INTERFACE
IEG 45-3LA/400/21
Data sheet
1Description
Correct invoicing on the basis of a measuring instrument
can only be ensured if the three phases L1, L2, and L3 are
available.
IEG 45-3LA/400/21 voltage indication modules are used for
monitoring, for example, on a tariff changing board. These
modules indicate all three phases with high-accuracy
reading, even in case of reverse voltages.
These modules also have a floating PDT contact, thereby
offering the convenience of voltage monitoring through
remote querying.
1.1 Function
Figure 1 Circuit diagram
L1 failure: Glow lamp 1 does not light up,
relay drops
L2 failure: Glow lamp 2 does not light up,
relay drops
L3 failure: Glow lamp 3 does not light up,
relay drops
Failure of two
phase conductors: No glow lamps light up,
relay drops
L1
L2
L3
14
11
12
Make sure you always use the latest documentation.
It can be downloaded at www.phoenixcontact.net/download.
This data sheet is valid for all products listed on the following page:
Voltage indication module
IEG 45-3LA/400/21
104160_en_00 2
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: +49 - 52 35 - 30 0
PHOENIX CONTACT • P.O.Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717-944-1300
www.phoenixcontact.com
2Ordering data
3 Technical data
Description Type Order No. Pcs./Pkt.
Voltage indication module, with relay contact output, SPDT, 400 V AC
operating voltage
IEG 45-3LA/400/21 2963268 5
General data
Ambient temperature range -20°C +40°C
Rated insulation voltage according to EN 50178 300 V
Pollution degree according to EN 50178 2
Surge voltage category according to EN 50178 3, basic insulation
Mounting position Any
Installation Can be aligned without spacing
Width 45 mm
Height 47.5 mm
Length 75 mm
Connection data
Conductor cross-section, solid 0.2 mm² ... 4 mm²
Conductor cross-section, stranded 0.2 mm² ... 4 mm²
Conductor cross-section, AWG 24 - 12
Stripping length 8 mm
Connection method Screw connection
Input
Operating voltage UN (phase conductor/phase conductor) 400 V AC ±10%
Operating voltage range 0.93 … 1.1 x UN (at 20°C)
Indication range 100 V AC
Indication elements Glow lamp (green cover)
Current consumption of each light indicator at UN
L1
L2
L3
5.3 mA
5.3 mA
7.9 mA
Relay output
Contact type Single contact, SPDT
Contact material AgSnO
Maximum switching voltage 250 V AC/DC
Limiting continuous current 6 A
Output fuse 6.3 A (fast-blow)
Maximum interrupting rating (ohmic load)
At 24 V DC
At 250 V AC
144 W
1500 VA
Mechanical service life 2 x 107 cycles, approximately
Conformance/approvals
Conformance CE-compliant
Conformance with EMC Directive 2004/108/EC
Noise immunity according to EN 61000-6-2
Noise emission according to EN 61000-6-4
Conformance with Low Voltage Directive (LVD) 2006/95/EC
Electronic equipment according to EN 50178