched neutral Configuration
key
Switched neutral pole N
Variants
Tripping characteristics Rated current Switched neutral Config. Code Order Number
1.0-1.25xIn / 3-5xIn / 0.5-52 A 30.0 A AS168X-CB3F300 4420.0742
1.0-1.25xIn / 3-5xIn / 0.5-52 A 35.0 A AS168X-CB3F350 4420.0994
1.0-1.25xIn / 6-10xIn / 0.5-52 A 2.0 A AS168X-CB3G020 4420.0402
1.0-1.25xIn / 6-10xIn / 0.5-52 A 3.0 A AS168X-CB3G030 4420.0400
1.0-1.25xIn / 6-10xIn / 0.5-52 A 4.0 A AS168X-CB3G040 4420.0388
1.0-1.25xIn / 6-10xIn / 0.5-52 A 5.0 A AS168X-CB3G050 4420.0301
1.0-1.25xIn / 6-10xIn / 0.5-52 A 10.0 A AS168X-CB3G100 4420.0241
1.0-1.25xIn / 6-10xIn / 0.5-52 A 15.0 A AS168X-CB3G150 4420.0204
1.0-1.25xIn / 6-10xIn / 0.5-52 A 20.0 A AS168X-CB3G200 4420.0198
1.0-1.25xIn / 6-10xIn / 0.5-52 A 25.0 A AS168X-CB3G250 4420.0242
1.0-1.25xIn / 6-10xIn / 0.5-52 A 30.0 A AS168X-CB3G300 4420.0210
1.0-1.25xIn / 6-10xIn / 0.5-52 A 32.0 A AS168X-CB3G320 4420.0323
1.0-1.25xIn / 6-10xIn / 0.5-52 A 40.0 A AS168X-CB3G400 4420.0199
1.0-1.25xIn / 12-20xIn / 0.5-52 A 15.0 A AS168X-CB3H150 4420.0569
1.0-1.25xIn / 12-20xIn / 0.5-52 A 20.0 A AS168X-CB3H200 4420.0308
1.0-1.25xIn / 12-20xIn / 0.5-52 A 25.0 A AS168X-CB3H250 4420.0542
1.0-1.25xIn / 12-20xIn / 0.5-52 A 30.0 A AS168X-CB3H300 4420.0287
1.0-1.25xIn / 12-20xIn / 0.5-52 A 40.0 A AS168X-CB3H400 4420.0372
1.0-1.25xIn / 12-20xIn / 0.5-52 A 50.0 A AS168X-CB3H500 4420.0762
Most Popular.
Availability for all products can be searched real-time:https://www.schurter.com/en/Stock-Check/Stock-Check-SCHURTER
9
PHASE-OUT
Thermal-magnetic (TM and AS-line) AS168XAC3
https://www.schurter.com /PG20
Circuit Breakers
Packaging Unit 1 Pcs
The specifications, descriptions and illustrations indicated in this document are based on current
information. All content is subject to modifications and amendments. Information furnished is believed
to be accurate and reliable. However, users should independently evaluate the suitability and test each
product selected for their own applications.
19.02.2018
PHASE-OUT
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Schurter: